IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
140 www.DaikinApplied.com
Warranty Registration Form (Scroll)
REFRIGERANT PIPING FOR REMOTE EVAPORATOR APPLICATIONS
A. Has all field piping been leak tested at 150 psig (690 kPA)?
B. Has system been properly evacuated and charged?
C. Refrigerant R-
Circuit 1
lbs (kg) Circuit 2
lbs. (kg)
D.
Reviewed and confirmed piping is per the approved SF-99006 form submitted to the factory?
E. Is a liquid line filter-drier installed in each circuit?
F. Is a liquid line solenoid installed correctly in each circuit?
G. Is Expansion Valve and associated sensors installed, insulated and wired correctly?
(Including Entering water and Leaving water sensors.)
DESIGN CONTROLS
Ft. (kPa)
Leaving
°F (°C)
A.
CHILLER
Water Pressure Drop:
Water Temperatures: Entering
B.
CONDENSER
Design Ambient Temperatures
:
Entering
Minimum Ambient Temperatures
: Entering
°F (°C)
°F (°C)
gpm (lps)
°F (°C)
°F (°C)
START-UP
A.
Does unit start and perform per sequence of operation as stated in the
IOM
Manual?
B.
Do condenser fans rotate in the proper directions?
MICROTECH STATUS CHECK-Each Reading Must be Verified with Field Provided Instruments of Known Accuracy?
MicroTech
Verification
C. Water Temperatures: Leaving Evaporator
………………………………
°F (°C)
°F (°C)
Entering Evaporator
………………………………
°F (°C)
°F (°C)
D. Circuit #1 Refrigerant Pressures:
Evaporator ………………………………………….
psig (kPa)
psig (kPa)
Liquid Line pressure
……………………………………………………………..
psig (kPa)
Condenser Pressure
………………………………
psig (kPa)
psig (kPa)
E. Circuit #2 Refrigerant Pressures:
Evaporator ………………………………………….
psig (kPa)
psig (kPa)
Liquid Line Pressure
…………………………………………………………….
psig (kPa)
Condenser Pressure
……………………………..
psig (kPa)
psig (kPa)
F. Circuit #1 Refrigerant Temperatures:
Saturated Evaporator Temperature ……………………
°F (°C)
°F (°C)
Suction Line Temperature ……………………………….
°F (°C)
°F (°C)
Suction Superheat ……………………………………….
°F (°C)
°F (°C)
Saturated Condenser Temperature ……………………
°F (°C)
Liquid Line Temperature …………………………………………………………..
°F (°C)
Subcooling …………………………………………………………………………..
°F (°C)
Discharge Temperature
…………………………………………………………..
°F (°C)
SF-
20001
AGZ/AMZ Start-Up
8
/2020
3
of
8
www.DaikinApplied.com
N/A Yes No
Yes No
°F (°C)
Leaving
Leaving