SiE71-202
Control Functions
Control Functions
25
Note:
1. All the setting can be made by the remote controller for VRV and HRV unit.
The setting of mode No. 19 (29) and 40 can be made only by the remote controller for VRV unit. The
mode No. 30 is used for the individual setting such as the calculation of power bill, etc.
2. The mode No. in ( ) is used for making individual setting of each unit.
3. Group number setting for centralized controller
1. Mode no. 00: Group controller
2. Mode no. 30: Individual controller
∗
Regarding the setting procedure, refer to the section “Group number setting for centralized control” in
the operating manual of either the on / off controller or the central controller.
Caution
1. The setting positions are set at “01” at the factory.
The ventilation air flow, however, is set at “05” (medium) in the HRV unit. When lower or higher setting
is desired, change the setting after installation.
Indication of
ventilation mode /
Not indication
Field
setting
18(28)
4
Indication
No
Indication
—
—
—
—
Fresh up air
supply / exhaust
setting
7
No
Indication
No
Indication
Indication
Indication
—
—
Supply
Exhaust
Supply
Exhaust
—
—
External input
terminal function
selection
(between J1 and
JC)
8
Fresh up
Overall
alarm
Overall
malfunction
Forced
off
Fan
forced off
Air flow
increase
KRP50-2 output
switching
selection
(between 1 and
3)
9
Humidify
Abnormal
Fan on / off
—
—
—
Air flow setting
19(29)
0
Low
Low
Low
Low
High
High
Ventilation mode
setting
2
Automatic
Total heat
exchange
Normal
—
—
—
Fresh up
operation
3
OFF
ON
—
—
—
—
Electric heater
setting
8
No delay
No delay
ON / OFF
Delay
ON / OFF
Delay
—
—
Refer to E/D
“INSTALLATION
MANUAL”
Error record
display
Service
40
Refer to
operation
manual for
remote controller
of air conditioner
Forced
ventilation fan On
43
Unit No.
allocation
45
Details of setting
Mode
Setting
mode
Setting
switch
No.
Setting position
Operation method
01
02
03
04
05
06
Summary of Contents for VAM 1000FAVE
Page 5: ...SiE71 202 iv Table of Contents ...
Page 13: ...General Constructions SiE71 202 4 General Constructions ...
Page 37: ...Control Functions SiE71 202 28 Control Functions ...
Page 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Page 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Page 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Page 77: ...Appendix SiE71 202 68 Appendix ...
Page 81: ...SiE71 202 iv Index ...