Daikin VKM100GAMV1 Operation Manual Download Page 19

English

14

In case of the malfunction with the code in white letters 
on the black background in the unit still operates.
However, be sure to have it inspected and repaired 
and as soon as possible.
If other than the above error codes are displayed, 
there is a possibility that the problem in question has 
occurred with a combined air conditioner or outdoor 
unit. See the operation manuals included with the air 
conditioners or outdoor units for details.

5.3

IF THE SYSTEM DOES NOT PROPERLY OPERATE 
EXCEPT FOR THE ABOVE MENTIONED CASE, AND 
NONE OF THE ABOVE MENTIONED MALFUNC-
TIONS IS EVIDENT, CONTACT YOUR DEALER, AND 
REQUEST FOR INVESTIGATION THE SYSTEM 
ACCORDING TO THE FOLLOWING PROCEDURES 
BY A QUALIFIED SERVICE PERSON

The following malfunctions must be cheched by a qualified 
service person. Do not check by yourself.

The unit does not operate at all.

a. Check if there is a power failure.

After power has been restored, start operation again.

b. Check if the fuse has blown.

Change the fuse.

c. Check if breaker has worked.

Contact your dealer.

d. Are there any problems with the power or wiring?

Inspect the power and wiring.

e. Are there any problems with the fan unit?

Inspect the fan motor and fan.

Amount of discharged air is small and the discharging 
sound is high.

a. Check if the air filter and heat exchange element are

clogged. (Check both SA and RA air filter. Check both
sides of elements.)
Clean the air filter and heat exchange element.

Amount of discharged air is large and so is the sound.

a. Check if the air filter and heat exchange element are not

installed.
Install the air filter and heat exchange element.

It dries usually in winter. <VKM-GAMV1 series only>

a. Is the water supply service valve open?

Open the water supply service valve.

b. Have you lowered setting on the humidistat (locally pro-

cured) too far?
Correct the setting.

Humidifies very little or not at all. <VKM-GAMV1 series only>

a. Is there water in the water supply tank?
b. Is water being supplied?

Inspect the water supply pipes and supply the water.

c. Is the strainer clogged?

Clean the strainer.

d. Is the solenoid valve broken (i.e. won’t open)?

Replace the solenoid valve.

e. Is the humidifier element torn?

Replace.

f. Has the water resistance of the humidifier element dropped?

Replace the humidifier element.

g. Are the control circuits broken?

Replace the printed circuit board and other electric parts.

h. Is the float switch broken?

Replace the float switch.

i. Is the water supply pressure sufficient?

Re-set it so that there is sufficient pressure.

j. Is there foreign matter in the feed water tank?

Clean the feed water tank.

After-sales service and warranty

After-sales service:

WARNING

• Do not modify the unit.

This may cause electric shock or fire.

• Do not disassemble or repair the unit.

This may cause electric shock or fire.
Contact your dealer.

• If the refrigerant leaks, keep out of fire.

The refrigerant used in this unit is safe.
Although the refrigerant does not usually leak, if the refriger-
ant leaks out into a room and comes in contact with the com-
bustible air in the equipment such as fan heater, stove, oil 
(gas) cooker, etc., it will cause toxic gas to be generated.
When a refrigerant leakage failure has been repaired, con-
firm a service person that the leakage point has been cor-
rected surely before restarting operation.

• Do not remove or reinstall the unit by yourself.

Incomplete installation may cause a water leakage electric 
shock and fire.
Contact your dealer.

„

When asking your dealer to repair, inform related 
staff of the details as follows:

• Shipping date and installation date: 
• Malfunction: 

Inform the staff of the defective details.
(Malfunction code being displayed on 
the remote controller.)

• Name, address, telephone number

„

Repair where the warranty term is expired

Contact your dealer.  If necessary to repair, pay service is 
available.

„

Minimum storage period of important parts

Even after a certain type of air conditioner is discontinued, 
we have the related important parts in stock for 6 years at 
least.
The important parts indicate parts essential to operate the air 
conditioner.

„

Recommendations for maintenance and inspec-
tion

Since dust collects after using the unit for several years, the 
performance will be deteriorated to some extent.
Taking apart and cleaning inside require technical expertise, 
so we recommend entering a maintenance and inspection 
contract (at a cost) separate from normal maintenance.

„

Recommended inspection and maintenance 
cycles
[Note: The maintenance cycle is not the same as 
the warranty period.]

Table 1 assumes the following usage conditions.
• Normal use without frequent starting and stopping of the 

machine.
(Although it varies with the model, we recommend not start-
ing and stopping the machine more than 6 times/hour for 
normal use.)

• Operation of the product is assumed to be 10 hours/day, 

2500 hours/year.

01_EN_3P130767-3G.fm  Page 14  Monday, March 5, 2007  10:05 AM

Summary of Contents for VKM100GAMV1

Page 1: ...ий OPERATION MANUAL Total Heat Exchanger HRV Heat Reclaim Ventilation with DX Coil MODELS Ceiling mounted duct type With DX coil Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 With DX coil VKM50GAV1 VKM80GAV1 VKM100GAV1 00_CV_3P130767 3G_01 fm Page 1 Wednesday March 7 2007 3 18 PM ...

Page 2: ...e al condizionatore d aria per interni sistema VRVII di tipo M RXYQ REYQ RXQ È anche possibile utilizzare questa unità come sistema indipendente L unità non può controllare la temperatura del locale Se ciò è necessario non installare l unità HRV da sola ma invece installare un altra unità interna Per controllare l unità utilizzare il telecomando del condizionatore d aria interno a sistema VRVII HR...

Page 3: ...e cover 6 Electric parts box 8 Heat exchanger elements 12 Gas pipe 13 Liquid pipe 16 Strainer included VKM GAMV1 series only VKM GAMV1 series only 14 Drain outlet 15 Humidifier Natural evaporating type 19 Remote controller Optional accessory 11 Direct expansion coil 9 Name plate 10 Air supply fan 4 Air filter Long life filter 5 Damper 21 EA Exhaust air to outdoors 22 OA Fresh air from outdoors out...

Page 4: ...dent system HRV With DX Coil Remote controller for indoor unit Outdoor unit Remote controller for VRV BRC1A62 3 2 Remote controller for VRV BRC1A62 4 1 5 3 Remote controller for VKM BRC1D527 EU only 4 5 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 4 1 2 3 2 00_CV_3P130767 3G_02 fm Page 2 Friday March 2 2007 6 37 PM ...

Page 5: ... BRC1D527 EU only 1 2 3 6 1 Heat exchanger element 2 2 Handle 3 Rail 9 1 Air filter 8 2 8 1 3 10 11 12 1 3 2 Remote controller for VRV BRC1A62 7 6 7 UNIT No GROUP Remote controller for VKM BRC1D527 EU only 1 2 4 7 8 3 5 6 00_CV_3P130767 3G_02 fm Page 3 Friday March 2 2007 6 37 PM ...

Page 6: ...ot including air filters etc Be sure to stop the unit and turn off the power when cleaning or inspecting it As the fan is rotating at high speed it will cause injury Never inspect or service the unit by yourself Ask a qualified service person to perform this work The qualified service person Keep all flames away if the refrigerant leaks The refrigerant in the air conditioner is safe and normally d...

Page 7: ... When the HRV unit is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the limiting concen tration even when it leaks If the refrigerant leaks exceeding the level of limiting concentration an oxygen deficiency acci dent may happen Do not install the HRV unit at any place where flamma ble gas may leak out If the gas...

Page 8: ...ditioner CHECK LIST CORRESPONDING TO OPERATING NOISE Is the unit installed at the following locations a Location strong enough to support the weight of the unit and which will not amplify noise or vibration b Location where the warm air and the noise from the outlet vent of the outdoor unit will not bother neighbors Are any obstructions near the outlet vent of the outdoor unit They may reduce the ...

Page 9: ...tton for programming start and or stop time 18 Temperature setting button Use this button for setting the desired temperature of air conditioner combined with this unit This button can t use for this unit This unit can t change temperature setting 19 Filter sign reset button Refer to 4 1 HOW TO CLEAN THE AIR FILTER 20 Fan speed control button Press this button to select the fan speed of air condit...

Page 10: ...sing the unit as an independent system Ask your dealer what kind of system your system is set up for before operation For the operation of the remote controller for indoor unit and centralized controller refer to the instruction manual provided with each unit See the included operating manuals for details on how to operate each remote control OPERATION for EACH SYSTEM Sample system Refer to figure...

Page 11: ...t exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping HRV Heat exchange mode When air conditioner and HRV unit are not connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode When air conditioner and HRV unit are connected via duct Operation mode VRV Cooling mode HRV Heat exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping...

Page 12: ...set for systems operating in cooling and heating at the same time is displayed on all remote controllers when using the VRVΙΙ system cooling only type but only and can be set Select the operating mode on a remote controller on which is not displayed and only for simultaneous cooling heat ing systems cannot be selected on remote controllers on which it is displayed See 3 2 if is displayed Press ven...

Page 13: ...ues driv ing factory setting The purpose of this is to maintain the amount of ventilation and humidifying The change of the layout in the room should be examined when the cold draft from air supplying opening is feared Though the fan can be stopped by the setting of remote con troller Do not stop the fan in the place where no ventilation by stop ping the fan may cause the influence of diffusion of...

Page 14: ...D SET THE TIMER WITH THE REMOTE CONTROLLER BRC1A62 Refer to figure 7 The timer is operated in the following two ways Programming the stop time The system stops operating after the set time has elapsed Programming the start time The system starts operating after the set time has elapsed The start and the stop time can be simultaneously pro grammed Press the timer mode start stop button several time...

Page 15: ...ered you must confirm the programmed actions Make sure the last schedule timer action you want to keep is selected schedule timer actions with a higher number will be deleted Now you must choose between 2 options 1 CONFIRM AND COPY TO NEXT DAY The schedule timer action programmed for the current day are also valid for the next day use the confirm last action and copy actions to next day function b...

Page 16: ...CESSARY Increase the frequency of cleaning if the unit is installed in a room where the air is etermely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Detach the maintenance cover Go into ceiling through the inspection hatch remove binding metal of maintenance cover and take it off Refer to figure 8 1 2 Detach the air filter Take ou...

Page 17: ...oller does not display any error code Usage under that status will lead to insufficient humidification and increased tap water consumption The solenoid valve should be checked at the beginning of the heating season For dealers 4 5 INSPECTION OF THE FAN MOTER NOTE When the fan motor fails the remote controller does not dis play any error code Usage under that status will lead to insufficient ventil...

Page 18: ...the power on The remote control buttons do not work well Measure Turn off the main power switch If the display INSPECTION UNIT No and the OPERATION lamp flash and the MALFUNCTION CODE appears Measure Notify and inform the model name and what the malfunction code indicates to your Daikin dealer There are other malfunctions Measure Stop the unit List of malfunction codes of Remote controller of the ...

Page 19: ...board and other electric parts h Is the float switch broken Replace the float switch i Is the water supply pressure sufficient Re set it so that there is sufficient pressure j Is there foreign matter in the feed water tank Clean the feed water tank After sales service and warranty After sales service WARNING Do not modify the unit This may cause electric shock or fire Do not disassemble or repair ...

Page 20: ... wear out parts The cycle is not the same as the warranty period Table 2 Replacement Cycle Lists Note 1 This table indicates main parts See the maintenance and inspection contract for details Note 2 This maintenance cycle indicates recommended lengths of time until the need arises for maintenance work in order to ensure the product is operational as long as possible Use for appropriate maintenance...