background image

Installation Manual

EDUS341411-N

40

Installation of Outdoor Units

3P362438-1B

30

3P362438-1B English

 NOTE

r

The refrigerant charging port is connected to the piping inside the 
unit. The unit’s internal piping is already factory charged with refrig-
erant, so be careful when connecting the charge hose.

r

After adding the refrigerant, do not forget to close the lid of the 
refrigerant charging port. The tightening torque for the lid is 8.48 to 
10.3 ft

x

lbf (11.5 to 13.9 N

x

m). 

r

In order to ensure uniform refrigerant distribution, it may take the 
compressor ±10 minutes to start up after the unit has started opera-
tion. This is not a malfunction.

A.

Adding refrigerant by using the automatic charging function

 INFORMATION

The automatic refrigerant charging has limits as described below. Out 
of these limits, the system cannot operate the automatic refrigerant 
charging:

r

Outdoor temperature: 32°F (0°C) DB -109°F (43°C) DB.

r

Indoor temperature: 50°F (10°C) DB - 89°F (32°C) DB.

r

Total indoor unit capacity:  80% (VRV indoor units only).

6A

The remaining additional refrigerant charge can be charged by 
operating the outdoor unit by means of the automatic refrigerant 
charge operation mode.
Depending on the ambient limitation conditions (see above), the 
unit will automatically decide which operation mode will be used 

VQHWNƂNNVJGCWVQOCVKETGHTKIGTCPVEJCTIGEQQNKPIQTH
CDQXGEQPFKVKQPUCTGHWNƂNNGFEQQNKPIQRGTCVKQPYKNNDGUH

not, heating mode will start.

Procedure

r

Idle (default) screen is shown.

r

Push BS2 once, indication 

888

.

r

Push BS2 for more than 5 seconds, wait while the unit is 
preparing for operation. Segment display indication: 

01

 (pres-

UWTGEQPVTQNKUGZGEWVGF

- In case heating operation is started: indication 

22

 till 

23

will be displayed (start up control; waiting stable heating 
operation).

- In case cooling operation is started: indication 

02

 till 

03

will be displayed (start up control; waiting stable cooling 
operation).

r

When

23

 or 

03

UVCTVUƃCUJKPITGCF[HQTEJCTIKPIRWUJ

BS2 within 5 minutes. Open valve A. If BS2 is not pushed within 
5 minutes, a malfunction code will appear:

- Heating operation:

26

YKNNDGƃCUJKPI2WUJ$5VQTGUVCTV

the procedure.

- Cooling operation: malfunction code 

P2

 will appear.

Push BS1 to abort and restart the procedure.

Heating (middle segment indicates 

2

)

Charging will continue, the segment indication intermittently 
shows the current low pressure value and the status indication

23

.

When the remaining additional refrigerant amount is charged, 
close valve A immediately and push BS3 to stop charging opera-
tion.
After BS3 is pushed, the ending code 

26

 will appear. When BS2 

is pushed, the unit will check whether the ambient conditions are 

HCXQTCDNGVQGZGEWVGVJGVGUVTWP

- If 

01

,

02

, or 

03

CRRGCTURWUJ$5VQƂPKUJVJGCWVQ

-

matic charging function procedure. The ambient conditions 

CTGHCXQTCDNGVQGZGEWVGVJGVGUVTWP

- If the unit indicates 

E-2

, or 

E-3

, the ambient conditions are 

016HCXQTCDNGVQGZGEWVGVJGVGUVTWP2WUJ$5VQƂPKUJVJG

automatic charging procedure.

 INFORMATION

In case a malfunction code occurred during this automatic charging 
procedure, the unit will stop and indicate 

26

ƃCUJKPI2WUJ$5VQ

restart the procedure. 

Cooling (middle segment indicates 

0

)

Automatic charging will continue, the segment indication shows 
the current low pressure value and the status indication 

03

intermittent. 
If the segment indication/user interface of indoor unit shows 

PE

EQFGEJCTIKPIKUCNOQUVƂPKUJGF9JGPVJGWPKVUVQRUQRGTCVKPI

close valve A immediately and check whether the segment indi-
cation/user interface of indoor unit shows 

P9

. This indicates the 

CWVQOCVKEEJCTIKPIKPEQQNKPIRTQITCOYCUƂPKUJGFUWEEGUUHWNN[

 INFORMATION

When the charging amount is little, the 

PE

 code may not be displayed, 

but instead the 

P9

 code will be displayed immediately. 

When the required (calculated) additional refrigerant amount is 
already charged before 

PE

 or 

P9

 indication appears, close valve A and 

wait till 

P9

 is displayed. 

If during the cooling operation for the automatic refrigerant charge 
the ambient conditions go beyond the allowable for this operation 
mode, the unit will indicate on the segment display the code 

E-2

in case indoor temperature is out of range or 

E-3

 in case the out-

door temperature is out of range. In this case, when the additional 

TGHTKIGTCPVEJCTIKPIYCUPQVƂPKUJGFUVGR#JCUVQDGTGRGCVGF

 INFORMATION

r

When a malfunction is detected during the procedure (e.g, in case 
of closed stop valve), a malfunction code will be displayed. In that 

ECUGTGHGTVQ/CNHWPEVKQPEQFGNKUVQPRCIG|CPFUQNXG

the malfunction accordingly. Resetting the malfunction can be done 
by pushing BS1. The procedure can be restarted from 6A.).

r

Aborting the automatic refrigerant charge is possible by pushing 
BS1. The unit will stop and return to idle condition.

Perform the test procedure as described in 15.4.2. Test operation on 

RCIG|

B.

Adding refrigerant by using the manual charging function

6B

The remaining additional refrigerant charge can be charged by 
operating the outdoor unit by means of the manual refrigerant 
charge operation mode:

r

Turn on the power of the indoor units and outdoor unit.

r

Take all the precautions mentioned in 

UVCTVWRCPFEQPƂIWTC

-

tion

 into account.

r

Activate outdoor unit setting [2-20]=1 to start manual refriger-

CPVEJCTIGOQFG4GHGTVQRCIG|HQTFGVCKNU

Result: 

The unit will start operation. Valve A can be opened.

Charging of remaining additional refrigerant can be done.
When the remaining calculated additional refrigerant amount is 
added, close valve A and push BS3 to stop the manual refrig-
erant charging procedure.

 INFORMATION

The manual refrigerant charge operation will automatically stop within 
30 minutes. If charging is not completed after 30 minutes, perform the 
additional refrigerant charging operation again.

Summary of Contents for VRV IV RXYQ TTJU Series

Page 1: ...EDUS341411 N Installation...

Page 2: ...Installation Manual 9 3 1 RXYQ TYDN RXYQ TTJU 9 4 REFNET Pipe System 54 4 1 Layout Example 54 4 2 REFNET Joints and Headers 56 5 REFNET Joint and Header 58 5 1 REFNET Joint Branch Kit 58 5 2 REFNET H...

Page 3: ...Center of Gravity EDUS341411 N 4 Installation of Outdoor Units 1 Center of Gravity 1 1 RXYQ TYDN RXYQ72TYDN Unit in mm RXYQ96TYDN RXYQ120TYDN Unit in mm 4D087112 4D087113...

Page 4: ...EDUS341411 N Center of Gravity Installation of Outdoor Units 5 RXYQ144TYDN RXYQ168TYDN Unit in mm 4D087114...

Page 5: ...Center of Gravity EDUS341411 N 6 Installation of Outdoor Units 1 2 RXYQ TTJU RXYQ72TTJU Unit in mm RXYQ96TTJU RXYQ120TTJU Unit in mm 4D087109 4D087110...

Page 6: ...EDUS341411 N Center of Gravity Installation of Outdoor Units 7 RXYQ144TTJU RXYQ168TTJU Unit in mm 4D087111...

Page 7: ...Drawing EDUS341411 N 8 Installation of Outdoor Units 2 Foundation Drawing RXYQ72TYDN RXYQ96TYDN RXYQ120TYDN RXYQ144TYDN RXYQ168TYDN RXYQ72TTJU RXYQ96TTJU RXYQ120TTJU RXYQ144TTJU RXYQ168TTJU Unit in m...

Page 8: ...r trans portation will result in injuries or death by suffocation WARNING r 1PN SWCNK GF RGTUQPPGN OWUV ECTT QWV VJG KPUVCNNCVKQP work Installation must be done in accordance with this installation ma...

Page 9: ...nverter or rapid start types Install the indoor WPKV HCT CYC HTQO WQTGUEGPV NCORU CU OWEJ CU RQUUKDNG r Indoor units are for indoor installation only Outdoor units can be installed either outdoors or...

Page 10: ...pe length 9 7 1 General information 9 7 2 Selection of piping material 9 7 3 Selection of piping size 9 7 4 Selection of refrigerant branch kits 10 7 5 System piping length limitations 11 8 Precaution...

