background image

15 Troubleshooting

Installation and operation manual

34

RXYLQ10~14T7Y1B*

VRV IV system air conditioner

4P543426-1 – 2018.07

14.2

After-sales service and warranty

14.2.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

14.2.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do not modify, disassemble, remove, reinstall or repair

the unit yourself as incorrect dismantling or installation
may  cause  an  electric  shock  or  fire.  Contact  your
dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustible  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  Always  have  qualified  service
personnel  confirm  that  the  point  of  leakage  has  been
repaired or corrected before resuming operation.

15

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does NOT properly work.

Turn OFF the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does NOT work
well.

Turn OFF the power
supply.

Malfunction

Measure

If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.

Notify your installer and
report the malfunction
code.

If  the  system  does  NOT  properly  operate  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  according  to  the  following
procedures.

Malfunction

Measure

If the system does not
operate at all.

▪ Check  if  there  is  no  power  failure.  Wait

until  power  is  restored.  If  power  failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

If the system goes into
fan only operation, but
as soon as it goes into
heating or cooling
operation, the system
stops.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the user interface display shows

 (time to clean the air filter). (Refer to

"14  Maintenance  and  service"  on
page 33

 and "Maintenance" in the indoor

unit manual.)

The system operates
but cooling or heating
is insufficient.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the air filter is not clogged (refer

to  "Maintenance"  in  the  indoor  unit
manual).

▪ Check the temperature setting.

▪ Check the fan speed setting on your user

interface.

▪ Check for open doors or windows. Close

doors and windows to prevent wind from
coming in.

▪ Check if there are too many occupants in

the room during cooling operation. Check
if  the  heat  source  of  the  room  is
excessive.

▪ Check  if  direct  sunlight  enters  the  room.

Use curtains or blinds.

▪ Check if the air flow angle is proper.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

15.1

Error codes: Overview

In case a malfunction code appears on the indoor unit user interface
display,  contact  your  installer  and  inform  the  malfunction  code,  the
unit  type,  and  serial  number  (you  can  find  this  information  on  the
nameplate of the unit).

For  your  reference,  a  list  with  malfunction  codes  is  provided.  You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.

Main code

Contents

External protection device was activated

Summary of Contents for VRV IV RXMLQ8T7Y1B Series

Page 1: ...Installation and operation manual VRV IV system air conditioner English Installation and operation manual VRV IV system air conditioner RXMLQ8T7Y1B RXYLQ10T7Y1B RXYLQ12T7Y1B RXYLQ14T7Y1B...

Page 2: ...18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v plat...

Page 3: ...astaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota T...

Page 4: ...onnecting the electrical wiring 18 5 7 1 Field wiring Overview 18 5 7 2 Guidelines when knocking out knockout holes 19 5 7 3 To route and fix the transmission wiring 19 5 7 4 To connect the transmissi...

Page 5: ...INDICATIONOFINSTALLATIONINFORMATION 1 RECORD OF INDOOR UNIT MODELAND INSTALLATION SITE 2 RECORD FOR SETTINGS CONTENTS SEE INSTALLATION MANUAL SETTING 40 30 10 20 19 9 29 39 38 28 8 18 17 7 27 37 36 26...

Page 6: ...ating capacities ranging from 31 5 to 45 kW and cooling capacities rating from 28 to 40 kW In multi combination the heating capacity ranges from 50 to 135 kW and cooling capacity ranges from 45 to 120...

Page 7: ...ation see About the piping length in the installer reference guide Only use phosphoric acid deoxidised seamless copper 4 2 2 To select the piping size Determine the proper size using the following tab...

Page 8: ...e adapters for the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6 3 To determine the additional refrigerant amount on page...

Page 9: ...wed O Allowed If the piping length between the outdoor units exceeds 2 m create a rise of 200 mm or more in the gas line within a length of 2 m from the kit If Then 2 m a b 2 m 2 m a 2 m 2 m 200 mm 20...

Page 10: ...ssed See 5 1 2 To open the electrical component box of the outdoor unit on page 10 For service purposes the pushbuttons on the main PCB need to be accessed To access these pushbuttons the electrical c...

Page 11: ...t holes Avoid damaging the casing After making the knockout holes we recommend you remove the burrs and paint the edges and areas around the edges using repair paint to prevent rusting When passing el...

Page 12: ...nadequate torque may cause leakage of refrigerant and breakage of the stop valve cap NOTICE Pay attention that mentioned torque range is applicable for opening 19 1 25 4 mm stop valves only To close t...

Page 13: ...Wait until all oil has dripped out before continuing with the connection of the field piping in case the recovery was not complete 5 4 Checking the refrigerant piping 5 4 1 About checking the refrige...

Page 14: ...nt piping on page 13 5 4 4 To perform a leak test The leak test must satisfy the specifications of EN378 2 To check for leaks Vacuum leak test 1 Evacuate the system from the liquid and gas piping to 1...

Page 15: ...E Close the front panel before any refrigerant charge operation is executed Without the front panel attached the unit cannot judge correctly whether it is operating properly or not NOTICE In case of m...

Page 16: ...Weight factor 15 9 mm 0 18 15 mm 0 16 16 mm 0 18 19 1 mm 0 26 18 mm 0 24 22 2 mm 0 37 22 mm 0 35 5 6 4 To charge refrigerant Flow chart For more information see 5 6 5 To charge refrigerant on page 17...

Page 17: ...t outdoor unit operation If Then The additional refrigerant amount is smaller than 10 kg Perform steps 2 3 The additional refrigerant charge is larger than 10 kg Perform steps 2 8 3 Pre charging can b...

Page 18: ...refrigerant charge operation will automatically stop within 30 minutes If charging is not completed after 30 minutes perform the additional refrigerant charging operation again 5 6 7 Checks after char...

Page 19: ...2 left b Internal transmission wiring Q1 Q2 c Plastic bracket d Field supplied clamps 5 7 4 To connect the transmission wiring The wiring from the indoor units must be connected to the F1 F2 In Out te...

Page 20: ...ting the earth wire it is recommended to perform curling Multiple outdoor units To connect the power supply for multiple outdoor units to each other ring tongues have to be used No bare cable can be u...

Page 21: ...ent display s To access you can remove the front inspection cover of the front plate see figure Now you can open the inspection cover of the electrical component box front plate see figure You can see...

Page 22: ...e selected setting s value is done by pushing BS3 1 time Now BS2 is used to select the required value of the selected setting When the required value is selected you can define the change of value by...

Page 23: ...t Deactivated 1 Activated To stop the manual additional refrigerant charge operation when the required additional refrigerant amount is charged push BS3 If this function was not aborted by pushing BS3...

Page 24: ...ts Pipe size and pipe insulation Be sure that correct pipe sizes are installed and that the insulation work is properly executed Stop valves Be sure that the stop valves are open on both liquid and ga...

Page 25: ...splay idle Completion Description Abnormal completion Indication of malfunction code on the 7 segment display Refer to 7 5 Correcting after abnormal completion of the test run on page 25 to take actio...

Page 26: ...connection on PCB or actuator Discharge temperature too high R21T R22T Stop valve closed Refrigerant shortage Open stop valves Check refrigerant amount recharge unit Compressor casing temperature too...

Page 27: ...nection Transmission outdoor unit inverter INV2 transmission trouble A1P X20A X28A X40A Check connection INV1 unbalanced power supply voltage Check if power supply is within range INV2 unbalanced powe...

Page 28: ...llowing items before retrying autocharge procedure Check if the gas side stop valve is opened correctly Check if the valve of the refrigerant cylinder is opened Check if the air inlet and outlet of th...

Page 29: ...obstacles the wall heights of sides A C have no impact on service space dimensions Refer to the figure above for impact of wall heights of sides B D on service space dimensions In case of an installat...

Page 30: ...smission wiring refer to the service manual Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P Noise filter PCB A3P Inverter PCB A4P SUB P...

Page 31: ...se of using Hydrobox units or AHU They can be found in the installation operation manual of the dedicated unit Latest information can be found in the technical engineering data 13 2 Operating the syst...

Page 32: ...ystem does not go into operation if the room temperature is low 20 C 13 3 2 To use the dry program WITHOUT cool heat changeover remote control switch To start 1 Press the operation mode selector butto...

Page 33: ...signate one of the user interfaces as the master user interface The displays of slave user interfaces show change over under centralised control and slave user interfaces automatically follow the oper...

Page 34: ...e unit Stop the operation The operation switch does NOT work well Turn OFF the power supply Malfunction Measure If the user interface display indicates the unit number the operation lamp flashes and t...

Page 35: ...related Autocharge operation related Capacity setting malfunction outdoor Abnormal low pressure drop faulty expansion valve Reversed power supply phase malfunction INV voltage power shortage System te...

Page 36: ...l and refrigerant from remaining in the system a small amount of refrigerant is kept flowing 15 2 9 Symptom Noise of air conditioners Indoor unit outdoor unit A continuous low hissing sound is heard w...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P543426 1 2018 07 Copyright 2018 Daikin 4P543426 1 0000000M...

Reviews: