Installation manual
11
250FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P415946-1 – 2015.08
Example
When adjusting the ventilation air flow to low setting in the group
setting mode, enter the mode No., "19" setting switch No., "0" and
setting position No., "01".
List of Settings
Mode No.
Setting
switch No.
Description of Setting
Setting position No.(Caution *1.)
Group
settings
Individual
settings
01
02
03
04
05
06
17
27
0
Filter cleaning time setting
Approx. 2500
hours
Approx. 1250
hours
No
counting
–
–
–
2
Precool/preheat on/off setting
Off
On
–
–
–
–
3
Precool/preheat time setting
30 min
45 min
60 min
–
–
–
4
Fan speed initial setting
Normal
Ultra high
–
–
–
–
5
Yes/No setting for direct duct
connection with VRV system
No duct (Air
flow setting)
With duct
(fan off)
–
–
–
–
Setting for cold areas (Fan
operation selection for heater thermo
OFF)
–
–
No duct
With duct
Fan off
Fan L
Fan off
Fan L
7
Centralized/individual setting
Centralized
Individual
–
–
–
–
8
Centralized zone interlock
setting
No
Yes
Priority on
operation
–
–
–
9
Preheat time extension setting
0 min
30 min
60 min
90 min
–
–
18
28
0
External signal JC/J2
Last
command
Priority on
external
input
–
–
–
–
1
Setting for direct Power ON
Off
On
–
–
–
–
2
Auto restart setting
Off
On
–
–
–
–
3
Setting for external damper
–
–
On
–
–
–
4
Indication of ventilation mode/Not
indication
Indication
No
Indication
–
–
–
–
7
Fresh up air supply/exhaust
setting
No
Indication
No
Indication
Indication
Indication
–
–
Supply
Exhaust
Supply
Exhaust
–
–
8
External input terminal function
selection (between J1 and JC)
Fresh-up
Overall alarm
Overall
malfunction
Forced off
Fan forced
off
Air flow
increase
9
KRP50-2 output switching
selection (between 1 and 3)
Fan on/off
Abnormal
–
–
–
–
19
29
0
Ventilation air flow setting
Low
Low
Low
Low
High
High
2
Ventilation mode setting
Automatic
Exchange
By pass
–
–
–
3
"Fresh Up" on/off setting
Off
On
–
–
–
–
8
Electric heater setting
No delay
No delay
On, off delay On, off delay
–
–
CAUTION
1.
The setting positions are set at "01" at the factory.
The ventilation air flow, however, is set at "06"
(medium) in the HRV unit. When lower or higher
setting is desired, change the setting after installation.
2.
Group number setting for centralized controller
Mode No. 00: Group controller
Mode No. 30: Individual controller
Regarding the setting procedure, refer to the section
"Group number setting for centralized control" in the
operating manual of either the on/off controller or the
central controller.