Page 11: ...CVGUV PIKPGGTKPI CVC QQM HQT OQTG FGVCKNU 1 2 2 Outdoor unit combinations Standard combinations for VRV IV heat pump system are as indicated in table below where RXYQ192 408 consists of several RXYQ72...

Page 12: ...essories supplied with this unit QP TO VJG HQNNQYKPI CEEGUUQTKGU CTG KPENWFGF 6JG UVQTCIG NQECVKQP QH VJG CEEGUUQTKGU KU UJQYP KP VJG IWTG DGNQY Accessories assy piping Accessories assy operation and...

Page 13: ...PU VJCV CTG FGUKIPGF VQ RTQXKFG TGCUQPCDNG RTQVGEVKQP against such interference However there is no guarantee that inter ference will not occur in a particular installation It is therefore recommended...

Page 14: ...ng in snow 1 2 1 Construct a large canopy 2 Construct a pedestal NOTE When operating the unit in a low outdoor ambient temperature with high humidity conditions make sure to take precautions to keep t...

Page 15: ...ct2 50 dt19 5 8 500 et3 7 8 100 ft23 5 8 600 h2 a Front side Suction side b h2 2 or more Service space h1 2 or more h1 b a 59 in 1500 mm b 19 5 8 in 500 mm r In case of an installation site where sid...

Page 16: ...it s center of gravity NOTE Use a belt sling of d3 4 in 20 mm wide that adequately bears the weight of the unit A forklift can only be used for transport as long as the unit remains on its pallet as s...

Page 17: ...heir length remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE r There are restrictions on the refrigerant pipe connecting order between outdoor unit in the case of the multi...

Page 18: ...piping size to determine the correct size Thickness Select a thickness for the refrigerant piping which complies with national and local laws r QT RKRKPI YQTM HQNNQY VJG OCZKOWO VQNGTCVGF NGPIVJ FKHHG...

Page 19: ...Q TUV TGHTKIGTCPV DTCPEJ MKV 3 Increase 4 First refrigerant branch kit 5 Indoor unit Size up for equivalent length for outdoor indoor units over 295 ft 90 m Outdoor unit capacity type Gas pipe Liquid...

Page 20: ...n the range of the OCZKOWO CNNQYCDNG RKRG NGPIVJ CNNQYCDNG JGKIJV FKHHGTGPEG CPF CN lowable length after branching as indicated below 3 patterns will be discussed including VRV indoor units combined w...

Page 21: ...65 m Example 1 2 unit 6 a b hd540 ft 165 m unit 8 a i kd540 ft 165 m Example 1 3 unit 8 a id540 ft 165 m Equivalent length 2 623 ft 190 m Total piping length 3280 ft 1000 m Example 1 1 a b c d e f g h...

Page 22: ...m d The piping length difference between the nearest indoor from the TUV DTCPEJ VQ VJG QWVFQQT WPKV CPF HCTVJGUV KPFQQT VQ VJG QWVFQQT unit is d130 ft 40 m Example The farthest indoor unit 8 The neare...

Page 23: ...Make sure to blow through with Dry Nitrogen when brazing Blowing through with Dry Nitrogen prevents the creation of large quantities QH QZKFK GF NO QP VJG KPUKFG QH VJG RKRKPI P QZKFK GF NO CF versely...

Page 24: ...alve for liquid Stop valve for gas Protective plate Stop valve mounting plate 5 Cut off the lower part of the smaller pinched piping with an ap propriate tool such as pipe cutters Let the remaining oi...

Page 25: ...V U UVGO r To connect the piping between outdoor units an optional multi con nection piping kit BHFP22P100U 151U is always required When installing the piping follow the instructions in the installati...

Page 26: ...Mount the refnet header so that it branches horizontally r Installation of the multi connection piping kit A 1 max 15 B 1 C D C 4 3 4 in 120 mm D 19 11 16 in 500 mm 3 Install the joints horizontally s...

Page 27: ...5 Nxm I1 9 Field wiring NOTE r NN GNF YKTKPI CPF EQORQPGPVU OWUV DG KPUVCNNGF D C NKEGPUGF GNGE trician and must comply with relevant local and national regulations r Be sure to use a dedicated power...

Page 28: ...460 V 460 V 460 V 460 V 460 V 460 V 460 V 460 V 460 V 460 V 460 V 460 V 460 V 27 6A 36 3A 36 3A 55 1A 55 1A 27 6A 36 3A 36 3A 36 3A 36 3A 36 3A 36 3A 55 1A 55 1A 55 1A 55 1A 55 1A 55 1A 55 1A 36 3A 36...

Page 29: ...he Outdoor unit that connects the transmission wiring to an indoor unit is Master unit of the multi system 6JG QVJGT WPKVU CTG 5WD WPKVU P VJKU IWTG 1WVFQQT WPKV is the Master unit Check installation...

Page 30: ...erminal block 9 Ground terminal 10 Clamp 1 accessory 11 Vinyl tube accessory CAUTION r Be sure to use crimp style terminal with insulating sleeves for con PGEVKQPU 5GG VJG IWTG DGNQY Crimp style termi...

Page 31: ...nsulation measurement has been completed Measuring after the stop valve is opened will cause the insulation value to drop Needed tools Gauge manifold Charge hose valve r To prevent entry of any impuri...

Page 32: ...system and pipe connections r Failing to insulate the pipes may cause leaking or burns Be sure to use insulation designed for HVAC equipment r Reinforce the insulation on the refrigerant piping accord...

Page 33: ...2GTHQTO GNF UGVVKPIU FGOCPF QRGTCVKQP NQY PQKUG GVE GNQY RTQEGFWTG GZRNCKPU JQY VQ QRGTCVG VJG RWUJ DWVVQPU VQ TGCEJ the required mode in the menu select the correct setting and modify the value of t...

Page 34: ...anging the value of the selected setting in mode 2 Once mode 2 is selected push BS1 for more than 5 seconds you can select the wanted setting It is done by pushing BS2 Accessing the selected setting s...

Page 35: ...e 14 2 1 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R lbs R should be rounded off in units of 0 1 lbs R X1 u I7 8 u 0 249 X2 u I3 4 u 0 175 X3 u I5...

Page 36: ...ge label r Go to test run see 15 4 Test opera VKQP QP RCIG R Q QW YCPV VQ GZGEWVG CWVQOCVKE refrigerant charge B A Step 4b 5 Manual refrigerant charging method in cooling operation NO 5 Step 4b 5 Auto...

Page 37: ...bel r Go to test run see 15 4 Test opera VKQP QP RCIG During gray conditions If following codes appear E 2 indoor temperature out of range and E 3 outdoor temperature out of range In this case perform...

Page 38: ...lit indoor units are connected to the system QY EJCTV KU CXCKNCDNG YJKEJ IKXGU CP QXGTXKGY QH VJG RQUUKDKNKVKGU CPF CEVKQPU VQ DG VCMGP UGG NQY EJCTV QP RCIG To speed up the process of pre charging re...

Page 39: ...The ambient conditions CTG HCXQTCDNG VQ GZGEWVG VJG VGUV TWP If the unit indicates E 2 or E 3 the ambient conditions are 016 HCXQTCDNG VQ GZGEWVG VJG VGUV TWP 2WUJ 5 VQ PKUJ VJG automatic charging pro...

Page 40: ...rature must be between 60 F 16 C and 97 F Purge gauge lines Connect service gauge manifold to the service port between the compressor and the reversing valve in each outdoor unit Run the system for 30...

Page 41: ...UGVVKPI ECP CNUQ DG RGTHQTOGF XKC VJG 2 EQP IWTCVKQP UQHVYCTG Below relevant Monitoring mode mode 1 and Field setting mode OQFG UGVVKPIU CTG GZRNCKPGF KP FGVCKN QY VQ CEEGUU VJGO JQY VQ EJCPIG VJG XC...

Page 42: ...PCVKQPU 2 0 Cool Heat selection setting Cool Heat selection setting is used in case the optional Cool Heat selector KRC19 26A is used Depending on the outdoor unit setup single outdoor unit setup or m...

Page 43: ...2 To activate function change 2 25 1 2 or 3 2 26 Low noise operation start time Change 2 26 1 2 or 3 in function of required timing Default value 2 Value 2 26 Start time automatic low noise QRGTCVKQP...

Page 44: ...QRVKOWO QRGTCVKQP 2 82 Heating comfort setting Default value 1 Value 2 82 Heating comfort setting 0 EQ 1 Mild default 2 Quick 3 Powerful Change 2 82 0 1 2 or 3 in function of required limitation This...

Page 45: ...ng 2 8 r To activate the powerful comfort setting under heating opera VKQP EJCPIG GNF UGVVKPI This setting is used in conjunction with setting 2 9 r Quick Overshoot during heating operation or undersh...

