250FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P415946-1 – 2015.08

Installation manual

14

Connecting the remote controller for HRV

The remote controller for HRV cannot be used for starting/stopping
operation or for timer operation. (The centralized control indication
will be lit.)

To set pre-cool/pre-heat function settings, change the remote control
air flow rate setting from medium (M) to high (H), etc., perform initial
settings from the remote controller for HRV.

Since it will become a two-remote-control system, perform master/
slave setting as shown below.

Refer to "preforming initial settings" in the remote control instruction
manual.

Example 4:

To set the pre-cool/pre-heat reservation function to on and have the
HRV start operating 60 minutes after the air conditioner has started,
set the same numbers as shown in example 1 using the remote
controller for HRV.

Example 5:

To increase the remote control air ventilation rate setting from
Medium to High, set the same numbers as shown in example 2 using
the remote controller for HRV.

Set the switches of the HRV unit PCB to the default factory settings.

Determination of heating/cooling selection rights for VRV-
systems is performed using the remote controller for HRV.
The heating/cooling selection rights can be enabled or disabled
using the ventilation mode button of the remote controller for
HRV.
This operation cannot be performed with the remote controller
for air conditioner.

Direct duct connection system for 1-group operation system

Line connections and the settings of the switches on the HRV unit
PCB should be the same as for "Standard system for 1-group
system".

Set the switches of the HRV unit PCB to the default factory settings.

1

Be sure to set the initial settings to Direct duct connection:
Enabled.

When the remote controller for HRV is not yet connected,
initial settings can be performed using the air conditioner
remote control. Set the mode number to "17", the setting
switch number to "5", and the setting position number to "02"
according to the procedure in 

"Local setting" on page 10

.

When the remote controller for HRV, initial settings should be
performed using the remote controller for HRV. Set the same
numbers as described above when using the remote
controller for air conditioner according to the procedure
"Making initial settings" in the remote control instruction
manual.

2

Settings for other HRV functions should be made using the
same method as in "Standard system for 1-group system".

Linked control with more than two groups

Mount the optional
KRP2A61 Adapter PCB for
remote control on the
electric component
mounting base of one HRV
unit.

A maximum of 64 air
conditioners and HRV
units can be connected to
the F1 and F2 terminals.

Use the remote controller
of the air conditioner to
make the initial settings.

Remote control

Master/slave setting

Remote controller for air conditioner

Slave

Remote controller for HRV

Master

Air ventilation 

rate setting 

using remote 

control

Default factory settings

When set 

as in example 5

Low

Low (L) air flow rate

Low (L) air flow rate

High

Medium (M) air flow rate

High (H) air flow rate

Default factory settings

air flow rate

Heating/cooling selection rights

Operation switchover control display

Enabled

Not lit

Disabled

Lit

Not set

Blinking

P1
P2

P1P2

P1 P2

P1 P2

VRV

1

2

5

3

4

1

Remote controller for air 
conditioner

4

Medium (M) air flow rate

2

Remote controller for HRV

5

When the remote controller for 
HRV is connected, set the 
switches on the HRV unit PCB to 
the default factory settings.

3

Maximum connection line length: 
500 m

H M L

SS1

1

Remote controller for air 
conditioner

2

Connecting line can be 
extended up to 1000 m 
maximum

3

Optional distant control 
adapter KRP2A61

P1
P2

P1P2

P1 P2

P1 P2

VRV

1

2

3

4

1

Remote controller for air 
conditioner

3

Maximum connection line length: 
500 m

2

Remote controller for HRV

4

Medium (M) air flow rate

VRV

VRV

HRV  1

HRV  2

X11A

F1 F2

P1

P2

P1 P2

F1 F2

F1 F2

1

2

3

Summary of Contents for VAM250FC

Page 1: ...aim Ventilation of Hergebruik van warmte Type voor plafondmontage met kanaalaansluiting Nederlands Intercambiador de Calor Total HRV Ventilaci n de Reclamo de Calor Tipo de conducto montado en el tech...

