10 Technical data
Installation and operation manual
29
RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543426-1 – 2018.07
a
b
a
c
d
a
b
a
e
d
e
c
a
b
a
e
d
f
c
a
b
a
e
b
d
c
a
b
a
e
d
f
c
Layout
A+B+C+D
A+B
Possibility 1
Possibility 2
1
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
a≥200 mm
b≥300 mm
2
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
e≥20 mm
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
e≥100 mm
a≥200 mm
b≥300 mm
e≥400 mm
3
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
e≥20 mm
f≥600 mm
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
e≥100 mm
f≥500 mm
—
4
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
e≥20 mm
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
e≥100 mm
5
a≥10 mm
b≥500 mm
c≥10 mm
d≥500 mm
e≥20 mm
f≥900 mm
a≥50 mm
b≥500 mm
c≥50 mm
d≥500 mm
e≥100 mm
f≥600 mm
—
h
1
h
2
1500
500
F
(mm)
d
b
ABCD
Sides along the installation site with obstacles
F
Front side
Suction side
▪ In case of an installation site where sides A+B+C+D have
obstacles, the wall heights of sides A+C have no impact on
service space dimensions. Refer to the figure above for impact of
wall heights of sides B+D on service space dimensions.
▪ In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.
▪ The installation space required on these drawings are for full load
heating operation without considering possible ice accumulation. If
the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation of
ice in between the outdoor units.
INFORMATION
The service space dimensions in above figure are based
on cooling operation at 35°C ambient temperature
(standard conditions).
INFORMATION
Further specifications can be found in the technical
engineering data.
10.2
Piping diagram: Outdoor unit
Piping diagram: RXYLQ10~14
R3T
R8T
R21T
R6T
R5T
R1T
R4T
d
c
b
c
d
h
l
i
f
n
o
m
g
j
e
k
a
p
M2F
M
M1F
M
R7T
R10T
M1C
Y5S
Y4S
S1NPL
S1NPH
S1PH
SV
SV
SV
SV
a
Compressor (M1C)
b
Heat exchanger
c
Fan
d
Fan motor (M1F, M2F)
e
Accumulator
Summary of Contents for VRV IV RXMLQ8T7Y1B Series