Adaptors for Connection of Air Conditioners
Si30-408
208
Appendix
5.1.5 Combined use with Centralized Controllers
The combined use of the wiring adaptor for electrical appendices (2) and the centralized
controllers is enabled by the setting method shown below under the limited conditions.
Setting method
Cut the spare jumper (J5) connected to wiring adaptor for electrical appendices (2). (If the
use conditions shown below are not satisfied, however, the adapter may not normally
function.)
Use conditions
1. If the wiring adaptor for electrical appendices (2) is used by following methods, the combined
use will be enabled.
• Operation and malfunction with the wiring adaptor for electrical appendices (2)
• Forcedly thermostat OFF control with the wiring adaptor for electrical appendices (2)
(For mode settings, only use the input B in Positions C and E.)
• Temperature setting shift control with the wiring adaptor for electrical appendices (2)
(For mode settings, only use the input B in Positions D and F. This control, however, is
disabled in combined use with the temperature setting unit (DPF201A53).)
• The operation mode of the centralized controllers is set to "Individual (last pressing
priority)" and the control mode of the wiring adaptor for electrical appendices (2) is also set
to "Individual (last pressing priority)".
2. If the system is adaptable to telecommunication with the use of the wiring adaptor for
electrical appendices (2) and further the centralized remote controllers are used by the
methods listed in table below.
CN1
CN2
J5
W1
W2
W3
W4
B1 B2 BC A
+
A
-
Spare 1
Cut this jumper.
To terminal blocks
(P1 and P2) of
indoor unit
To indoor unit
VRV: X18
KRP4A51~54
Model
Conditions
Central remote controller
(DCS302C61)
No forcedly stop input is used and further this controller is used in
any of operation mode 6, 7, 16, and 17.
Unified ON / OFF controller
(DCS301B61)
No forcedly stop input is used and further this controller is used in
the operation mode set to “last pressing priority”.
Schedule timer
(DST301B61)
This timer used in operation code set to “last pressing priority”.
Unified adaptor for
computerized control
(DCS302A52)
This adapter is used in input mode set to Position 3.
Parallel interface Basic unit
(DPF201A51)
No forcedly stop input is used and further this interface is used in
operation mode set to Position 1.
Data station
(DDS501A51)
No forcedly stop input is used and further no system forcedly stop
command or remote controller inhibited command is used.