Page 2: ...50 250 149 104 269 718 760 600 164 90 124 200 20 20 164 3 4 1 9 2 5 7 8 6 12 11 10 2 4 14 15 16 13 A B VAM150F 145 97 VAM250F 132 146 2 2 VAM 280 415 150 250 600 415 280 112 2 3 18 11 9 1 18 10 10 17...

Page 3: ...ertificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifika...

Page 4: ...lation Always use the air filter If the air filter is not used heat exchange elements will be clogged possibly causing poor performance and subsequent failure Do not change operations suddenly It can...

Page 5: ...ment this product may cause radio interference in which case the user may be required to take adequate measures 1 Air suction discharge grille option 2 Inspection hole 450 mm field supply 3 Maintenanc...

Page 6: ...he indoor air intake as far as from the opening of the exhaust suction 4 Use the duct applicable to the model of unit used Refer to the outline drawing 5 Install the two outdoor ducts with down slope...

Page 7: ...operation system Since all VRV units are connected to a single line in view of installation all VRV units are subjects for operation If there are problems operating all VRV units do not use this syste...

Page 8: ...trol device All individual control on page 15 Zone control system Use of the centralized controller enables zone control via the centralized control line maximum of 64 zones The central controller dis...

Page 9: ...eep total current of crossover wiring between indoor units less than 12 A When using two power wiring of a gauge greater than 2 mm2 1 6 branch the line outside the terminal board of the unit in accord...

Page 10: ...conform to Japanese standards stipulated in the Electric Appliance Regulatory Act Transmission wiring need not be grounded when using sheathed wire 1 2 5 3 4 6 7 8 A B C 1 Terminal board for transmis...

Page 11: ...controller for incorporating function of the external damper in the system Mode No 18 Group control or 28 Individual control Setting switch No 3 Setting position No 03 CAUTION Before opening the cove...

Page 12: ...required Install the heater control kit to the outside of the switch box of the HRV unit as shown below For more detailed information on how to install the BRP4A50 option kit see the installation man...

Page 13: ...ngs for individual units under group control when mode No 27 28 or 29 is selected press the TIMER SETTING ON OFF button to select the unit No for which the settings are to be made This process is not...

Page 14: ...command Priority on external input 1 Setting for direct Power ON Off On 2 Auto restart setting Off On 3 Setting for external damper On 4 Indication of ventilation mode Not indication Indication No In...

Page 15: ...and Heat Exchange mode Heat Exchange mode In this mode the air passes through the heat exchange element to effect Total Heat Exchanging ventilation Bypass mode In this mode the air does not pass throu...

Page 16: ...l pre heat function When the pre cool pre heat function is set the HRV unit switches on at the preset time 30 45 or 60 minutes after the VRV system air conditioner begins cooling or heating operation...

Page 17: ...formed using the air conditioner remote control Set the mode number to 17 the setting switch number to 5 and the setting position number to 02 according to the procedure in Local setting on page 10 Wh...

Page 18: ...r flow rate from High to Ultra High connect the remote controller for the air conditioner to HRV and make settings on site Refer to Initial setting under item Local setting on page 10 All individual c...

Page 19: ...setting of the group number refer to the section on the centralized control group number setting in the operating instructions of the Centralized controller Refer to the section All individual control...

Page 20: ...ample of control wiring System description TEST RUN After completing the installation of the system check again to make sure that No error was made in wiring or switch setting on the printed circuit b...

Page 21: ...Magnetic relay M1D M1D Motor Damper motor M1F Motor Air supply Fan motor M2F Motor Exhaust Fan motor Q1L Q2L Thermo switch M1F M2F Built in R1T Thermistor Indoor air R2T Thermistor Outdoor air S1W Li...

Page 22: ...NOTES...

Page 23: ...NOTES...

Page 24: ...4P415946 1 2015 08 Copyright 2015 Daikin...

Reviews: