Installation Manual
EDUS341411-N
48
Installation of Outdoor Units
3P362438-1B
38
3P362438-1B English
No matter which control is selected, variations on the behavior of the
system are still possible due to protection controls to keep the unit
operating under reliable conditions. The intentional target, however,
KUƂZGFCPFYKNNDGWUGFVQQDVCKPVJGDGUVDCNCPEGDGVYGGPGPGTI[
consumption and comfort, depending on the application type.
15.4. Test
operation
#HVGTKPUVCNNCVKQPCPFQPEGVJGƂGNFUGVVKPIUCTGFGƂPGFVJGKPUVCNNGT
is obliged to verify correct operation. Therefore a test run must be
performed according to the procedures described below.
15.4.1.
Precautions before starting test operation
During test operation, the outdoor unit and the indoor units will start
up:
r /CMGUWTGVJCVVJGRTGRCTCVKQPUQHCNNKPFQQTWPKVUCTGƂPKUJGFƂGNF
piping, electrical wiring, air purge, etc.). See installation manual of
the indoor units for details.
CAUTION
&QPQVKPUGTVƂPIGTUTQFUQTQVJGTQDLGEVUKPVQVJGCKTKPNGVQTQWVNGV
When the fan is rotating at high speed, it will cause injury.
CAUTION
Do not perform the test operation while working on the indoor units.
When performing the test operation, not only the outdoor unit, but the
connected indoor unit will operate as well.
Working on an indoor unit while performing a test operation is danger-
ous.
CAUTION
r
During tests never pressurize the appliances with a pressure higher
VJCPVJGOCZKOWOCNNQYCDNGRTGUUWTGCUKPFKECVGFQPVJGPCOG
-
plate of the unit).
r +HTGHTKIGTCPVICUNGCMUXGPVKNCVGVJGCTGCKOOGFKCVGN[6QZKEICU
OC[DGRTQFWEGFKHTGHTKIGTCPVICUEQOGUKPVQEQPVCEVYKVJƂTG
r
Never directly touch any accidental leaking refrigerant. This could
result in severe wounds caused by frostbite.
r
Test run is possible for ambient temperatures between -4°F and
95°F (-20°C and 35°C).
DANGER: DO NOT TOUCH PIPING AND ITERNAL PARTS
5GG5CHGV[EQPUKFGTCVKQPUQPRCIG|K
DANGER:ELECTRICAL SHOCK
5GG5CHGV[EQPUKFGTCVKQPUQPRCIG|K
r
Provide a logbook and machine card.
In accordance with the applicable legislation, it may be necessary to
provide a logbook with the equipment containing at least: informa-
tion on maintenance, repair work, results of tests, stand-by periods,
etc.
INFORMATION
0QVGVJCVFWTKPIVJGƂTUVTWPPKPIRGTKQFQHVJGWPKVTGSWKTGFRQYGTKP
-
put may be higher. This phenomenon originates from the compressor
that requires a 50 hour run elapse before reaching smooth operation
and stable power consumption. Reason is that the scroll is made out
of iron and that it takes some time to smooth the surfaces that make
contact.
NOTE
To protect the compressor, be sure to turn on the power supply 6
hours before starting operation.
15.4.2. Test
operation
The procedure below describes the test operation of the complete
system. This operation checks and judges following items:
r
Check of wrong wiring (communication check with indoor units).
r
Check of the stop valves opening.
r
Judgment of piping length.
Mini-split indoor units are present in the system, above 2 checks will
not be performed.
On top of this system test operation, indoor units operation should
also be checked separately.
r /CMGUWTGVQECTT[QWVVJGU[UVGOVGUVQRGTCVKQPCHVGTVJGƂTUV
installation. Otherwise, the malfunction code U3 will be displayed on
the user interface and normal operation or individual indoor unit test
run cannot be carried out.
r
Abnormalities on indoor units cannot be checked for each unit
UGRCTCVGN[#HVGTVJGVGUVQRGTCVKQPKUƂPKUJGFEJGEMVJGKPFQQT
units one by one by performing a normal operation using the user
interface. Refer to the indoor unit installation manual for more de-
tails concerning the individual test run.
INFORMATION
r
It may take 10 minutes to achieve a uniform refrigerant state before
the compressor starts.
r
During the test operation, the refrigerant running sound or the mag-
netic sound of a solenoid valve may become loud and the display
indication may change.
These are not malfunctions.
Procedure
1
Close all front panels in order to not let it be the cause of misjudg-
ment.
2
/CMGUWTGCNNƂGNFUGVVKPIU[QWYCPVCTGUGVUGG/QPKVQTKPI
HWPEVKQPCPFƂGNFUGVVKPIUQPRCIG|
3
Turn ON the power to the outdoor unit and the connected indoor
units.
NOTE
Be sure to turn on the power 6 hours before operation in order to have
power running to the crankcase heater and to protect the compressor.
4
/CMGUWTGVJGFGHCWNVKFNGUKVWCVKQPKUGZKUVKPIUGG1RGTCV
-
ing the push buttons and DIP switches on the logic board on
RCIG|2WUJ$5HQTUGEQPFUQTOQTG6JGWPKVYKNNUVCTVVGUV
operation.
Summary of Contents for VRV IV RXYQ TTJU Series
Page 1: ...EDUS341411 N Installation...
Page 62: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 63 3P161697D...
Page 66: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 67 C 3P113151C 7 8 1 1 1 8...
Page 67: ...REFNET Joint and Header EDUS341411 N 68 Installation of Outdoor Units KHRP26M73HU 3P185500...
Page 68: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 69 3P185500...
Page 70: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 71 1P218719...
Page 71: ...REFNET Joint and Header EDUS341411 N 72 Installation of Outdoor Units 1P218719...
Page 72: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 73 1P218720...
Page 73: ...REFNET Joint and Header EDUS341411 N 74 Installation of Outdoor Units 1P218720...
Page 75: ...REFNET Joint and Header EDUS341411 N 76 Installation of Outdoor Units 1P280278A...
Page 76: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 77 1P280278A...
Page 77: ...REFNET Joint and Header EDUS341411 N 78 Installation of Outdoor Units 1P280279...
Page 79: ...Caution Label EDUS341411 N 80 Installation of Outdoor Units 2P361359C...
Page 80: ...EDUS341411 N Caution Label Installation of Outdoor Units 81 3P357947A...
Page 81: ...Caution Label EDUS341411 N 82 Installation of Outdoor Units 3P357947A...
Page 83: ...Caution Label EDUS341411 N 84 Installation of Outdoor Units 1P361833B...
Page 84: ...EDUS341411 N Caution Label Installation of Outdoor Units 85 1P361833B...
Page 85: ...Caution Label EDUS341411 N 86 Installation of Outdoor Units 1P361833B...
Page 86: ...EDUS341411 N Caution Label Installation of Outdoor Units 87 1P361833B...
Page 87: ...Caution Label EDUS341411 N 88 Installation of Outdoor Units 1P361833B...
Page 88: ...EDUS341411 N Caution Label Installation of Outdoor Units 89 1P361833B...
Page 89: ...Caution Label EDUS341411 N 90 Installation of Outdoor Units 3P357946A...
Page 90: ...EDUS341411 N Caution Label Installation of Outdoor Units 91 3P357946A...