Page 46: ...ORGTCVWTG Quick Powerful Mild Room temperature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A...

Page 47: ...ork results of tests stand by periods etc INFORMATION 0QVG VJCV FWTKPI VJG TUV TWPPKPI RGTKQF QH VJG WPKV TGSWKTGF RQYGT KP put may be higher This phenomenon originates from the compressor that requir...

Page 48: ...ZRNCKPGF KP VJG OCNHWPEVKQP EQFG VCDNG After correcting the abnormality press BS3 to reset the malfunction code and retry operation The malfunction code which is displayed on the outdoor unit will ind...

Page 49: ...VWTG UGPUQT CHVGT UWDEQQN OCNHWPE tion R6T A1P X30A Check connection on printed circuit board or actuator JA 06 08 10 High pressure sensor malfunction S1NPH open circuit A1P X32A Check connection on p...

Page 50: ...wiring of other outdoor unit to TO OUT D UNIT F1 F2 02 Faulty wiring to Q1 Q2 or indoor outdoor Connect transmission wiring of indoor unit to TO IN D UNIT F1 F2 and transmission wiring of other outdo...

Page 51: ...ITERNAL PARTS 5GG 5CHGV EQPUKFGTCVKQPU QP RCIG K CAUTION When performing service to inverter equipment 1 Q PQV QRGP VJG EQPVTQN DQZ EQXGT HQT OKPWVGU CHVGT VJG RQYGT supply is turned off 2 Measure th...

Page 52: ...GU CTG KPUVCNNGF KP C TQQO VJCV KU UWH EKGPVN NCTIG 6JKU CUUWTGU VJCV VJG OCZKOWO EQPEGPVTCVKQP NGXGN QH TGHTKIGTCPV ICU KU PQV GZEGGFGF KP VJG WPNKMGN GXGPV QH OCLQT NGCM KP VJG U UVGO CPF VJKU KP ac...

Page 53: ...must be used for all the pipe work For further details concerning choosing components see REFNET and Piping Selection Rules 3 The Daikin REFNET kits are supplied with insulation intended to fit over t...

Page 54: ...culated the liquid pipe size is selected Pipe Size 1 4 in 6 4 mm 3 8 in 9 5 mm 1 2 in 12 7mm 5 8 in 15 9mm 3 4 in 19 1mm 7 8 in 22 2mm 1 in 25 4mm 1 1 8 in 28 6mm 1 1 4 in 31 8mm 1 3 8 in 34 9mm 1 1 2...

Page 55: ...ly or vertically When the size of the selected field piping is different from that of branch pipe then the connecting section should be cut with a pipe cutter as shown in the figure below When you are...

Page 56: ...he outdoor unit side of the liquid pipe header Cut the B section with a pipe cutter as shown below and connect it to the A section Connect the flared section of the field pipe to the B section Fit the...

Page 57: ...as Side Liquid Side 1 2 5 8 3 4 13 5 16 14 15 16 1 5 8 1 2 5 8 1 2 3 1 8 5 8 7 8 5 8 3 4 3 4 3 15 16 3 1 8 3 8 9 13 16 3 8 3 8 1 4 1 4 1 9 16 11 7 16 3 1 8 C D3K05235B Liquid Side 7 8 3 4 1 7 8 3 4 7...

Page 58: ...D 3 4 O D 1 3 8 THERMAL INSULATION 3 9 16 I D 1 2 I D 1 4 THERMAL INSULATION I D 7 8 O D 5 8 I D 3 4 1 15 16 1 1 2 14 1 8 3 1 8 12 6 8 I D 3 8 I D 1 1 8 20 3 4 3 15 16 4 3 4 I D 5 8 4 3 4 O D 7 8 I D...

Page 59: ...4 7 8 3 4 7 8 1 7 8 1 2 7 8 1 1 8 1 1 4 1 1 2 1 4 3 4 7 8 5 8 3 4 1 1 8 1 7 8 1 2 3 4 5 8 5 8 5 8 1 2 1 2 7 8 3 4 3 4 5 8 5 8 1 2 1 1 4 1 1 3 4 5 8 5 8 1 2 3 4 1 1 8 1 1 2 1 1 4 1 1 4 1 1 8 1 5 8 3 4...

Page 60: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 61 C 2P182411 3 4 5 8 5 8 1 2 7 8 3 4 3 4 3 4 5 8 3 4 7 8 3 4 5 8 7 8 3 4 3 8 3 8 3 8 3 8 1 2 3 8 3 8 1 4...

Page 61: ...REFNET Joint and Header EDUS341411 N 62 Installation of Outdoor Units KHRP26M72TU KHRP26M73TU 3P161697D...

Page 62: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 63 3P161697D...

Page 63: ...6 3 4 5 11 16 4 3 4 4 3 4 2 2 3 8 4 3 4 4 3 4 10 7 16 8 1 16 3 15 16 24 3 16 2 I D 1 2 I D 1 2 O D 1 2 I D 5 8 I D 5 8 I D 1 O D 7 8 I D 5 8 I D 3 4 I D 7 8 5 I D 1 2 3 3 16 4 3 4 3 1 8 6 I D 3 8 6 I...

Page 64: ...05574 I D 1 3 8 6 1 2 5 3 1 8 15 3 4 Thermal Insulation Thermal Insulation 30 1 2 I D 3 4 I D 5 8 3 1 8 3 1 8 3 11 16 5 5 16 I D 5 8 7 1 16 I D 3 4 I D 5 8 I D 7 8 O D 3 4 O D 3 8 I D 1 4 1 15 16 O D...

Page 65: ...26M33H KHRP26M72H C 3P113151C 7 8 5 8 3 8 1 5 8 5 8 3 4 3 8 1 2 1 4 7 8 3 8 5 8 3 4 5 8 1 2 3 8 1 4 3 8 3 8 1 4 3 8 3 8 3 8 1 4 5 8 1 2 1 2 1 4 2 1 4 1 2 3 8 1 4 3 4 5 8 5 8 3 8 8 5 8 5 8 3 4 1 1 2 1...

Page 66: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 67 C 3P113151C 7 8 1 1 1 8...

Page 67: ...REFNET Joint and Header EDUS341411 N 68 Installation of Outdoor Units KHRP26M73HU 3P185500...

Page 68: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 69 3P185500...

Page 69: ...it may cause the malfunction of outdoor unit Make sure the piping up to the joint is straight for more than 19 11 16in Do not bend the field piping within this range If a straight field piping more th...

Page 70: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 71 1P218719...

Page 71: ...REFNET Joint and Header EDUS341411 N 72 Installation of Outdoor Units 1P218719...

Page 72: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 73 1P218720...

Page 73: ...REFNET Joint and Header EDUS341411 N 74 Installation of Outdoor Units 1P218720...

Page 74: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 75 BHFP22P151U Gas side Unit in Liquid side Unit in 3D071077 3D071076...

Page 75: ...REFNET Joint and Header EDUS341411 N 76 Installation of Outdoor Units 1P280278A...

Page 76: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 77 1P280278A...

Page 77: ...REFNET Joint and Header EDUS341411 N 78 Installation of Outdoor Units 1P280279...

Page 78: ...EDUS341411 N Caution Label Installation of Outdoor Units 79 6 Caution Label 6 1 RXYQ72TYDN RXYQ72TTJU 2P361359C...

Page 79: ...Caution Label EDUS341411 N 80 Installation of Outdoor Units 2P361359C...

Page 80: ...EDUS341411 N Caution Label Installation of Outdoor Units 81 3P357947A...

Page 81: ...Caution Label EDUS341411 N 82 Installation of Outdoor Units 3P357947A...

Page 82: ...EDUS341411 N Caution Label Installation of Outdoor Units 83 6 2 RXYQ96 168TYDN RXYQ96 168TTJU 3P361373...

Page 83: ...Caution Label EDUS341411 N 84 Installation of Outdoor Units 1P361833B...

Page 84: ...EDUS341411 N Caution Label Installation of Outdoor Units 85 1P361833B...

Page 85: ...Caution Label EDUS341411 N 86 Installation of Outdoor Units 1P361833B...

Page 86: ...EDUS341411 N Caution Label Installation of Outdoor Units 87 1P361833B...

Page 87: ...Caution Label EDUS341411 N 88 Installation of Outdoor Units 1P361833B...

Page 88: ...EDUS341411 N Caution Label Installation of Outdoor Units 89 1P361833B...

Page 89: ...Caution Label EDUS341411 N 90 Installation of Outdoor Units 3P357946A...

Page 90: ...EDUS341411 N Caution Label Installation of Outdoor Units 91 3P357946A...

Page 91: ...ured for export to numerous countries throughout the world Daikin Industries Ltd does not have control over which products are exported to and used in a particular country Prior to purchase please the...

Reviews: