• Use city water or clean water and take steps to prevent 

condensation from forming. (VKM-GAMV1 series only)

The life of humidifier become shorter when the supply 
water is hard water. (VKM-GAMV1 series only)

Use a water softener.

Do not install the remote controller where the indoor 
temperature and humidity, respectively, are out of the 
range of 0-35°C and RH 40-80%.

This may cause malfunction.

Do not install the remote controller where direct sun-
light may fall on it.

This may cause discoloration or deformation.

NOTE

• When the fan motor fails, the remote controller does not dis-

play any error code.
Usage under that status will lead to insufficient ventilation.
The air supply and exhaust fans should be checked once 
every one or two months.
You can make a simple check such as below way.
To check the wind flow, hold a bar of which the end has a 
string or other similar lightweight item over the supply grille 
and exhaust grille.

• When the solenoid valve fails, the remote controller does not 

display any error code.
Usage under that status will lead to insufficient humidification 
and increased tap water consumption.
The solenoid valve should be checked at the beginning of the 
heating season. <VKM-GAMV1 series only>

4

MAINTENANCE
(for a qualified service person only)

ONLY A QUALIFIED SERVICE PERSON IS ALLOWED TO 
PERFORM MAINTENANCE

DO NOT CHECK OPENING INSIDE THE UNIT BY YOURSELF.

WARNING

• BEFORE OBTAINING ACCESS TO TERMINAL DEVICES, 

ALL POWER SUPPLY CIRCUITS MUST BE INTERRUPTED.

• To clean the HRV, or maintenance be sure to stop operation, 

and turn the power switch off. It may cause electrical shock 
and it is very dangerous to touch the rotating part.

• Do not wash the HRV with water.

Doing so may result in an electric shock.

CAUTION

• Use gloves when cleaning.

Cleaning without gloves may cause injury.

• Watch your step.

Use caution, as this requires working in high places.

• Do not use benzene or thinner to clean the outside surfaces 

of the air conditioner.
This may cause cracks, discoloration, or machine trouble.

4.1 HOW TO CLEAN THE AIR FILTER

Clean the air filter when the display shows “

” (TIME TO 

CLEAN AIR FILTER).

It will display that it will operate for a set amount of time.

AT LEAST ONCE EVERY YEARS (FOR GENERAL OFFICE USE)
(CLEAN THE MORE FREQUENTLY IF NECESSARY.)

• Increase the frequency of cleaning if the unit is installed in a 

room where the air is etermely contaminated.

• If the dirt becomes impossible to clean, change the air filter 

(Air filter for exchange is optional).

(1) Detach the maintenance cover.

Go into ceiling through the inspection hatch, remove binding
metal of maintenance cover and take it off.

(Refer to figure 8-1)

(2) Detach the air filter.

Take out from the heat exchange elements.
 

(Refer to figure 8-2)

(3) Clean the air filter.

 (Refer to figure 9)

Use vacuum cleaner A) or wash the air filter with water B).

A) Using a vacuum cleaner
B) Washing with water

When the air filter is very dirty, use soft brush and neau-
tral detergent.

After cleaning, remove water and dry in the shade.

NOTE

• Do not wash the air filter with hot water of more than 50°C, 

as doing so may result in discoloration and/or deformation.

• Do not expose the air filter to fire, as doing so may  result in 

burning.

• Do not use gasoline, thinner, or other organic solvents.

This may cause discoloration or deformation.

(4) Fix the air filter.

If the air filter is washed, remove water completely and allow 
to dry for 20 to 30 minutes in the shade. When dried com-
pletely, install the air filter back in place. 

(Refer to figure 10)

NOTE

• Be sure to install the air filter after servicing.

(Missing air filter causes clogged heat exchange element.)
The air filter is an optional item and the replacement is 
available.

(5) Install the maintenance cover.

Refer to page 11 (4.1, (1)).

Consult your dealer if you want to change the time setting 
for when the filter sign goes on.

CAUTION

Always use the air filter.

If the air filter is not used, heat exchange elements will be clogged, 
possibly causing poor performance and subsequent failure.

4.2

HOW TO CLEAN THE HEAT EXCHANGE ELEMENT

AT LEAST ONCE EVERY TWO YEARS
(FOR GENERAL OFFICE USE)
(CLEAN THE ELEMENT MORE FREQUENTLY IF NECES-
SARY.)

WARNING

Please exchange the heat exchange element if you find 
that the knob of the heat exchange element is damaged 
or is deteriorated when cleaning it. 

There is falling danger.

(1) Detach the maintenance cover.

Refer to page 11 (4.1, (1)).

(2) Detach the air filter.

Refer to page 11 (4.1, (2)).

(3) Take out the heat exchange elements.

Pull out the air filter and then pull out the two heat 
exchanger elements. 

(Refer to figure 11)

For remote controllers which display the filter sign, turn on the 
power after maintenance, and press the filter sign reset button.

01_EN_3P130767-3G.fm  Page 11  Monday, March 5, 2007  10:05 AM

Summary of Contents for VKM100GAMV1

Page 1: ...ий OPERATION MANUAL Total Heat Exchanger HRV Heat Reclaim Ventilation with DX Coil MODELS Ceiling mounted duct type With DX coil Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 With DX coil VKM50GAV1 VKM80GAV1 VKM100GAV1 00_CV_3P130767 3G_01 fm Page 1 Wednesday March 7 2007 3 18 PM ...

Page 2: ...e al condizionatore d aria per interni sistema VRVII di tipo M RXYQ REYQ RXQ È anche possibile utilizzare questa unità come sistema indipendente L unità non può controllare la temperatura del locale Se ciò è necessario non installare l unità HRV da sola ma invece installare un altra unità interna Per controllare l unità utilizzare il telecomando del condizionatore d aria interno a sistema VRVII HR...

Page 3: ...e cover 6 Electric parts box 8 Heat exchanger elements 12 Gas pipe 13 Liquid pipe 16 Strainer included VKM GAMV1 series only VKM GAMV1 series only 14 Drain outlet 15 Humidifier Natural evaporating type 19 Remote controller Optional accessory 11 Direct expansion coil 9 Name plate 10 Air supply fan 4 Air filter Long life filter 5 Damper 21 EA Exhaust air to outdoors 22 OA Fresh air from outdoors out...

Page 4: ...dent system HRV With DX Coil Remote controller for indoor unit Outdoor unit Remote controller for VRV BRC1A62 3 2 Remote controller for VRV BRC1A62 4 1 5 3 Remote controller for VKM BRC1D527 EU only 4 5 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 4 1 2 3 2 00_CV_3P130767 3G_02 fm Page 2 Friday March 2 2007 6 37 PM ...

Page 5: ... BRC1D527 EU only 1 2 3 6 1 Heat exchanger element 2 2 Handle 3 Rail 9 1 Air filter 8 2 8 1 3 10 11 12 1 3 2 Remote controller for VRV BRC1A62 7 6 7 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 1 2 4 7 8 3 5 6 00_CV_3P130767 3G_02 fm Page 3 Friday March 2 2007 6 37 PM ...

Page 6: ...ot including air filters etc Be sure to stop the unit and turn off the power when cleaning or inspecting it As the fan is rotating at high speed it will cause injury Never inspect or service the unit by yourself Ask a qualified service person to perform this work The qualified service person Keep all flames away if the refrigerant leaks The refrigerant in the air conditioner is safe and normally d...

Page 7: ... When the HRV unit is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the limiting concen tration even when it leaks If the refrigerant leaks exceeding the level of limiting concentration an oxygen deficiency acci dent may happen Do not install the HRV unit at any place where flamma ble gas may leak out If the gas...

Page 8: ...ditioner CHECK LIST CORRESPONDING TO OPERATING NOISE Is the unit installed at the following locations a Location strong enough to support the weight of the unit and which will not amplify noise or vibration b Location where the warm air and the noise from the outlet vent of the outdoor unit will not bother neighbors Are any obstructions near the outlet vent of the outdoor unit They may reduce the ...

