Daikin Pre
-
Plumbed Cylinder with Hydraulic Separation
(Factory Default)
Daikin Pre
-
Plumbed Cylinder with Inline Volumizer
4.5.6
Hydraulic Separator or Volumiser Vessel
This pre plumbed cylinder is supplied with the vessel which can be used as hydraulic separator, between the primary and secondary heating
circuits, or just as a volumiser.
From the factory, the pre plumbed cylinder will be supplied with the vessel as a hydraulic separator. In order to change the vessel to function
only as a volumiser, use the following configuration.
NOTICE
On
-
Board Pump:
The pre plumbed cylinder is supplied with an on
-
board water circulation pump. If the vessel is used as a hydraulic separation and if
there is no possibility for water circulation on the secondary side, an automatic bypass valve should be fitted. Water circulation could be via a towel
rail, a by
-
pass valve or a radiator without a TRV.