Field Setting on Outdoor Unit
Si30-408
56
Field Settings from Remote Controller
2. Field Setting on Outdoor Unit
Using pushbutton switches on the PC board enables a variety of settings.
However, setting items and setting No. etc. are different according to the model.
The following explanation was made based on the representative models of RX(Y)(Q) ~ M. For
further details, refer to each service manual of applicable model of the target machine.
* For the multi-outdoor system, make setting using the master unit.
(Setting using the slave unit is not valid.)
The following 3 setting modes are available.
1. Setting mode 1 (H1P: OFF)
Initial state (while in normal operation): Used to make setting of the method of "Cool/Heat
selection".
This mode is displayed while in "malfunction", "low noise control", and "demand control" as
well.
2. Setting mode 2 (H1P: ON)
This mode is used to make changes of operating conditions or settings of a variety of
addresses, mainly for service work.
3. Monitor mode (H1P: Blinking)
This mode is used to check the contents set in Setting mode 2.
Procedure for Changing Mode
Steps to Change Mode
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
(V2760)
Setting mode 1
Monitor mode
H1P
Push the BS1(MODE button)
one time.
Blinking
MODE
MODE
Off
H1P
Setting mode 2
MODE
On
H1P
Push and hold the BS1
(MODE button) for 5 seconds.
Push the BS1(MODE button) one time.
(Normal)
(V2761)
Using the MODE button, the modes can be changed as follows.
Check item selection (Set)
Contents display
Monitor mode
Setting mode 1
(Initial condition)
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Setting item selection (Set)
Setting mode 2
(Set): Select mode with BS2 (SET button) in each selection step.
Setting condition
selection (Set)
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS1
(MODE button).
Press BS1
(MODE button).
Press BS1(MODE button).
Press BS1 (MODE button) for more than 5 sec.
(V2762)