Page 9: ...tton for programming start and or stop time 18 Temperature setting button Use this button for setting the desired temperature of air conditioner combined with this unit This button can t use for this unit This unit can t change temperature setting 19 Filter sign reset button Refer to 4 1 HOW TO CLEAN THE AIR FILTER 20 Fan speed control button Press this button to select the fan speed of air condit...

Page 10: ...sing the unit as an independent system Ask your dealer what kind of system your system is set up for before operation For the operation of the remote controller for indoor unit and centralized controller refer to the instruction manual provided with each unit See the included operating manuals for details on how to operate each remote control OPERATION for EACH SYSTEM Sample system Refer to figure...

Page 11: ...t exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping HRV Heat exchange mode When air conditioner and HRV unit are not connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode When air conditioner and HRV unit are connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping...

Page 12: ...set for systems operating in cooling and heating at the same time is displayed on all remote controllers when using the VRVΙΙ system cooling only type but only and can be set Select the operating mode on a remote controller on which is not displayed and only for simultaneous cooling heat ing systems cannot be selected on remote controllers on which it is displayed See 3 2 if is displayed Press ven...

Page 13: ...ues driv ing factory setting The purpose of this is to maintain the amount of ventilation and humidifying The change of the layout in the room should be examined when the cold draft from air supplying opening is feared Though the fan can be stopped by the setting of remote con troller Do not stop the fan in the place where no ventilation by stop ping the fan may cause the influence of diffusion of...

Page 14: ...D SET THE TIMER WITH THE REMOTE CONTROLLER BRC1A62 Refer to figure 7 The timer is operated in the following two ways Programming the stop time The system stops operating after the set time has elapsed Programming the start time The system starts operating after the set time has elapsed The start and the stop time can be simultaneously pro grammed Press the timer mode start stop button several time...

Page 15: ...ered you must confirm the programmed actions Make sure the last schedule timer action you want to keep is selected schedule timer actions with a higher number will be deleted Now you must choose between 2 options 1 CONFIRM AND COPY TO NEXT DAY The schedule timer action programmed for the current day are also valid for the next day use the confirm last action and copy actions to next day function b...

Page 16: ...CESSARY Increase the frequency of cleaning if the unit is installed in a room where the air is etermely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Detach the maintenance cover Go into ceiling through the inspection hatch remove binding metal of maintenance cover and take it off Refer to figure 8 1 2 Detach the air filter Take ou...

Page 17: ...oller does not display any error code Usage under that status will lead to insufficient humidification and increased tap water consumption The solenoid valve should be checked at the beginning of the heating season For dealers 4 5 INSPECTION OF THE FAN MOTER NOTE When the fan motor fails the remote controller does not dis play any error code Usage under that status will lead to insufficient ventil...

Page 18: ...the power on The remote control buttons do not work well Measure Turn off the main power switch If the display INSPECTION UNIT No and the OPERATION lamp flash and the MALFUNCTION CODE appears Measure Notify and inform the model name and what the malfunction code indicates to your Daikin dealer There are other malfunctions Measure Stop the unit List of malfunction codes of Remote controller of the ...

Page 19: ...board and other electric parts h Is the float switch broken Replace the float switch i Is the water supply pressure sufficient Re set it so that there is sufficient pressure j Is there foreign matter in the feed water tank Clean the feed water tank After sales service and warranty After sales service WARNING Do not modify the unit This may cause electric shock or fire Do not disassemble or repair ...

Page 20: ... wear out parts The cycle is not the same as the warranty period Table 2 Replacement Cycle Lists Note 1 This table indicates main parts See the maintenance and inspection contract for details Note 2 This maintenance cycle indicates recommended lengths of time until the need arises for maintenance work in order to ensure the product is operational as long as possible Use for appropriate maintenance...

Page 21: ...3P130767 3G EM05A069A 0704 HT 00_CV_3P130767 3G_01 fm Page 2 Wednesday March 7 2007 3 18 PM ...

Reviews: