background image

 

T-CU19-JAN24-1 

 

 

Page 21 

System Charge 

 

Never start the compressor under vacuum. 
Ensure an adequate liquid charge has been 
introduced to the high side of the system 
before starting to ensure a minimum 
operating pressure on the suction side of 0.5 

bar is maintained, otherwise overheating of the scrolls 
and subsequent damage may occur. Refrigerant blend 
must be charged in liquid form to avoid change of 
chemical properties.  
 

Condensing unit must not run, and service valves must be 
closed for initial refrigerant charge. The service port on the 
receiver outlet rotolock valve (liquid line) can be used for 
initial charge. Charge refrigerant as close as possible to the 
nominal system charge (will varying depend on the tube 
size and lengths) before the compressor with all service 
valves turn to OPEN position.  
Compressor Charge Limit = 6kgs 
 
For the adjustment of refrigerant charge until the 
installation reaching a level of stable nominal working 
condition, slowly throttling liquid in through schrader valve 
on the suction service valve. Charge system until reaching 
suction superheat 6~12K at desired evaporating 
temperature. Suction superheat, suction, and condensing 
pressures (temperatures) could be found on the info screen 
of the controller. While optimizing charging, ensure oil sight 

glass doesn’t start foaming.  

 

 

A proper refrigerant charge should secure stable condition 
at minimum and maximum heat load within the limits of the 

condensing unit’s application envelope. 

 

 

Minimum heat load conditions, which occurred during 
winter. Condenser should not be flooded by liquid 
refrigerant, receiver and liquid line should be able to 
contain remaining charge at this condition.      

 

Maximum heat load conditions, which occurred during 
summer. All evaporators are working with maximum 
air/liquid flow via evaporators and refrigerant charge 
should be enough to feed to all evaporators.      

 

Refrigerant charge by judging the liquid sight 
glass does not guarantee as 100% correct 
way.  
 

 

To avoid system overcharging, which can cause higher 
energy consumption and low compressor sump superheat

 

 
Compressor sump superheat = temperature of (compressor 
shell-bottom at 30mm above foot shell 

 condensing 

saturated vapor at that time) 
 

 

Ensure compressor sump superheat more than 10K.   

 
The system approximate maximum charge can be 
calculated as below:  
 

Approximate Maximum Charge = (Receiver Volume 
+ Internal volume of Liquid Line) * 0.9 

 
When the compressor operates under stabilized conditions, 
the oil level must be visible in the sight glass (floating ball). 
Foam filling the oil sight glass indicates presence of large 
concentration of liquid to the compressor.   

No additional oil is required for installation with good oil 
returns, line runs up to 30m. Additional oil might be 
required if lines exceeded 30m, with minimum oil level must 
not lower than ¼ of sight glass. Top-up the oil while 
compressor is idle, via suction schrader connector with a 
suitable pump.   
 
 
 

Pipe Size Selection 

 

Do not assume that the suction/liquid 
connections sizes on the condensing unit are 
the correct sizes to run your interconnecting 
refrigeration pipes.  

 

As a piping design concept, convenience store application 
will operate at part load condition. It is a concern that too 
big suction cross section area will cause refrigerant do not 
obtain sufficient velocity to carry oil returned to compressor. 

Table 15

 provides a guideline for quick selection of suction 

pipe size.    
To find optimum suction pipe size for oil return. 
Example:  
1. Calculate % of refrigerant flow for each indoor 

 

Total cooling load = 6.5+6.5 = 13kW = 100% 

 

Flow for IDU 1 = 6.5/13 = 50% 

 

Flow for IDU 2 = 6.5/13 = 50% 

 

2. Select suction pipe size using 

Table 15

 

based on optimum 

minimum speed not lower than 30rps. Refer 

Figure 18

 for 

the selected suction pipe size.  
 
3. Conclusion: Minimum running speed of compressor for oil 
return with this combination of piping is 21rps.  
 

Figure 18: Suction Pipe Layout for 1 outdoor to 
2 indoors

 

 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for V3

Page 1: ...ure Variable Capacity Scan below QR code to download latest manual from Website https drm daikinmalaysia com download V3 INVERTER SCROLL AIR COOLED SPLIT COMMERCIAL CONDENSING UNIT TECHNICAL MANUAL NO...

Page 2: ...to perform their assigned tasks properly and safely It is essential that prior to performing any task on this equipment this individual shall have read and understood this document and any referenced...

Page 3: ...D Display Button Functions 15 CONTROLLER HOME SCREEN 15 PASSWORD FOR ACCESSIBILITY LEVEL 15 CHANGING SET POINT 16 REFRIGERANT SELECTION 16 SWITCH UNIT ON OFF BY CONTROLLER 16 COMPRESSOR MODEL SELECTIO...

Page 4: ...sensors Low pressure switch adjustable default auto reset High pressure safety switch manual reset cartridge type Mains switch for isolation of incoming power supply Manual motor starter for isolatio...

Page 5: ...I 29 CABLE PRESSURE TRANSDUCER 30 SENSOR TEMPERATURE SUCTION VI 31 SENSOR TEMPERATURE DISCHARGE T 32 SENSOR TEMPERATURE AMBIENT 33 FUSE 34 VALVE SERVICE 35 VALVE DISCHARGE LINE 36 VALVE NON RETURN 37...

Page 6: ...T CU19 JAN24 1 Page 4 Figure 3 Exploded View of LRMIFS0900AXY1...

Page 7: ...and Weight Model SEPR 10K SH SPL 10m dB A Overall Dimensions mm Mounting Dimensions mm Dry Weight Gross Weight R448A R449A Width Depth Height Width Depth kgs kgs LRMIFS0300AXY1 3 03 3 03 31 3 1334 54...

Page 8: ...450 2620 60 38 COP 1 6 1 75 1 92 2 1 2 29 2 48 60 43 CC 2620 3170 3796 4504 5301 6191 60 43 PC 1787 2023 2260 2497 2733 2970 60 43 COP 1 47 1 57 1 68 1 8 1 94 2 08 80 27 CC 4116 4906 5795 6788 7891 91...

Page 9: ...35 COP 1 39 1 74 2 04 2 30 2 53 2 73 60 38 CC 4781 6356 7931 9506 11081 12679 60 38 PC 3630 3935 4240 4545 4850 5155 60 38 COP 1 32 1 62 1 87 2 09 2 28 2 46 60 43 CC 4606 5947 7289 8630 60 43 PC 3824...

Page 10: ...6100 6150 6200 6250 60 38 COP 1 03 1 26 1 48 1 87 2 26 2 64 60 43 CC 5817 6741 7664 9925 12186 14446 60 43 PC 6700 6688 6675 6663 6650 6638 60 43 COP 0 87 1 01 1 15 1 49 1 83 2 18 80 27 CC 9718 12601...

Page 11: ...Table 8 Operating Limit Operating Limits Recommendation Discharge gas temperature 1100C maximum Evaporator outlet superheat Above 6K to avoid liquid flood back Suction gas superheat at compressor inle...

Page 12: ...units regardless of short term or long term operation The units are not designed to withstand loads or stress from other equipment or personnel Such extraneous loads or stress may cause failure leak i...

Page 13: ...rap system is fitted Additional oil may be required if piping length exceeds 20m or multiple oil traps are fitted Check the oil level closely during commissioning and add oil as necessary Add oil in s...

Page 14: ...sting has been completed satisfactorily release the pressure from the system gradually and safely to external atmosphere Evacuation and Charging Moisture prevents proper functioning of the compressor...

Page 15: ...ital input Safe Torque Off STO on the drive When the STO contact is open the drive stops operating bypassing the software control Phase Sequence for Correct Compression BLDC scroll compressor requires...

Page 16: ...r R448A Type of refrigerant available for selection R448A R449A R404A Low Pressure Switch Cut In 3barg Differential 2barg Auto Reset To cut off compressor when suction pressure drops below 1barg Softw...

