24
English
NOTE
1.
Abnormal stop is applied depending on the model or condition.
J9
Gas piping thermistor malfunction (cooling) (outdoor)
(NOTE 1)
JA
Discharge pipe pressure sensor faulty
JC
Suction pipe pressure sensor faulty
L1
Inverter error (outdoor unit)
L3
Reactor thermistor faulty (outdoor unit)
(NOTE 1)
L4
Overheated heat-radiating fin (outdoor unit)
(NOTE 1)
Inverter cooling defect.
L5
Instantaneous overcurrent (outdoor unit)
(NOTE 1)
Possible earth fault or short circuit in the compressor motor.
L8
Electric thermal (outdoor unit)
Possible electrical overload in the compressor or cut line in the compressor motor.
L9
Stall prevention (outdoor unit)
Compressor possibly locked.
LC
Transmission malfunction between the outdoor control units’ inverters (outdoor unit)
P1
Open-phase (outdoor unit)
(NOTE 1)
P3
P-board temperature sensor malfunction (outdoor unit)
P4
Heat-radiating fin temperature sensor malfunction (outdoor unit)
(NOTE 1)
P6
DC output current sensor system malfunction (outdoor unit)
PJ
Type set improper (outdoor unit)
Capacity data is wrongly proset. Or there is nothing programmed in the data hold IC.
U0
Suction pipe temperature abnormal
(NOTE 1)
U1
Reverse phase
Reverse two phase of the L1,L2and L3 leads.
U2
Power source voltage malfunction (outdoor unit)
(NOTE 1)
Includes the defect in 52C.
U4
UF
Transmission error (indoor unit – outdoor unit)
Wrong wiring between indoor and outdoor units or malfunction of the PC board
mounted on the indoor and the outdoor units.
U5
Transmission error (indoor unit – remote controller)
Transmission is improper between the indoor unit and the remote controller.
U7
Transmission error of the inverter module
U8
Malfunction in transmission between main and sub remote controls.
(Malfunction in sub remote control.)
UA
Miss setting for multi system
Setting is wrong for selector switch of multi-system. (see switch SS2 on the main
unit’s PC board)
UC
Central control address overlapping
UE
Transmission error (indoor unit - central controller)
UH
Field setting error
(NOTE 1)
UJ
Accessory equipment transmission error
(NOTE 1)
01_EN_3PN06588-4M.fm Page 24 Monday, December 19, 2011 7:04 PM