IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
70 www.DaikinApplied.com
Unit Controller Operation
Table 32: AGZ-E Models with 2 VFDs per Circuit
Output Descr .
Physical
Output
Number of Fans
6
8
10
12
14
Circuit 1
Speed 1
UC X5
Fan 11
Fan 11/13
Fan 11/13
Fan 11/13
Fan 11/13
Speed 2
UC X2
Fan 12/13
Fan 12/14
Fan 12/14 Fan 12/14/15/16 Fan 12/14/15/16
Fan Output 1
UC DO3
Fan Output 2
UC DO4
Fan Output 3
UC DO5
Fan Output 4
UC DO6
Fan Output 5
EEXV1 DO1
Fan 15
Fan 17
Circuit 2
Speed 1
UC X6
Fan 21
Fan 21/23
Fan 21/23
Fan 21/23
Fan 21/23
Speed 2
UC X3
Fan 22/23
Fan 22/24
Fan 22/24 Fan 22/24/25/26 Fan 22/24/25/26
Fan Output 1
UC DO7
Fan Output 2
UC DO8
Fan Output 3
UC DO9
Fan Output 4
UC DO10
Fan Output 5
EEXV2 DO1
Fan 25
Fan 27
RapidRestore
®
This module will be used only when the unit is equipped with
the RapidRestore
®
option.
Table 33: Digital Inputs
Description
Signal Off
Signal On
DI1
RapidRestore
Enable
Disable
RapidRestore
Allow RapidRestore
Enabling
DI2
Backup Chiller
Designation
Not Backup
Chiller
Backup Chiller
Sensor Information
Pressure
Pressure inputs will be read using 0 to 5 volt ratiometric
sensors. Nominal voltage range will be 0.5 to 4.5 volts.