EDUS341411-N
Installation Manual
Installation of Outdoor Units
31
3P362438-1B
21
3P362438-1B English
r 1WVUKFGVJGWPKVUVJGVTCPUOKUUKQPYKTKPIOWUVDGƂPKUJGFUKOWNVC
-
PGQWUN[YKVJVJGNQECNTGHTKIGTCPVRKRKPICPFYQWPFYKVJVCRGƂGNF
UWRRN[CUUJQYPKPVJGƂIWTGDGNQY
1
2
3
4
5
1
Liquid pipe
2
Gas pipe
3
Transmission wiring
4
Insulation material
5
Finishing tape
r
For multi system:
1
Transmission wiring between outdoor units in the same piping
system must be connected to terminals Q1 and Q2 (TO MULTI
UNIT).
Connecting the wires to the F1, F2 (TO OUT/D UNIT) terminals
results in system malfunction.
2
Wiring to other systems should be connected to terminals F1 and
F2 (TO OUT/D UNIT) on the printed circuit board of the master
unit. The outdoor unit that connects transmission wiring to indoor
unit is the master unit. The others are sub unit.
9.5. Power wiring connection procedure
r
Be sure to connect the power supply wiring to the power supply ter-
minal block and hold it in place using the included clamp as shown
KPVJGƂIWTGDGNQY
r
The L1, L2 and L3 phases of the power wiring should be secured
separately to the hook using the included clamp (1).
r
The ground wiring should be bound to the power wiring using the
included clamp (1) to prevent outside force from being applied to the
terminal area.
RXYQ72T
1
7
8
10
11
9
4
5
6
2
3
RXYQ96-168T
7
9
10
11
1
4
6
5
2
3
8
1
Power supply
/1&'.6;&0s8*\
/1&'.66,7s8*\
2
Branch switch, Overcurrent breaker
3
Ground wire
4
%QPVTQNDQZ
5
(Only RXYQ – TYDN)
%QPVTQNDQZ
6
(Only RXYQ – TYDN)
&QPQVQRGPVJGEQPVTQNDQZEQXGT
(There are no work when installation.)
7
Attach insulation sleeves
8
Power supply terminal block
9
Ground terminal
10
Clamp (1) (accessory)
11
Vinyl tube (accessory)
CAUTION
r
Be sure to use crimp-style terminal with insulating sleeves for con-
PGEVKQPU5GGVJGƂIWTGDGNQY
Crimp-style terminal
Insulating sleeve
Power wire
r (QTYKTKPIWUGVJGFGUKIPCVGFRQYGTYKTGCPFEQPPGEVƂTON[VJGP
UGEWTGVQRTGXGPVQWVUKFGRTGUUWTGDGKPIGZGTVGFQPVJGVGTOKPCN
board.
r
Use an appropriate screwdriver for tightening the terminal screws.
A screwdriver with a small head will strip the head and make proper
tightening impossible.
r
Over-tightening the terminal screws may break them.
See the following table for the tightening torque of the terminal
screws.
Screw size
Tightening torque
M8 Power terminal
4.20-5.09 ft
x
lbf (5.7-6.9 N
x
m)
M8 Ground terminal
7.15-8.63 ft
x
lbf (9.7-8.63 N
x
m)
r
When pulling the ground wire out, wire it so that it comes through
VJGEWVQWVUGEVKQPQHVJGEWRYCUJGT5GGVJGƂIWTGDGNQY#P
improper ground connection may prevent a good ground from being
achieved.
Crimp-style terminal
Cut out section
Cup washer
r
When 2 wires are connected to a single terminal, connect them so
that the rear sides of the crimp contacts face each other. Also, make
sure the thinner wire is on top, securing the 2 wires simultaneously
to the resin hook using the included clamp (1).
Crip style
terminal
Wire : narrow
Terminal
block
Wire : thick
Resin hook
9.6. Procedure for Wiring Inside Units
r 4GHGTTKPIVQVJGƂIWTGDGNQYUGEWTGCPFYKTGVJGRQYGTCPFVTCPU
-
mission wiring using the included clamp (1) and (2).
r
Wire so that the ground wiring does not come into contact with the
compressor lead wiring.
If they touch, this may have an adverse effect on other devices.
r
The transmission wiring must be at least 2 in. (51 mm) away from
the power wiring.
r
Make sure all wiring
U
do not contact to the pipes (hatching parts in
VJGDGNQYƂIWTG
Summary of Contents for VRV IV RXYQ TTJU Series
Page 1: ...EDUS341411 N Installation...
Page 62: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 63 3P161697D...
Page 66: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 67 C 3P113151C 7 8 1 1 1 8...
Page 67: ...REFNET Joint and Header EDUS341411 N 68 Installation of Outdoor Units KHRP26M73HU 3P185500...
Page 68: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 69 3P185500...
Page 70: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 71 1P218719...
Page 71: ...REFNET Joint and Header EDUS341411 N 72 Installation of Outdoor Units 1P218719...
Page 72: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 73 1P218720...
Page 73: ...REFNET Joint and Header EDUS341411 N 74 Installation of Outdoor Units 1P218720...
Page 75: ...REFNET Joint and Header EDUS341411 N 76 Installation of Outdoor Units 1P280278A...
Page 76: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 77 1P280278A...
Page 77: ...REFNET Joint and Header EDUS341411 N 78 Installation of Outdoor Units 1P280279...
Page 79: ...Caution Label EDUS341411 N 80 Installation of Outdoor Units 2P361359C...
Page 80: ...EDUS341411 N Caution Label Installation of Outdoor Units 81 3P357947A...
Page 81: ...Caution Label EDUS341411 N 82 Installation of Outdoor Units 3P357947A...
Page 83: ...Caution Label EDUS341411 N 84 Installation of Outdoor Units 1P361833B...
Page 84: ...EDUS341411 N Caution Label Installation of Outdoor Units 85 1P361833B...
Page 85: ...Caution Label EDUS341411 N 86 Installation of Outdoor Units 1P361833B...
Page 86: ...EDUS341411 N Caution Label Installation of Outdoor Units 87 1P361833B...
Page 87: ...Caution Label EDUS341411 N 88 Installation of Outdoor Units 1P361833B...
Page 88: ...EDUS341411 N Caution Label Installation of Outdoor Units 89 1P361833B...
Page 89: ...Caution Label EDUS341411 N 90 Installation of Outdoor Units 3P357946A...
Page 90: ...EDUS341411 N Caution Label Installation of Outdoor Units 91 3P357946A...