5.1

 

Overview: Commissioning

 

Typical workflow

 

Commissioning typically consists of the following stages:

 

1.

 

Checking the 

checklist before commissioning

”.

 

2.

 

Performing a test run for the system.

 

3.

 

Checking the 

Checklist before commissioning

”.

 

5.2

 

Checklist before commissioning

 

After the installation of the unit, first check the following items. Once all below 
checks are fulfilled, the unit MUST be closed, ONLY then can the unit be 
powered up.

 

 

To perform a wiring check.

 

 

Pre

-

plumbed pipework is free from any leaks.

 

Expansion vessel is set to 3 bar.

 

 

There are NO water leaks on the connections including any which 
are factory made.

 

 

Domestic hot water tank is properly mounted.

 

 

System is properly earthed and the earth terminals are tightened.

 

 

The fuses or locally installed protection devices are installed 
according to this document, and have not been bypassed.

 

 

There are NO loose connections or damaged electrical components 
in the switch box.

 

 

The immersion heater circuit breaker F2B on the switch box is 
turned ON.

 

 

The shut

-

off valves are properly installed and fully open.

 

 

The pressure relief valve purges water when opened.

 

 

The minimum water volume is guaranteed in all conditions.

 

 

Be sure field wiring has been carried out according to the 
instructions described.

 

5.3 

 

Checklist during commissioning

 

6

 

Hand

-

over to the user

 

Once the test run is finished and the unit operates properly, please make sure 
the following is clear for the user:

 

• 

Make sure that the user has printed documentation and ask him/her to keep 
it for future reference. 

 

• 

Explain the user how to properly operate the system and what to do in case 
of problems.

 

• 

Show the user what to do in relation to maintaining the unit.

 

WARNING

 

ALWAYS use multicore cable for power supply cables.

 

CAUTION

 

Indicates a situation that could result minor or moderate injury.

 

 

Commissioning

 

Summary of Contents for UK.PPC150SL/R32

Page 1: ...Altherma R32 Monobloc Systems Installation Manual UK PPC150SL R32 UK PPC150 R32 UK PPC180SL R32 UK PPC180 R32 UK PPC210 R32 UK PPC250 R32 UK PPC300 R32 English Installation Manual Domestic hot water...

Page 2: ...that nobody especially children can play with them Possible risk suffocation DANGER RISK OF BURNING Do NOT touch the refrigerant piping water piping or internal parts during and immediate after operat...

Page 3: ...rical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touching electrical parts Disconnect the power supply for more than 1...

Page 4: ...5 consecutive days after installation Domestic hot water tank Standstills In cases where during longer periods of time there is no consumption of hot water the equipment MUST be flushed with fresh wa...

Page 5: ...mponents The discharge pipe away from the tundish must terminate in a safe visible position without forming any risk to persons in the vicinity WARNING Do NOT install any valves between the domestic h...

Page 6: ...must be installed by a qualified electrician The fuse rating should be sized correctly to suite the heater s duty and isolators must be double pole to BS 3456 Correct cable sizing must be carried out...

Page 7: ...4 5 5 Parts List 4 5 6 Plan View and Dimensions Allow 300mm space in front for servicing immersion heater...

Page 8: ...the factory the pre plumbed cylinder will be supplied with the vessel as a hydraulic separator In order to change the vessel to function only as a volumiser use the following configuration NOTICE On B...

Page 9: ...d protection devices are installed according to this document and have not been bypassed There are NO loose connections or damaged electrical components in the switch box The immersion heater circuit...

Page 10: ...tic cover of the pressure reducing valve 2 Extract the cartridge with the aid of long nosed pliers to grip the heat of the set screw 3 Remove the strainer element 4 Clean the strainer element and cart...

Page 11: ...device such as a timer or connected to a circuit that is regularly turned ON and OFF by the utility 10 3 Solving problems based on symptoms 10 3 1 Symptom No water flow from hot taps Possible causes C...

Page 12: ...the Dixell control panel We recommend the setpoint to be 37o C however it could be changed based on your requirements e g if using low temperature heat emitters If there is no possibility for water ci...

Page 13: ...UK PPC150 300 SL R32 November 2022 Version 2 1 Domestic hot water tank for Daikin Altherma Monobloc R32 12 Technical data 12 1 Components Domestic hot water tank 12 2 Exploded Diagram...

Page 14: ...eight kg 46 56 59 71 86 Material inside cylinder Stainless steel 2304 Water inlet H E mm 28 Piping connections diameter Water outlet H E mm 28 Cold water in mm 22 Hot water out mm 22 Domestic hot wate...

Page 15: ...and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the require service to the product Accessories Labels manuals information sheets and eq...

Page 16: ...Appendix Wiring Connections Factory Fitted Wiring Wiring when using Madoka BRC1HHD Controller...

Page 17: ...Third Party Thermostat 1 Zone Wiring when using Third Party Thermostat 2 Zones Third party controller must be volt free and TPI disabled Cable must be sized for 230V Third party controller must be vol...

Page 18: ...and Service Record Log Book CUSTOMER DETAILS NAME ADDRESS TEL No IMPORTANT 1 Please keep the Log Book in a safe place for future reference 2 This Log Book is to be completed in full by the competent p...

Page 19: ...VALVE AND EXPANSION VALVE FITTED AND DISCHARGE TESTED YES NO IS PRIMARY ENERGY SOURCE CUT OUT FITTED NORMALLY 2 PORT VALVE YES NO WHAT IS THE PRESSURE REDUCING VALVE SETTING IF FITTED YES NO WHERE IS...

Page 20: ...ENTS SIGNATURE SERVICE 2 DATE ENGINEER NAME COMPANY NAME TEL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No...

Page 21: ...UK PPC150 300 SL R32 November 2022 Version 2 1 Domestic hot water tank for Daikin Altherma Monobloc R32...

Page 22: ...Daikin UK 1 The Heights Brooklands Weybridge Surrey KT13 0NY...

Reviews: