background image

RZQG71~140L + RZQSG100~Y1B(9)

Split system air conditioners

4P327537-1 – 2012.08

Installation manual

12

Be sure to insulate the liquid and gas-side field piping.

(The highest temperature that the gas-side piping can reach is 
around 120°C, so be sure to use insulating material which is 
very resistant.)

1

Compressor

2

Indoor and outdoor field piping

3

Sealant, etc.

4

Insulation material

A

Wind heat insulation material around the piping section so 
it is not exposed and then cover the insulation material with 
vinyl tape.

10.3. Cautions for necessity of a trap

To avoid the risk of oil held inside the riser piping flowing back into the 
compressor when stopped and causing liquid compression 
phenomenon, or cases of deterioration of oil return, it will be 
necessary to provide a trap at each difference in height of 10 m in the 
riser gas piping.

Trap installation spacing. 

(See figure 6)

A

Outdoor unit

B

Indoor unit

C

Gas piping

D

Liquid piping

E

Oil trap

H

Install trap at each difference in height of 10 m.

A trap is not necessary when the outdoor unit is installed at 
higher position than the indoor unit.

11. Leak test and vacuum drying

When all piping work is complete and the outdoor unit is connected to 
the indoor unit, it is necessary to:

check for any leakages in the refrigerant piping

to perform vacuum drying to remove all moisture in the 
refrigerant piping.

If there is a possibility of moisture being present in the refrigerant 
piping (for example, rainwater may have entered the piping), first 
carry out the vacuum drying procedure below until all moisture has 
been removed.

11.1. General guidelines

All piping inside the unit has been factory tested for leaks.

Use a 2-stage vacuum pump with a non-return valve which can 
evacuate to a gauge pressure of –100.7 kPa (5 Torr absolute, 

 

–755 mm Hg). 

Connect the vacuum pump to 

both

 the service port of the gas 

stop valve and the liquid stop valve to increase efficiency.

11.2. Setup

(See figure 8)

1

Pressure gauge

2

Nitrogen

3

Refrigerant

4

Weighing machine

5

Vacuum pump

6

Stop valve

11.3. Leak test

The leak test must satisfy specification EN378-2.

1

Vacuum leak test

1.1

Evacuate the system from the liquid and gas piping to 

 

–100.7 kPa (5 Torr).

1.2

Once reached, turn off the vacuum pump and check that 
the pressure does not rise for at least 1 minute.

1.3

Should the pressure rise, the system may either contain 
moisture (refer to the paragraph 

"Vacuum drying"

) or have 

leaks.

2

Pressure leak test

2.1

Break the vacuum by pressurizing with nitrogen gas to a 
minimum gauge pressure of 0.2 MPa (2 bar). 

 

Never set the gauge pressure higher than the maximum 
operation pressure of the unit, i.e. 4.0 MPa (40 bar).

2.2

Test for leaks by applying a bubble test solution to all piping 
connections.

2.3

Discharge all nitrogen gas.

NOTICE

Any exposed piping may cause condensation.

DANGER

Do not touch piping and internal parts.

1
3

4

A

2

NOTICE

Do not purge the air with refrigerants. Use a vacuum 
pump to evacuate the installation. No additional 
refrigerant is provided for air purging.

Make sure that the gas stop valve and liquid stop 
valve are firmly closed before performing the leak test 
or vacuum drying.

NOTICE

Make sure to use a recommended bubble test solution 
from your wholesaler.

 

Do not use soap water, which may cause cracking of 
flare nuts (soap water may contain salt, which absorbs 
moisture that will freeze when the piping gets cold), 
and/or lead to corrosion of flared joints (soap water 
may contain ammonia which causes a corrosive effect 
between the brass flare nut and the copper flare).

Summary of Contents for SkyAir RZQG71L7V1B

Page 1: ...RZQG71L7V1B RZQG100L7V1B RZQG125L7V1B RZQG140L7V1B RZQG71L7Y1B9 RZQG100L7Y1B RZQG125L7Y1B RZQG140L7Y1B RZQSG100L7V1B RZQSG125L7V1B RZQSG140L7V1B RZQSG100L7Y1B9 RZQSG125L7Y1B9 RZQSG140L7Y1B Split syst...

Page 2: ...A B 1 2 4 5 H1 L3 L2 L3 L4 L2 L3 L3 L4 L5 L6 A C E B D H 1 2 3 1 50 Hz 220 240 V 3N 50 Hz 380 415 V V1 type Y1 type 1 2 4 5 A 1 A 2 100 100 100 100 1 1 2 H1 H1 H1 H2 H2 H2 L1 L1 L1 L1 L2 7 R410A R410...

Page 3: ...com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet C 12 Merk som det fremkommer i...

Page 4: ...run 18 15 4 Precautions regarding test runs 19 15 5 Failure diagnosis at the moment of first installation 19 16 Wiring diagram 20 Thank you for purchasing this product The original instructions are w...

Page 5: ...at can withstand its weight Insufficient strength may result in the fall of equipment and causing injury Carry out the specified installation work in consideration of strong winds typhoons or earthqua...

Page 6: ...it is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting the unit...

Page 7: ...bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibility of flammable gas or product...

Page 8: ...e outdoor unit In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind...

Page 9: ...outlet space position the units with consideration to the space required for the onsite refrigerant piping work as well Consult your dealer if the work conditions do not match those in the drawings 7...

Page 10: ...llation shall comply with applicable legislation In Europe the EN378 is the application standard that shall be used NOTICE To persons in charge of piping work Be sure to open the stop valve after pipi...

Page 11: ...ze Model 71 100 125 140 Maximum total one way piping length a a Parenthesized figure represents the equivalent length Pair L1 size down 10 m 10 m standard 50 m 70 m 75 m 90 m size up 25 m 35 m 35 m 45...

Page 12: ...ecause using existing piping with deteriorated oil will cause compressor breakdown Put some residual oil of the pipes you want to reuse on a piece of white paper or on the white surface of an oil chec...

Page 13: ...ine it will deteriorate the refrigerant oil 9 3 Stop valve operation Cautions on handling the stop valve Make sure to keep both stop valves open during operation The figure below shows the name of eac...

Page 14: ...to the edge and the surrounding end surfaces to prevent rusting When passing electrical wiring through the knock out holes remove any burrs from the knock out holes and wrap the wiring with protective...

Page 15: ...leaks Use a 2 stage vacuum pump with a non return valve which can evacuate to a gauge pressure of 100 7 kPa 5 Torr absolute 755 mm Hg Connect the vacuum pump to both the service port of the gas stop...

Page 16: ...the leak test and vacuum drying see 11 Leak test and vacuum drying on page 12 This unit requires additional charging of refrigerant according to the length of refrigerant piping connected at the site...

Page 17: ...kg b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0kg b G1 G2 30 5 54 30 29 6 4 R2 0 9 kg 3 Refrige...

Page 18: ...nding on mode type RZQG71 RZQSG100 125 RZQG100 140 RZQSG140 Model Liquid piping Refrigerant piping length 5 10 m a b a For RZQG units only 3 10 m b For RZQG units only When piping length is less than...

Page 19: ...t wiring Secure the earth wire to the stop valve attachment plate so that it does not slide Secure the earth wire to the stop valve attachment plate one more time along with the electric wiring and th...

Page 20: ...esponsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circ...

Page 21: ...the wiring as mentioned on the wiring diagram Make sure no wiring has been forgotten and that there are no missing phases or reverse phases Is the unit properly grounded Is the wiring between units co...

Page 22: ...tector of this product only works during the initialisation stage after a power reset The reversed phase protection detector is designed to stop the product in case of an abnormality when the product...

Page 23: ...or heat exchanger middle R6T Thermistor liquid R10T Thermistor fin RC V1B Signal receiver circuit S1PH High pressure switch TC V1B Signal transmission circuit V1R IGBT power module V1T V1B Insulated g...

Page 24: ...4P327537 1 2012 08 Copyright 2012 Daikin...

Reviews: