Mechanical Safety Pressure 
Switch 

 

Mechanical  high-pressure  switch  will  cut  out  the  STO 
connection  on  the  drive  to  stop  the  compressor  when 
discharge pressure is higher than the cut-out pressure of the 
manual reset cartridge type pressure switch: cut out 28barg/ 
cut in 22barg.  
 

 

Once  tripped  by  high  pressure  switch,  it  will  create 
Alarm: ALW25: A1. Power+ and ALC01: Compressor1 
alarm1. High pressure switch needs to be manual reset 
by access to the part from hinged right door (for JEHSI-
033-B3-M and JEHSI-066-B3-M) and hinged front top 
door (for JEHSI-087-B4-M).  

 

Alarm ALB04 High cond. Press. is only triggered by high 
pressure  transducer  through  setting  in  Mask  De02 
Condenser  high  pressure 

  threshold:  28barg; 

Condenser high pressure - alarm diff: 7barg; Condenser 
low pressure - alarm delay: 5s. To reset ALB04 alarm, 
remove the fault and hold down button ALARM until no 
active alarm appears.   

 
Low  pressure  alarm  could  be  either  triggered  by  pressure 
switch or low-pressure transducer. 

 

When  compressor  turns  off  by  activation  of  force  off, 

“Forced Off” only 

shows in moment on info screen and 

no logging on alarms history.  

 

When  setting  of  Mask  Cae26  Suction  low  pressure 
alarm 

 threshold: 

1.2bar

, Cae27 turn off compressor: 

NO

. Alarm history will record 

ALB16

 low pressure alarm 

if  system  suction  pressure  falls  below  1.2bar  for 
delayed time set, without turning off compressor.  

 

If alarms triggered by low pressure switch. Alarm 

ALB01

 

Com. Dig. Low press. will be logged in history. Default 
setting: semiautomatic reset 5/60min. Manual reset by 
holding 

down on the button “ALARM” until active alarm 

is clear, is required on the 5

th

 times of this alarm occur in 

an  hour.  Low  pressure  setting  had  been  configured  in 
such a way that  it is the first  device to cut in and last 
device to cut out the system.     

 

For  standalone  application,  compressor  is 
force off at threshold value set in Mask Caf95 
(2.5barg)  to  avoid  recycling  pump  down. 
When the setpoint in Mask Cab03 is set lower 

than 2.7barg, threshold value in Mask Caf95 needs to be 
adjusted to avoid unnecessary unit trigger off. 
Do not adjust the suction low pressure alarm 

 threshold 

in Mask Cae26.   

 
 

High Discharge Temperature 
Management 

 

 

The envelope of a BLDC compressor is also limited by 
high discharge temperature. If the discharge 
temperature continues to rise, a safety algorithm will 
be activated to gradually reduce it. The corresponding 
parameters are under submenu: Compressors -
>Advanced -> mask Hb02, Hb03, Fdb04. 

 

Near the limit value, compressor speed will start 
slowing, until stopping on reaching the alarm with the 
high temperature alarm is activated. The alarm is reset 
manually. 

Figure 17: Discharge Temperature Management 

110

0

C

ALW28: Compressor Stops

Alarm

105

0

C

Speed Deduction

Limit

100

0

C

Vapor Injection

Action Distance

90

0

C

Acceleration rate reduction

Normal Operation

Speed reduction limits - alarm limit
Speed reduction - 3% of max. speed
E.g. if max 100rps, 

3rps every 90s; 3rps every 1

0

C

Vapor injection - EEV control based on (Fdb04): 
SH if T_disch.< min temp. 
T_disch if T_disch>min temp limit, opening to 
max % at max temp. limit (Fdb04)

 

Note: EEV Vapor Injection not applicable to *-M-3* 
models 

Speed control based on discharge temperature (Hb03): 

 

Speed reduction: 3% of max. speed, e.g., if max. 
speed is 100rps. 3rps every 90s; 3rps every 1

0

 

Compressor stopping at high temperature alarm.  

 
EEV vapor injection control based on (Fdb04): 

 

SH if T_disch. < min. temp 

 

T_disch if T_disch.> min. temp limit, opening to 
maximum % at max. temperature limit.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for V3

Page 1: ...ure Variable Capacity Scan below QR code to download latest manual from Website https drm daikinmalaysia com download V3 INVERTER SCROLL AIR COOLED SPLIT COMMERCIAL CONDENSING UNIT TECHNICAL MANUAL NO...

Page 2: ...to perform their assigned tasks properly and safely It is essential that prior to performing any task on this equipment this individual shall have read and understood this document and any referenced...

Page 3: ...D Display Button Functions 15 CONTROLLER HOME SCREEN 15 PASSWORD FOR ACCESSIBILITY LEVEL 15 CHANGING SET POINT 16 REFRIGERANT SELECTION 16 SWITCH UNIT ON OFF BY CONTROLLER 16 COMPRESSOR MODEL SELECTIO...

Page 4: ...sensors Low pressure switch adjustable default auto reset High pressure safety switch manual reset cartridge type Mains switch for isolation of incoming power supply Manual motor starter for isolatio...

Page 5: ...I 29 CABLE PRESSURE TRANSDUCER 30 SENSOR TEMPERATURE SUCTION VI 31 SENSOR TEMPERATURE DISCHARGE T 32 SENSOR TEMPERATURE AMBIENT 33 FUSE 34 VALVE SERVICE 35 VALVE DISCHARGE LINE 36 VALVE NON RETURN 37...

Page 6: ...T CU19 JAN24 1 Page 4 Figure 3 Exploded View of LRMIFS0900AXY1...

Page 7: ...and Weight Model SEPR 10K SH SPL 10m dB A Overall Dimensions mm Mounting Dimensions mm Dry Weight Gross Weight R448A R449A Width Depth Height Width Depth kgs kgs LRMIFS0300AXY1 3 03 3 03 31 3 1334 54...

Page 8: ...450 2620 60 38 COP 1 6 1 75 1 92 2 1 2 29 2 48 60 43 CC 2620 3170 3796 4504 5301 6191 60 43 PC 1787 2023 2260 2497 2733 2970 60 43 COP 1 47 1 57 1 68 1 8 1 94 2 08 80 27 CC 4116 4906 5795 6788 7891 91...

Page 9: ...35 COP 1 39 1 74 2 04 2 30 2 53 2 73 60 38 CC 4781 6356 7931 9506 11081 12679 60 38 PC 3630 3935 4240 4545 4850 5155 60 38 COP 1 32 1 62 1 87 2 09 2 28 2 46 60 43 CC 4606 5947 7289 8630 60 43 PC 3824...

Page 10: ...6100 6150 6200 6250 60 38 COP 1 03 1 26 1 48 1 87 2 26 2 64 60 43 CC 5817 6741 7664 9925 12186 14446 60 43 PC 6700 6688 6675 6663 6650 6638 60 43 COP 0 87 1 01 1 15 1 49 1 83 2 18 80 27 CC 9718 12601...

Page 11: ...Table 8 Operating Limit Operating Limits Recommendation Discharge gas temperature 1100C maximum Evaporator outlet superheat Above 6K to avoid liquid flood back Suction gas superheat at compressor inle...

Page 12: ...units regardless of short term or long term operation The units are not designed to withstand loads or stress from other equipment or personnel Such extraneous loads or stress may cause failure leak i...

Page 13: ...rap system is fitted Additional oil may be required if piping length exceeds 20m or multiple oil traps are fitted Check the oil level closely during commissioning and add oil as necessary Add oil in s...

Page 14: ...sting has been completed satisfactorily release the pressure from the system gradually and safely to external atmosphere Evacuation and Charging Moisture prevents proper functioning of the compressor...

Page 15: ...ital input Safe Torque Off STO on the drive When the STO contact is open the drive stops operating bypassing the software control Phase Sequence for Correct Compression BLDC scroll compressor requires...

