T-CU19-JAN24-1
Page 22
Table 15: Suction Pipe Size Selection
Model
% Refrigerant flow
Oil return speed limited (rps) for each pipe size
1 3/8
1 1/4
1 1/8
1
7/8
3/4
5/8
1/2
3/8
1/4
LR
M
IFS
0
3
00
AXY1
100%
94
70
51
37
26
20
20
20
90%
105
78
56
40
28
20
20
20
80%
118
88
62
44
31
20
20
20
70%
100
71
50
34
22
20
20
60%
118
84
57
39
25
20
20
50%
101
68
45
29
20
20
40%
85
54
34
20
20
30%
114
72
43
24
20
20%
109
61
34
20
10%
60
26
LR
M
IFS
0
6
00
AXY1
100%
57
44
34
24
20
20
20
20
20
90%
75
49
37
27
20
20
20
20
20
80%
117
55
41
30
21
20
20
20
20
70%
71
47
34
24
20
20
20
20
60%
55
40
28
20
20
20
20
50%
85
47
33
21
20
20
20
40%
59
40
26
20
20
20
30%
53
34
20
20
20
20%
51
30
20
20
10%
58
29
20
LR
M
IFS
0
9
00
AXY1
100%
52
42
32
25
20
20
20
20
20
20
90%
58
46
36
27
20
20
20
20
20
20
80%
64
52
40
30
22
20
20
20
20
20
70%
72
59
46
34
25
20
20
20
20
20
60%
82
67
53
40
29
20
20
20
20
20
50%
97
78
63
47
34
24
20
20
20
20
40%
118
95
76
59
43
29
20
20
20
20
30%
97
75
56
39
25
20
20
20
20%
108
80
57
37
22
20
20
10%
105
71
42
22
20
Controller Settings
The controller inside the condensing unit had been preset from factory, in accordance to the following lists:
Note: In case controller is replaced, it shall be checked to ensure correct refrigerant selection and compressor model (Refer
Procedure Refrigerant Selection).
Table 16: Controller Default Settings
B - Inputs/Outputs
Mask Index
UoM
Type
Channel
Min Max Offset
Analog Input
Bab01
barg
0-5V
B1
0 17.3
0
Bab05
°C
NTC
B3
0
Bab07
barg
0-5V
B2
0 34.5
0
Bab15
°C
NTC
B8
0
Bab29
°C
HTNC
B4
0
Digital input
Logic
Baa00
NC
ID01
Baa01
NC
-
Baa02
NO
ID03
Analog Output
Bad01
PWM (0-10V)
1
Digital Output
Bacbt
NO
DO6
Bacen
NO
DO5
Baceq
NO
DO8
Bacev
NO
DO3