background image

Installation manual

9

250FC

Total Heat Exchanger

HRV (Heat Reclaim Ventilation)

4P415946-1 – 2015.08

How to install the optional adapter circuit board 

(KRP2A61, KRP50-2)

When installing the optional adaptor circuit board, it is necessary to
prepare the fixing box (KRP50-2A90)

1

Open the electrical compartment cover by following the
procedure described in the section 

"Opening the switch box" on

page 8

".

2

Remove the securing screw, and install the adapter circuit
board.

3

After the wires are connected, fasten the electrical compartment
cover.

Installation

How to install the optional heater control kit (BRP4A50)

When operating the HRV units at or below –10°C of the outdoor air
temperature, use a field supplied preheater to preheat outdoor air.

The BRP4A50 kit is required to have an ON/OFF delay control when
a preheater is used (initial setting is required).

Install the heater control kit to the outside of the switch box of the
HRV unit as shown below.

For more detailed information on how to install the BRP4A50 option
kit, see the installation manual delivered with the option kit.

KRP50-2A90

Components

Fixing screw

3 pieces

Clamp

2 pieces

1

5

4

3

2

3

A

B

1

Fixing board

2

PCB support (Attached to adapter PCB)

3

Fixing screw

4

Lid

5

Switch box

Applicable adapter name

Kit name

A

Adapter PCB for Humidifier

KRP50-2

B

Adapter PCB Remote controller

KRP2A1

CAUTION

For electric heater, safety devices, and installation
location, follow the standards or regulations of each
country.

Use a nonflammable duct for the electric heater. Be
sure to keep a distance of 

2 m between the heater

and HRV unit for safety.

Use a different power supply and different circuit
breaker for the HRV units and electric heaters.

For setting the initial setting on the remote controller,
see 19(29)-8-03 or 19(29)-8-04 in chapter 

"List of

Settings" on page 11

.

1

Switch box

2

Heater control kit

3

Fixing screw

4

Lid

4

3

1

2

3

Summary of Contents for VAM250FC

Page 1: ...aim Ventilation of Hergebruik van warmte Type voor plafondmontage met kanaalaansluiting Nederlands Intercambiador de Calor Total HRV Ventilaci n de Reclamo de Calor Tipo de conducto montado en el tech...

Page 2: ...50 250 149 104 269 718 760 600 164 90 124 200 20 20 164 3 4 1 9 2 5 7 8 6 12 11 10 2 4 14 15 16 13 A B VAM150F 145 97 VAM250F 132 146 2 2 VAM 280 415 150 250 600 415 280 112 2 3 18 11 9 1 18 10 10 17...

Page 3: ...ertificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifika...

Page 4: ...lation Always use the air filter If the air filter is not used heat exchange elements will be clogged possibly causing poor performance and subsequent failure Do not change operations suddenly It can...

Page 5: ...ment this product may cause radio interference in which case the user may be required to take adequate measures 1 Air suction discharge grille option 2 Inspection hole 450 mm field supply 3 Maintenanc...

Page 6: ...he indoor air intake as far as from the opening of the exhaust suction 4 Use the duct applicable to the model of unit used Refer to the outline drawing 5 Install the two outdoor ducts with down slope...

Page 7: ...operation system Since all VRV units are connected to a single line in view of installation all VRV units are subjects for operation If there are problems operating all VRV units do not use this syste...

Page 8: ...trol device All individual control on page 15 Zone control system Use of the centralized controller enables zone control via the centralized control line maximum of 64 zones The central controller dis...

Page 9: ...eep total current of crossover wiring between indoor units less than 12 A When using two power wiring of a gauge greater than 2 mm2 1 6 branch the line outside the terminal board of the unit in accord...

Page 10: ...conform to Japanese standards stipulated in the Electric Appliance Regulatory Act Transmission wiring need not be grounded when using sheathed wire 1 2 5 3 4 6 7 8 A B C 1 Terminal board for transmis...

Page 11: ...controller for incorporating function of the external damper in the system Mode No 18 Group control or 28 Individual control Setting switch No 3 Setting position No 03 CAUTION Before opening the cove...

Page 12: ...required Install the heater control kit to the outside of the switch box of the HRV unit as shown below For more detailed information on how to install the BRP4A50 option kit see the installation man...

Page 13: ...ngs for individual units under group control when mode No 27 28 or 29 is selected press the TIMER SETTING ON OFF button to select the unit No for which the settings are to be made This process is not...

Page 14: ...command Priority on external input 1 Setting for direct Power ON Off On 2 Auto restart setting Off On 3 Setting for external damper On 4 Indication of ventilation mode Not indication Indication No In...

Page 15: ...and Heat Exchange mode Heat Exchange mode In this mode the air passes through the heat exchange element to effect Total Heat Exchanging ventilation Bypass mode In this mode the air does not pass throu...

Page 16: ...l pre heat function When the pre cool pre heat function is set the HRV unit switches on at the preset time 30 45 or 60 minutes after the VRV system air conditioner begins cooling or heating operation...

Page 17: ...formed using the air conditioner remote control Set the mode number to 17 the setting switch number to 5 and the setting position number to 02 according to the procedure in Local setting on page 10 Wh...

Page 18: ...r flow rate from High to Ultra High connect the remote controller for the air conditioner to HRV and make settings on site Refer to Initial setting under item Local setting on page 10 All individual c...

Page 19: ...setting of the group number refer to the section on the centralized control group number setting in the operating instructions of the Centralized controller Refer to the section All individual control...

Page 20: ...ample of control wiring System description TEST RUN After completing the installation of the system check again to make sure that No error was made in wiring or switch setting on the printed circuit b...

Page 21: ...Magnetic relay M1D M1D Motor Damper motor M1F Motor Air supply Fan motor M2F Motor Exhaust Fan motor Q1L Q2L Thermo switch M1F M2F Built in R1T Thermistor Indoor air R2T Thermistor Outdoor air S1W Li...

Page 22: ...NOTES...

Page 23: ...NOTES...

Page 24: ...4P415946 1 2015 08 Copyright 2015 Daikin...

Reviews: