Adaptors for Connection of Air Conditioners
Si30-408
220
Appendix
3. To carry out operation mode switching and demand control simultaneously
You can carry out operation mode switching and demand control simultaneously by setting
function switch SS1 on the adaptor to "BOTH." Only one address, however, can be set on the
adaptor, so the "operation mode switch unit" and "demand control unit" are the same.
Set the COOL/HEAT address, demand address and low noise address, or both as needed.
Note 2: The outdoor unit can have an independent "COOL/HEAT address" and "demand
address". You can therefore set the "operation mode group" and "demand control
group" to different ranges.
Factory set to "BOTH".
SS1
BOTH
C/H
DE
FUNCTION
Left
(BOTH)
Middle
(C/H)
Right
(DE•LOW NOISE)
Fig. 1
Setting of 5-bit cool/heat
address by DS1,2
Designate and set cool/heat
addresses 0-31 for each
operation mode switch unit.
No. 0
No. 7
No. 8
No. 15
No. 16
No. 31
: OFF
: ON
Upper 2
bits DS2
C/H
LOWER
ADRESS
CENTRAL
NO.
DEMAND CONTROL ADRESS
Lower 3
bits DS1