REFRIGERANT PIPING WORK 

3) After the work is finished, make sure to check that there is no 

gas leak.

4) After checking for gas leaks, be sure to insulate the pipe connections.

• Insulate using the insulation for fitting included with the liquid and gas pipes. Besides, make sure the insulation for fitting 

on the liquid and gas piping has its seams facing up.
(Tighten both edges with clamp.)

• For the gas piping, wrap the medium sealing pad over the insulation for fitting (flare nut part).

Caution

Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

Cautions on Pipe Handling

• Protect the open end of the pipe against dust and moisture.

(Tighten both edges with clamp.)

• All pipe bends should be as gentle as possible. Use a pipe bender for 

bending.
(Bending radius should be 30 to 40mm or larger.)

Selection of Copper and Heat Insulation materials

When using commercial copper pipes and fittings, observe the following:
• Insulation material: Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

• Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.

Also, when subject to high humidity, heat insulation of the refrigerant 
piping (the unit piping and branch piping) must be further reinforced.
Reinforce the insulation when installing the unit near bathrooms, 
kitchens, and other similar locations.
Refer to the following:

• 30°C, more than 75% RH: 20mm Min. in thickness

If the insulation is not sufficient, condensation may form on the surface 
of the insulation.

• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Coat here with

refrigeration machine oil

Torque wrench

Piping union

Flare nut

Spanner

Gas pipe

Liquid pipe

Piping insulation 
material (main unit)

Attach to base

Flare nut connection

Turn seams up

Insulation for fitting 

(accessory)

Clamp 

Piping insulation material
(Field supplied)

Gas Piping Insulation Procedure

(accessory)

Main unit

Clamp (accessory)

Flare nut connection

Turn seams up

Piping insulation material
(Field supplied)

Piping insulation 
material (main unit)

Attach to base

Main unit

Insulation for fitting 
(accessory)

Liquid Piping Insulation Procedure

Small sealing pad 

Measure the length of the gas 
pipe as you will have to cover 
it with the sealing tape.

(accessory)

Wrap the sealing 
tape around the 
gas pipe.

Main unit

Wall

If no flare cap is

available, cover

the flare mouth

with tape to keep

dirt or water out.

Be sure to

place a cap.

Rain

Gas side

Gas pipe thermal insulation

Liquid side

Liquid pipe

thermal insulation

25/35 class

50/60 class

O.D. 9.5mm

O.D. 12.7mm

25/35 class

50/60 class

I.D. 12-15mm

I.D. 14-16mm

Thickness 0.8mm

O.D. 6.4mm

I.D. 8-10mm

Thickness 10mm Min.

Gas pipe

Liquid pipe

Gas pipe

insulation

Liquid pipe

insulation

Finishing tape

Drain hose

Inter-unit wiring

01_EN_3P132003-3K.fm  Page 7  Wednesday, September 28, 2005  3:32 PM

Summary of Contents for Super Multi NX FDKS25EAVMB

Page 1: ...s Espa ol Italiano Portugues T rk e Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Ma...

Page 2: ...5 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 49...

Page 3: ...r installation may cause terminal overheating electrical shock or fire When installing or relocating the system be sure to keep the refrigerant circuit free from substances other than the specified re...

Page 4: ...conditions under which the electric wave is generated even if a one meter allowance is maintained Use suspension bolts to install the unit Check whether or not the ceiling is strong enough to support...

Page 5: ...ontrol box and drain pump are easy Install the inspection opening also in the lower part of the unit Make sure the range of the unit s external static pressure is not exceeded See the technical docume...

Page 6: ...re not covered by anti sweat material Make sure there are no gaps between the different pieces of sealing pad 4 Attach the hanger right insulation to the right hanger Stored in outlet vent See the bel...

Page 7: ...the unit to the surface of the water at both ends of the plastic tube and adjust the unit horizontally One thing to watch out for in particular is if it is installed so that the slope is not in the d...

Page 8: ...ent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare Use refrigeration oil for R410A 2 Align the centres of both flares and tighten the flare nuts 3 or 4 turns...

Page 9: ...refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation when installing the unit near bathrooms kitchens and other similar locations Refer to the follo...

Page 10: ...ere causing water to leak Drain piping passing indoors Drain sockets Referring the figure below insulate the metal clamp and drain hose using the included large sealing pad PRECAUTIONS Drain piping co...

Page 11: ...ncy is at least 50 in a gravimetric technique Outlet side Connect the duct according to the inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape...

Page 12: ...rough the wiring through hole and connect to the power wiring terminal block 4P Be sure to put the part of the sheathed vinyl into the control box Warning Do not use tapped wires stand wires extension...

Page 13: ...If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air...

Page 14: ...0511 HT 3P132003 3K M05B026A...

Reviews: