PIM00424
12-1
Chapter 12
Parameter Adjustment
12.1
Parameter List
The default value of the parameter P13 ~ 28 is different, depending on the unit type.
Please refer to Page 12-6 “Table 1: Different default parameter values for different products” for the default value of
the parameter P13 ~ 28.
Item Sign
Name
Operating
range
Default
setting
Description Reference
P00 DI_A
Start-stop signal
switch
0: Operating at
DIN1-ON
1: Operating at
DIN1-OFF
1
DIN1: Setting the valid logic of start-stop
signal.
12-7
0
〜
35.0[MPa]
0
0
〜
507[×10PSI]
0
P01 SW_L
Pressure
switch
0
〜
350 [%]
0
Setting the working pressure of the
pressure switch.
Pressure switch function will be disabled,
if the setting value is "0".
12-13
P02 T_SW
Pressure switch
output delay time
0.00
〜
9.99[sec]
0
Setting the delay time, from the time the
pressure decreases below “P01”to the
time the pressure drop is confirmed.
12-13
P03 PSWH
Pressure switch
display holding
setting
0
〜
2
0
When the warning “L63: Pressure switch
operation” occures, you can keep the
"L63" displaying on the operation panel.
And, you can register the “L63: Pressure
switch operation” in the alarm history.
Value
L63
display
holding
Register in
the alarm
history
0
Do not
hold
Do not
register
1 hold
Do not
register
2 hold Register
12-13
P04 DS_P
Pressure unit
select setting
*
0: MPa
1: PSI
0
You can switch the pressure unit
displaying in the panel.
−
P05 K_RT
Load command
rate at the time of
regeneration
30
〜
100[%]
50
Please adjust it, if " E14: Regenerative
braking overload " occurs.
If you decrease the value, the
regeneration load rate will decrease, but
the deceleration time will become longer.
−
P06 D_RT
Regenerative load
ratio command at
the time of
deceleration
0
〜
100[%]
30
When you want to change the PQ
selection, if the deceleration is more than
50% of the maximum flow, please set the
deceleration torque.
If this value decreases, the regenerative
load ratio will decrease, but the
deceleration time will be longer.
If the default setting is 0, this function
will be disabled.
At this time, it’s not
necessary to change the setting.
−
Summary of Contents for Super Unit SUT00S8007-30
Page 2: ......
Page 12: ......
Page 19: ...PIM00424 3 5 3 4 Dimensions Motor Pump Type SUT00 SUT00S8007 30 ...
Page 20: ...PIM00424 3 6 SUT00D8021 30 ...
Page 21: ...PIM00424 3 7 Unit Type SUT10 SUT16 SUT10S8007 30 ...
Page 22: ...PIM00424 3 8 SUT10D8021 30 ...
Page 23: ...PIM00424 3 9 SUT16D8021 30 ...
Page 28: ......
Page 32: ......
Page 34: ......
Page 38: ......
Page 42: ......
Page 50: ......
Page 60: ......
Page 92: ......