18
|
Piping installation
Installer and user reference guide
71
RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452191-1B – 2020.10
(c) If the outdoor unit is connected to VRV DX indoor units only, the height difference
between indoor units (H2) can be increased to 30 m. In all other cases, the H2 is
limited to 15 m.
If
Then
The outdoor unit is
positioned higher than the
indoor units
▪
Minimum connection ratio: 80%
▪
Size up the liquid piping (refer to
65] for more information)
▪
Activate the outdoor unit setting. Refer to the
service manual for more information.
The outdoor unit is
positioned lower than the
indoor units
▪
Minimum connection ratio varies according to the
height difference between outdoor and indoor
units:
-
40~60 m: 80%
-
60~65 m: 90%
-
65~80 m: 100%
-
80~90 m: 110%
▪
Size up the liquid piping (refer to
65] for more information)
▪
Activate the outdoor unit setting. Refer to the
service manual for more information.
▪