18.1.2 Refrigerant piping insulation
▪
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
▪
Insulation thickness
Ambient temperature
Humidity
Minimum thickness
≤30°C
75% to 80% RH
15 mm
>30°C
≥80% RH
20 mm