Page 16: ...r R448A Type of refrigerant available for selection R448A R449A R404A Low Pressure Switch Cut In 3barg Differential 2barg Auto Reset To cut off compressor when suction pressure drops below 1barg Softw...

Page 17: ...to the setting fields in the setting fields confirms the set value and moves to the next parameter PRG Accesses the menu for selecting the group of parameters to be displayed modified access to the pa...

Page 18: ...type of refrigerant Press ENTER for execution and press DOWN button to move to the next screen 2 Cag02 Select the compressor model Refer compressor nameplate on the unit to ensure correct model is se...

Page 19: ...atible will be shown Compressor Operation Envelope management The compressor working zone in the software is defined based on the following measurements o Condensing pressure o Evaporation pressure o...

Page 20: ...ial during start up The BLDC compressor cannot start if the pressure differential is greater than 9 0barg This limit depends on the maximum current delivered by the inverter As soon as the pressure di...

Page 21: ...communication with the evaporators Serial communication allows information to be exchanged in real time between the controller and the MPXPRO devices AC Fan Speed Modulation One of the AC fans is cont...

Page 22: ...by holding down on the button ALARM until active alarm is clear is required on the 5th times of this alarm occur in an hour Low pressure setting had been configured in such a way that it is the first...

Page 23: ...o all evaporators Refrigerant charge by judging the liquid sight glass does not guarantee as 100 correct way To avoid system overcharging which can cause higher energy consumption and low compressor s...

Page 24: ...27 20 20 20 20 20 20 80 64 52 40 30 22 20 20 20 20 20 70 72 59 46 34 25 20 20 20 20 20 60 82 67 53 40 29 20 20 20 20 20 50 97 78 63 47 34 24 20 20 20 20 40 118 95 76 59 43 29 20 20 20 20 30 97 75 56...

Page 25: ...quest in case of regulat Probes fault 50 Cag43 BLDC settings Crankcase heater COMP OFF Cag43 BLDC settings Crankcase current 24 Cag43 BLDC settings STO alarm management MAN RESET Cag44 Crankcase heate...

Page 26: ...A24 Suction pressure probe broken or disconnected Automatic 60 s R1 Related functions disabled ALA25 Suction temperature probe broken or disconnected Automatic 60 s R2 Related functions disabled ALA46...

Page 27: ...drive Check the power supply voltage 5 Drive overtemperature The temperature inside the drive has exceeded the maximum level allowed Check that the quantity and flow of cooling air are regular Check t...

Page 28: ...compressed air inert gas or a low pressure sprayer utilizing clean water A suitable chemical coil cleaner may be used as required Accumulations of dirt on the condenser face can be removed with a soft...

Page 29: ...tor using the cable supplied with the power supply coming from the controller Figure 20 pCO Smart Key Appendix Table 20 Tightening Torque Model Tightening Torque Nm Compressor Mounting Main Cap Servic...

Page 30: ...T CU19 JAN24 1 Page 28 Figure 21 Outline Drawing LRMIFS0300AXY1 LRMIFS0600AXY1 Figure 22 Outline Drawing LRMIFS0900AXY1...

Page 31: ...T CU19 JAN24 1 Page 29 Figure 23 Wiring Diagram LRMIFS0300AXY1...

Page 32: ...T CU19 JAN24 1 Page 30 Figure 24 Wiring Diagram LRMIFS0600AXY1...

Page 33: ...PRESSURE SWITCH 3 15A A1P MAIN CONTROLLER N L N L IN OUT BRN GRN GRY GRY GRN YLW BLU BRN BLK M BLU BRN C2 BRN 380 415V 3N 50Hz L1L2L3PEU V WPE 1 2 3 4 5 6 7 8 910 POWER GRN YLW BRN GRY BLK BRN GRY BL...

Page 34: ...ON MALAYSIA SDN BHD 34543 W Shah Alam Plant 11A Jalan Utas 15 7 Seksyen 15 40200 Shah Alam Selangor Malaysia Banting Plant Lot 10 Jalan Perusahaan 8 Kawasan Perusahaan Pekan Banting 42700 Banting Sela...

Reviews: