RZQG71~140L + RZQSG100~Y1B(9)

Split system air conditioners

4P327537-1 – 2012.08

Installation manual

2

Service company:

Qualified company which can perform or coordinate the required 
service to the unit.

Applicable legislation:

All international, European, national and local directives, laws, 
regulations and/or codes which are relevant and applicable for a 
certain product or domain.

Accessories:

Equipment which is delivered with the unit and which needs to be 
installed according to instructions in the documentation.

Optional equipment: 

Equipment which can optionally be combined to the products as per 
the subject of this manual.

Field supply:

Equipment which needs to be installed according to instructions in 
this manual, but which are not supplied by Daikin.

2.

Safety considerations

The precautions here, all cover very important topics, so be sure to 
follow them carefully.

All activities described in this manual shall be carried out by an 
installer.

Be sure to wear adequate personal protection equipment (protection 
gloves, safety glasses, 

…) when performing installation, 

maintenance or service to the unit.

If not sure of installation procedures or operation of the unit, always 
contact your local dealer for advice and information.

Improper installation or attachment of equipment or accessories 
could result in electric shock, short-circuit, leaks, fire or other damage 
to the equipment. Be sure only to use accessories, optional 
equipment and spare parts made by Daikin which are specially 
designed for use with the products as of subject in this manual and 
have them installed by an installer.

Warning

Ask your dealer or qualified personnel to carry out installation 
work. Do not install the machine by yourself.
Improper installation may result in water leakage, electric shocks 
or fire.

Perform installation work in accordance with this installation 
manual.
Improper installation may lead to water leakage, electric shocks 
or fire.

The equipment is not intended for use in a potentially explosive 
atmosphere.

For RZQG units only

 

For year round cooling applications with low indoor humidity 
conditions, such as Electronic Data Processing rooms, contact 
your dealer or see the engineering databook or the service 
manual.

Consult your local dealer regarding what to do in case of 
refrigerant leakage. When the unit is to be installed in a small 
room, it is necessary to take proper measures so that the 
amount of any leaked refrigerant does not exceed the 
concentration limit in the event of a leakage. Otherwise, this may 
lead to an accident due to oxygen depletion.

Be sure to use only the specified accessories and parts for 
installation work.
Failure to use the specified parts may result in water leakage, 
electric shocks, fire, or the unit falling.

Install the unit on a foundation that can withstand its weight.
Insufficient strength may result in the fall of equipment and 
causing injury.

Carry out the specified installation work in consideration of 
strong winds, typhoons, or earthquakes.
Improper installation work may result in accidents due to fall of 
equipment.

Make sure that all electrical work is carried out by qualified 
personnel according to the applicable legislation and this 
installation manual, using a separate circuit.
Insufficient capacity of the power supply circuit or improper 
electrical construction may lead to electric shocks or fire.

Make sure that all wiring is secure, using the specified wires and 
ensuring that external forces do not act on the terminal 
connections or wires.
Incomplete connection or fixing may cause a fire.

When wiring between the indoor and outdoor units, and wiring 
the power supply, form the wires so that the frontside panel can 
be securely fastened.
If the frontside panel is not in place, overheating of the terminals, 
electric shocks or a fire may be caused.

If refrigerant gas leaks during installation work, ventilate the area 
immediately.
Toxic gas may be produced if refrigerant gas comes into contact 
with fire.

After completing the installation work, check to make sure that 
there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the room 
and comes into contact with a source of fire, such as a fan 
heater, stove or cooker.

When planning to relocate former installed units, you must first 
recover the refrigerant after the pump down operation. Refer to 
chapter 

"13. Pump down operation" on page 15

.

Never directly touch any accidental leaking refrigerant. This 
could result in severe wounds caused by frostbite.

Be sure to install an earth leakage circuit breaker in accordance 
with applicable legislation. Failure to do so may cause electrical 
shock and fire.

DANGER: ELECTRICAL SHOCK

Switch off all power supply before removing the switchbox 
service panel or before making any connections or 
touching electrical parts.

To avoid electric shock, be sure to disconnect the power 
supply 1 minute or more before servicing the electrical 
parts. Even after 1 minute, always measure the voltage at 
the terminals of main circuit capacitors or electrical parts 
and, before touching, be sure that those voltages are 
50 V DC or less.

When service panels are removed, live parts can easily be 
touched by accident. Never leave the unit unattended 
during installation or servicing when the service panel is 
removed.

DANGER: DO NOT TOUCH PIPING AND INTERNAL 
PARTS

Do not touch the refrigerant piping, water piping or internal 
parts during and immediately after operation. The piping 
and internal parts may be hot or cold depending on the 
working condition of the unit.

