Troubleshooting
SiUS12-928_A
109
Service Diagnosis
5.6
Thermistor or Related Abnormality (Indoor Unit)
Remote
Controller
Display
C4
,
C9
Method of
Malfunction
Detection
The temperatures detected by the thermistors are used to determine thermistor errors.
Malfunction
Decision
Conditions
The thermistor input is more than 4.96 V or less than 0.04 V during compressor operation.
Supposed
Causes
Disconnection of connector
Defective thermistor
Defective indoor unit PCB
Troubleshooting
Check No.06
Refer to P.152
C4
: Indoor heat exchanger thermistor
C9
: Room temperature thermistor
YES
(R7134)
NO
Check No. 06
Check the thermistor resistance
value.
YES
NO
Caution
Correct the connection.
Replace the thermistor.
(Replace the indoor unit PCB.)
Replace the indoor unit PCB.
Is it normal?
Is it normal?
Check the connection of
connectors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for SUPER MULTI NX G Series
Page 1: ...SiUS12 928_A Applied Models Inverter Multi Heat Pump G Series J Series...
Page 7: ...SiUS12 928_A Table of Contents vi...
Page 10: ...SiUS12 928_A 1 List of Functions Part 1 List of Functions 1 Functions 3...
Page 11: ...SiUS12 928_A List of Functions 2...
Page 17: ...SiUS12 928_A Specifications 8...
Page 23: ...SiUS12 928_A Specifications Specifications 14...
Page 25: ...SiUS12 928_A Printed Circuit Board Connector Wiring Diagram 16...
Page 37: ...SiUS12 928_A Function and Control 28...
Page 69: ...SiUS12 928_A Control Specification Function and Control 60...
Page 71: ...SiUS12 928_A Operation Manual 62...
Page 73: ...SiUS12 928_A Duct Free System Operation Manual 64 2 Duct Free System 2 1 Remote Controller...
Page 84: ...Duct Free System SiUS12 928_A 75 Operation Manual...
Page 85: ...SiUS12 928_A Duct Free System Operation Manual 76 2 8 TIMER Operation...
Page 86: ...Duct Free System SiUS12 928_A 77 Operation Manual...
Page 87: ...SiUS12 928_A Duct Free System Operation Manual 78 2 9 Note for Multi System...
Page 88: ...Duct Free System SiUS12 928_A 79 Operation Manual...
Page 97: ...SiUS12 928_A Slim Duct Built In System Operation Manual 88...
Page 99: ...SiUS12 928_A Service Diagnosis 90...
Page 169: ...SiUS12 928_A Removal Procedure 160...
Page 225: ...SiUS12 928_A Trial Operation and Field Settings 216...
Page 235: ...SiUS12 928_A Appendix 226...