Adaptors for Connection of Air Conditioners
Si30-408
206
Appendix
5.1.3 Settings of
Remote Control Mode Selector Switch (RS1)
Notes:
1. In Positions 7 to A while in input B, using constant input will put the system into forcedly
stop (disregard for input A). Furthermore, in Position B while in input B, the constant input
will be disabled.
2. For the overview of “Function” listed in table above, refer to information in the following
section.
3. For instantaneous input, set ON time to 200 msec or more
Position
Function
Contents of operations in input mode A or B
Input A (Between B1 and Bc)
Input B (Between B2 and Bc)
0
Disregard for input
—
—
1
Remote controller
inhibited
ON to operate, OFF to stop the system
ON to stop the system (Remote controller
inhibited)
OFF to permit input A
2
Centralized priority
ON to operate (Remote controller permitted),
OFF to stop the system (Remote controller
inhibited))
3
Remote controller
permitted / inhibited
Same as Position 1 (Only Remote controller stop
is permitted at all times.)
4
Remote controller
permitted / inhibited &
OFF
ON to permit the remote controller, OFF to inhibit
the remote controller and stop.
5
Remote controller
inhibited
Operate / Stop (Cyclic) (Instantaneous input)
6
Last pressing priority
Same as Position 5 (Only Remote controller is
permitted at all times.)
7
Remote controller
inhibited
ON to operate the system (Instantaneous input)
ON to stop the system (Instantaneous input)
8
Centralized priority
ON to operate the system (Remote controller
permitted) (Instantaneous input)
ON to stop (Remote controller inhibited)
(Instantaneous input)
9
Remote controller stop
permitted
Same as Position 7 (Only Remote controller stop
is permitted at all times.)
Same as Position 7
A
Remote controller
permitted / inhibited &
OFF
ON to operate the system (Remote controller
permitted) (Instantaneous input)
ON to stop the system (Remote controller
inhibited) (Instantaneous input)
B
Last pressing priority
Same as Position 7 (Only Remote controller is
permitted at all times.)
Same as Position 7
C
Position 5 + Energy
saving control
Same as Position 5
ON to put the system into forcedly thermostat OFF
D
Position 5 + Room
temperature setting shift
ON to operate the system in room temperature
setting shift mode*
E
Position 6 + Energy
saving control
Same as Position 6
ON to put the system into forcedly thermostat OFF
F
Position 6 + Room
temperature setting shift
ON to operate the system in room temperature
setting shift mode*