Your hand may suffer burns or frostbite if you touch the 
piping or internal parts. To avoid injury, give the piping and 
internal parts time to return to normal temperature or, if you 
must touch them, be sure to wear protective gloves.

Summary of Contents for SkyAir RZQG100L7V1B

Page 1: ...RZQG71L7V1B RZQG100L7V1B RZQG125L7V1B RZQG140L7V1B RZQG71L7Y1B9 RZQG100L7Y1B RZQG125L7Y1B RZQG140L7Y1B RZQSG100L7V1B RZQSG125L7V1B RZQSG140L7V1B RZQSG100L7Y1B9 RZQSG125L7Y1B9 RZQSG140L7Y1B Split syst...

Page 2: ...A B 1 2 4 5 H1 L3 L2 L3 L4 L2 L3 L3 L4 L5 L6 A C E B D H 1 2 3 1 50 Hz 220 240 V 3N 50 Hz 380 415 V V1 type Y1 type 1 2 4 5 A 1 A 2 100 100 100 100 1 1 2 H1 H1 H1 H2 H2 H2 L1 L1 L1 L1 L2 7 R410A R410...

Page 3: ...com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet C 12 Merk som det fremkommer i...

Page 4: ...run 18 15 4 Precautions regarding test runs 19 15 5 Failure diagnosis at the moment of first installation 19 16 Wiring diagram 20 Thank you for purchasing this product The original instructions are w...

Page 5: ...at can withstand its weight Insufficient strength may result in the fall of equipment and causing injury Carry out the specified installation work in consideration of strong winds typhoons or earthqua...

Page 6: ...it is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting the unit...

Page 7: ...bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibility of flammable gas or product...

Page 8: ...e outdoor unit In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind...

Page 9: ...outlet space position the units with consideration to the space required for the onsite refrigerant piping work as well Consult your dealer if the work conditions do not match those in the drawings 7...

Page 10: ...llation shall comply with applicable legislation In Europe the EN378 is the application standard that shall be used NOTICE To persons in charge of piping work Be sure to open the stop valve after pipi...

Page 11: ...ze Model 71 100 125 140 Maximum total one way piping length a a Parenthesized figure represents the equivalent length Pair L1 size down 10 m 10 m standard 50 m 70 m 75 m 90 m size up 25 m 35 m 35 m 45...

Page 12: ...ecause using existing piping with deteriorated oil will cause compressor breakdown Put some residual oil of the pipes you want to reuse on a piece of white paper or on the white surface of an oil chec...

Page 13: ...ine it will deteriorate the refrigerant oil 9 3 Stop valve operation Cautions on handling the stop valve Make sure to keep both stop valves open during operation The figure below shows the name of eac...

Page 14: ...to the edge and the surrounding end surfaces to prevent rusting When passing electrical wiring through the knock out holes remove any burrs from the knock out holes and wrap the wiring with protective...

Page 15: ...leaks Use a 2 stage vacuum pump with a non return valve which can evacuate to a gauge pressure of 100 7 kPa 5 Torr absolute 755 mm Hg Connect the vacuum pump to both the service port of the gas stop...

Page 16: ...the leak test and vacuum drying see 11 Leak test and vacuum drying on page 12 This unit requires additional charging of refrigerant according to the length of refrigerant piping connected at the site...

Page 17: ...kg b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0kg b G1 G2 30 5 54 30 29 6 4 R2 0 9 kg 3 Refrige...

Page 18: ...nding on mode type RZQG71 RZQSG100 125 RZQG100 140 RZQSG140 Model Liquid piping Refrigerant piping length 5 10 m a b a For RZQG units only 3 10 m b For RZQG units only When piping length is less than...

Page 19: ...t wiring Secure the earth wire to the stop valve attachment plate so that it does not slide Secure the earth wire to the stop valve attachment plate one more time along with the electric wiring and th...

Page 20: ...esponsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circ...

Page 21: ...the wiring as mentioned on the wiring diagram Make sure no wiring has been forgotten and that there are no missing phases or reverse phases Is the unit properly grounded Is the wiring between units co...

Page 22: ...tector of this product only works during the initialisation stage after a power reset The reversed phase protection detector is designed to stop the product in case of an abnormality when the product...

Page 23: ...or heat exchanger middle R6T Thermistor liquid R10T Thermistor fin RC V1B Signal receiver circuit S1PH High pressure switch TC V1B Signal transmission circuit V1R IGBT power module V1T V1B Insulated g...