PREPARATIONS BEFORE INSTALLATION
When two indoor units are installed in one room, one of the two wireless remote controllers can be easily
set for another addresses.
INDOOR UNIT INSTALLATION
〈〈
〈〈
〈〈
〈〈
As for the parts to be used for installation work, be sure to use the provided accessories and specified parts
designated by our company.
〉〉
〉〉
〉〉
〉〉
Install the indoor unit temporarily.
• Attach the hanger bracket to the suspension bolt. Be sure to fix
it securely by using a nut and washer from the upper and lower
sides of the hanger bracket. (Refer to Fig.)
[ PRECAUTION ]
Since the unit uses a plastic drain pan, prevent welding spatter
and other foreign substances from entering the outlet hole
during installation.
Adjust the height of the unit.
Check the unit is horizontally level.
Caution
Make sure the unit is installed level using a level or a plastic tube filled with water.In using a plastic tube instead of a level ,adjust
the top surface of the unit to the surface of the water at both ends of the plastic tube and adjust the unit horizontally.(One thing to
watch out for in particular is if it is installed so that the slope is not in the direction of the drain piping,as this might cause leaking.)
Tighten the upper nut.
Mounting the receiver.
Mount the receiver as shown below.
J4
ADDRESS
EXIST
1
CUT
2
Wireless
remote
controller
J4
PCB in the indoor unit
Cut the jumper
JA on PCB.
Cut the jumper J4.
Wireless remote controller
1
2
3
JA
ADDRESS:
CUT
EXIST 1
2
ADDRESS
JA
JB
JC
[ How to secure washers ]
Insert
below washer
Washer
fixing plate
(accessory)
Part to be procured
in the field
[ Securing the hanger bracket ]
Washer for
hanging bracket
Hanger
bracket
Tighten
(double nut)
(accessory)
Vinyl tube
Level
1 Press the receiver into the
mounting frame.
2 Mount the completed
assembly using two screws.
3 Press the decorative cover into
the mounting frame.
Note) Mount the Remote controller cord far enough away from strong electrical wires (such as distribution wires for
electrical lights, air conditioners, etc.) and from weak electrical wires (such as wires for telephones, intercoms, etc.).
01_EN_3P132003-3K.fm Page 5 Wednesday, September 28, 2005 3:32 PM