Control Functions
SiE71-202
22
Control Functions
1.2.2
Pre-cool/Pre-heat
Pre-cool/pre-heat operations require the following conditions.
1. System
Pre-heat operation is possible only in air conditioner linked system (1 group, 2-group link). Check the
system first.
2. Heat recovery ventilation setting
Set Preheat ON/OFF to ON.
Pre-cool/pre-heat On/OFF setting can be made in air conditioner or using field setting mode of LCD
remote controller of heat recovery ventilation unit. (Pre-cool time can be set between 30 and 60 min,
and pre-heat time can be set between 30 and 150 min.)
3. Others
a) Heat recovery ventilation unit must be in non-operating condition for two consecutive hours or more
prior to pre-cool/pre-heat operation.
b) Temperature control mode of the air conditioner must be set to Cool, Heat or Dry.
Note:
Operation standby indication is displayed only on LCD remote controller of heat recovery ventilation unit.
Operation
Normal ventilation
mode selection
Pre-cool/pre-heat
time over
Stop
Air conditioner
ON/OFF
Operation
Heat reco
v
e
ry
v
entilation unit
Ventilation fan motor
Damper motor
(ventilation mode)
Pre-cool/pre-heat ventilation
ON
ON
Total heat exchange ventilation
Normal ventilation
Total heat
exchange
ventilation
Remote controller
indication
Operation lamp
Lamp
ON
Lamp
ON
Operation standby
indication
(HL022)
Summary of Contents for VAM 1000FAVE
Page 5: ...SiE71 202 iv Table of Contents ...
Page 13: ...General Constructions SiE71 202 4 General Constructions ...
Page 37: ...Control Functions SiE71 202 28 Control Functions ...
Page 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Page 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Page 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Page 77: ...Appendix SiE71 202 68 Appendix ...
Page 81: ...SiE71 202 iv Index ...