Page 17: ...to the setting fields in the setting fields confirms the set value and moves to the next parameter PRG Accesses the menu for selecting the group of parameters to be displayed modified access to the pa...

Page 18: ...type of refrigerant Press ENTER for execution and press DOWN button to move to the next screen 2 Cag02 Select the compressor model Refer compressor nameplate on the unit to ensure correct model is se...

Page 19: ...atible will be shown Compressor Operation Envelope management The compressor working zone in the software is defined based on the following measurements o Condensing pressure o Evaporation pressure o...

Page 20: ...ial during start up The BLDC compressor cannot start if the pressure differential is greater than 9 0barg This limit depends on the maximum current delivered by the inverter As soon as the pressure di...

Page 21: ...communication with the evaporators Serial communication allows information to be exchanged in real time between the controller and the MPXPRO devices AC Fan Speed Modulation One of the AC fans is cont...

Page 22: ...by holding down on the button ALARM until active alarm is clear is required on the 5th times of this alarm occur in an hour Low pressure setting had been configured in such a way that it is the first...

Page 23: ...o all evaporators Refrigerant charge by judging the liquid sight glass does not guarantee as 100 correct way To avoid system overcharging which can cause higher energy consumption and low compressor s...

Page 24: ...27 20 20 20 20 20 20 80 64 52 40 30 22 20 20 20 20 20 70 72 59 46 34 25 20 20 20 20 20 60 82 67 53 40 29 20 20 20 20 20 50 97 78 63 47 34 24 20 20 20 20 40 118 95 76 59 43 29 20 20 20 20 30 97 75 56...

Page 25: ...quest in case of regulat Probes fault 50 Cag43 BLDC settings Crankcase heater COMP OFF Cag43 BLDC settings Crankcase current 24 Cag43 BLDC settings STO alarm management MAN RESET Cag44 Crankcase heate...

Page 26: ...A24 Suction pressure probe broken or disconnected Automatic 60 s R1 Related functions disabled ALA25 Suction temperature probe broken or disconnected Automatic 60 s R2 Related functions disabled ALA46...

Page 27: ...drive Check the power supply voltage 5 Drive overtemperature The temperature inside the drive has exceeded the maximum level allowed Check that the quantity and flow of cooling air are regular Check t...

Page 28: ...compressed air inert gas or a low pressure sprayer utilizing clean water A suitable chemical coil cleaner may be used as required Accumulations of dirt on the condenser face can be removed with a soft...

Page 29: ...tor using the cable supplied with the power supply coming from the controller Figure 20 pCO Smart Key Appendix Table 20 Tightening Torque Model Tightening Torque Nm Compressor Mounting Main Cap Servic...

Page 30: ...T CU19 JAN24 1 Page 28 Figure 21 Outline Drawing LRMIFS0300AXY1 LRMIFS0600AXY1 Figure 22 Outline Drawing LRMIFS0900AXY1...

Page 31: ...T CU19 JAN24 1 Page 29 Figure 23 Wiring Diagram LRMIFS0300AXY1...

Page 32: ...T CU19 JAN24 1 Page 30 Figure 24 Wiring Diagram LRMIFS0600AXY1...

Page 33: ...PRESSURE SWITCH 3 15A A1P MAIN CONTROLLER N L N L IN OUT BRN GRN GRY GRY GRN YLW BLU BRN BLK M BLU BRN C2 BRN 380 415V 3N 50Hz L1L2L3PEU V WPE 1 2 3 4 5 6 7 8 910 POWER GRN YLW BRN GRY BLK BRN GRY BL...

Page 34: ...ON MALAYSIA SDN BHD 34543 W Shah Alam Plant 11A Jalan Utas 15 7 Seksyen 15 40200 Shah Alam Selangor Malaysia Banting Plant Lot 10 Jalan Perusahaan 8 Kawasan Perusahaan Pekan Banting 42700 Banting Sela...

Reviews: