SiE71-202
Supplementary Explanation
Supplementary Explanation
57
Unit No.
reallocation (Mode
No.45)
Step 1
With equipment in field setting mode, press the
button for more than 4 seconds to enter
service mode.
Step 2
Mode No.: UP
↔
Mode No.: DOWN
Use [MODE] and [AIR VOLUME] to select mode No.45.
Step 3
Use
to select setting Unit No.
Step 4
Press
or
button to select Unit No. after reallocation.
Step 5
Press
button once to enter settings.
Step 6
Press
button to return to normal mode.
Unit No. before reallocation
Unit No. after reallocation
3
4
1, 6
5
4
2
(HL042)
Field setting mode
Mode No.