www.DaikinApplied.com 

IM 745-3

I

nstallatIon

Recommendations

NOTICE

Before installation and running the unit, please check the 

following:

1.   There must be enough space for the unit installation 

and maintenance. Please refer to the unit outline and 

dimensions in 

Figure 1

 for the minimum distance  

between the unit and obstacles.

2.   Mount with the lowest moving parts at least 8 feet above 

the floor or grade level.

3.   Ensure enough space for piping connection and  

electrical wiring.

4.   Leave a means for disconnection from the electrical  

supply according to NEC or local codes.

5.   Check whether the hanging rods can support the weight 

of the unit.

6.   The unit must be installed horizontally for proper  

operation and condensate draining.

7.   The external static pressure must be within the  

allowable static pressure range.

8.   The installing contractor must supply service valves 

and insulation for water piping in accordance with local 

codes and regulations.

9.   To prevent strain on the wire connections, use either 

conduit or approved strain relief device.

10.   Confirm that the power has been switched OFF before 

installing or servicing the unit.

The unit is designed to be concealed in the ceiling. Installation 

and maintenance should be performed by qualified personnel 

who are familiar with local codes and regulations, and experi-

enced with this type of equipment.
There are holes on the top of the unit for hanging the unit above 

the ceiling. Please refer to 

Figure 1

 and 

Figure 2

.

Note: 

Vibration isolators provided by others.

NOTICE

Make sure the top of the unit is level after installation. 

The drain pan is designed with a little gradient to facilitate  

drainage. 

Do Not Level Drain Pan!

Figure 1: Unit Clearances

Obstacle

Ceiling

B

A

C

A ≥ 8 in.
B ≥ 16 in.
C ≥ 16 in.

Obstacle

Air Duct Connection

Air ducts should be made of galvanized steel and  

connected to the flange of the unit with a canvas connector. 

Refer to the unit dimensions. Insert the duct into the flange and 

fix with screws. 

Duct connections must be installed in accordance with national 

and local codes.

Figure 2: Air Duct Connection

Discharge Air

Return Air

Ceiling

Ceiling Access Panel

with Air Return

Terminal

Block

A

Fan Coil 

Unit

Flat

Washer

Hanging

Rod

Expansion 

Screw

Nut

Detail A

Chilled Water Pipe Connection

Connect chilled water pipes to the unit. The water inlet is on 

the bottom and water outlet is on top.

Figure 3: Pipe Connections

Water Inlet, Control 

Valve Actuator

Water Outlet, Return Ball Valve

Air Flow

Supply Gate Valve 

Summary of Contents for THC02

Page 1: ...Installation and Maintenance Manual IM 745 3 Group Fan Coil Part Number 668708901 Date October 2018 Ceiling Concealed Fan Coil Unit Models THC02 THC03 THC04 THC06 THC08 THC10 THC12...

Page 2: ...t should be unpacked in the presence of the agent so that the extent of the damage or loss can be determined The carri er s agent will make an inspection report and a copy will be given to the consign...

Page 3: ...is designed to be concealed in the ceiling Installation and maintenance should be performed by qualified personnel who are familiar with local codes and regulations and experi enced with this type of...

Page 4: ...ed and removable for cleaning It may be necessary to manually fill the trap at system start up or to run the unit for sufficient time to build a condensate seal The condensate trap and condensate pipi...

Page 5: ...www DaikinApplied com 5 IM 745 3 Wiring Diagrams Model C3H 02 12EA 208 230V 60Hz Model C3H 02 12JA 277V 60Hz...

Page 6: ...OR FIELD WIRING MAIN SWITCH G Y BLACK WHITE BLUE N L FAN SPEED SWITCH H RED SHF YELLOW HF M L BROWN MF ORANGE LF G Y BLACK M BLACK Figure 8 220V 1Ph 50Hz L G Y GREEN YELLOW FIELD WIRING LF FAN SPEED L...

Page 7: ...PEED MEDIUM G Y RED G Y BLUE RED L SOURCE POWER N FAN SPEED SWITCH SHF HF ORANGE BROWN M2 BLACK G Y BLACK ORANGE BROWN L M MF LF M1 BLACK MAIN SWITCH G G Y WHITE BLACK G Y GREEN YELLOW BLACK G Y GREEN...

Page 8: ...ot Water Connection 3 4 FPT Main Drain Connection 3 4 O D 8 82 Unit w o Plenum 18 35 Unit w o Plenum Optional LV 3SP Jbox 7 73 H x 6 54 W x 3 38 D always located on the end opposite the coil connectio...

Page 9: ...ssed air or water They can be vacuumed or brushed with a soft brush CAUTION Water coils exposed to freezing temperatures should be drained or anti freeze should be added to the water circuit to avoid...

Page 10: ...new air filter The cooling or heating function fails The electric control valve of unit is not started Start the electric control valve of unit The circulating pump is not started As a result the cold...

Page 11: ...Driver Indicator Light Failure Description Suggested Elimination Method 1 Motor overcurrent protection Check whether there is open circuit or short circuit on the motor lead 3 Over voltage protection...

Page 12: ...ndard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details Refer to Form 933 430285Y To find your local Daikin Applied...