SiE71-202
Troubleshooting
Troubleshooting
39
1.6
Damper System Error (Alarm)
Remote Controller
LCD Display
Error Code
6A
Inspection
—
Unit No.
5
LED Indication
Remote Controller
4
Main Unit
5
Error Detection
Method
Measurement of damper motor limit ON/OFF time.
Error Generating
Conditions
When damper motor limit switch 1 (or 2) remains ON (or OFF) for more than a certain time duration
after ventilation mode is changed.
When damper motor limit switch 1 (or 2) repeats ON/OFF operations after damper motor 1 (or 2) stops.
Possible Causes
Faulty damper motor or limit switch
Broken wire in cable
Faulty contact in connector (including relay connector)
Faulty control PCB assembly
Troubleshooting
Note:
Note 1:
Place tester probes on connectors of limit switch. Move switch by hand and check continuity. If tester
indicates 0
Ω
when limit switch turns on, and infinity when it turns off, limit switch is normal.
Place tester probes on connectors of damper motor and check resistance. If tester indicates approx. 17
k
Ω
in 200-V model, damper motor is normal.
Check connectors
(X3A or X4A) (X5A or
X6A) on PCB assembly
of damper motor unit.
Is
damper
motor unit
operating
normally?
Note 1
YES
YES
YES
Connect relay connector.
Connect connectors.
Replace damper motor unit.
Replace control PCB assembly.
Is
relay
connector of
damper motor unit
connected?
NO
(HF005)
NO
Are connectors
connected?
NO
Check resistance and voltage
(HL029)
Summary of Contents for VAM 1000FAVE
Page 5: ...SiE71 202 iv Table of Contents ...
Page 13: ...General Constructions SiE71 202 4 General Constructions ...
Page 37: ...Control Functions SiE71 202 28 Control Functions ...
Page 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Page 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Page 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Page 77: ...Appendix SiE71 202 68 Appendix ...
Page 81: ...SiE71 202 iv Index ...