Si30-408
Field Setting on Outdoor Unit
Field Settings from Remote Controller
61
2.1.3
Monitor Mode
↑
The numbers in the "No." column show the number of times to press the
.
Display contents of setting item No.0 “Various settings”
Explanation of Used Examples
* 1: Use when checking the checker system.
* 2: Check the numbers to connected indoor units for transmission
malfunction, etc.
* 3: Check the malfunction code.
* 4: Check the Retry contents.
* 5: Check when the operation pattern of outdoor unit is unusual.
No.
Setting items
LED display
Data
display
H1P H2P H3P H4P H5P H6P H7P
0
Various settings
9 7 7 7 7 7 7
Refer to
below
1
Address in batch cooling /
heating
9 7 7 7 7 7 8
Lower six
digits
2
Low noise · Demand address
9 7 7 7 7 8 7
4
AirNet address (*1)
9 7 7 7 8 7 7
5
The number of connected
indoor units (*2)
9 7 7 7 8 7 8
7
The number of connected zone
units (Outdoor, except BS)
9 7 7 7 8 8 8
8
The number of outdoor units
9 7 7 8 7 7 7
11
The number of zone units
(Outdoor, except BS)
9 7 7 8 7 8 8
Lower six
digits
12
The number of terminals
9 7 7 8 8 7 7
Lower
four
digits
(upper)
13
The number of terminals
9 7 7 8 8 7 8
Lower
four
digits
(lower)
14
Content of malfunction
(latest)
(*3)
8 7 7 8 8 8 7
Refer to
page
104,
Malfunc-
tion code
list in the
chapter
of
trouble-
shooting.
15
Content of malfunction
(one cycle before)
8 7 7 8 8 8 8
16
Content of malfunction
(two cycles before)
8 7 8 7 7 7 7
20
Content of retry (latest)
(*4)
8 7 8 7 8 7 7
21
Content of retry (one
cycle before)
8 7 8 7 8 7 8
22
Content of retry (two
cycles before)
8 7 8 7 8 8 7
Pressing the MODE button (BS1)
while in "Setting mode 1" will enter
"Monitor mode".
<Selection of Setting Item>
Press the SET button (BS2) and set
the LED display to setting items.
<Check the set contents>
Pressing the RETURN button (BS3)
will display respective data by LED.
Pressing the RETURN button (BS3)
will put the system into the initial state
of "Monitor mode".
* Pressing the MODE button (BS1) will
return the system to "Setting mode 1".
SET button (BS2)
Setting of EMG
operation/ backup
operation (*5)
ON
9 7 7 8 7 7 7
OFF
9 7 7 7 7 7 7
Setting of defrost
selection
Short
time
9 7 7 7 8 7 7
Middle
time
9 7 7 7 9 7 7
Long
time
9 7 7 7 7 7 7
Te setting
H
9 7 7 7 7 8 7
M
9 7 7 7 7 9 7
L
9 7 7 7 7 7 7
Tc setting
H
9 7 7 7 7 7 8
M
9 7 7 7 7 7 9
L
9 7 7 7 7 7 7