Si30-408
Field Settings from Remote Controller
Field Settings from Remote Controller
53
Method to Specify the Indoor Unit No.
In indoor units where group control is made, mode No. 43 (turn on the forcedly fan) is used to
specify the location of installation of the indoor unit with a certain No.
(When the malfunction occurs within remote control group, above method can also be utilized to
specify the indoor unit which has the trouble.)
Procedure
Turn on the power supply.
���
Turn on the power supply of indoor unit (+ rate control unit).
(No settings can be made without turning on the power supply.)
Check the installation and electric wirings once again before turning on the power supply.
(When the power supply is turned on, there may be cases where any operation cannot be
accepted with "88" displayed once.)
���
Put the system into setting mode
Press the
button for a period of 4 seconds or more, and put the system into "Field
Setting Mode".
���
Put the system into service mode.
Press the
button for a period of 4 seconds or more once again.
���
Select the mode No.
Select the mode No. 43 using the
button. (Unit No. 1-16)
���
Select the unit No.
Select the unit No. using the
button. (Unit No. 1-16)
���
The fan in relevant indoor units starts to operate.
���
Turn the system into the normal mode.
Press the
button.
1-00
1
43
SETTING
AIR CONDITIONER
UNIT No.
TEST
(VL042)
4
Mode No.
7
3
2
5
Unit No.
Field Set Mode
Group No.