Installation manual

7

RZQG71~140L + RZQSG100~Y1B(9)

Split system air conditioners

4P327537-1 – 2012.08

2.

In case of installing multiple units (2 units or more) in lateral 
connection per row.

Relation of dimensions of H, A and L are shown in the table below.

8.

Refrigerant pipe size and allowable 
pipe length

8.1.

Selection of piping material

Construction material: phosphoric acid deoxidised seamless 
copper for refrigerant.

Temper grade: use piping with temper grade in function of the 
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with 
relevant local and national regulations. The minimal pipe 
thickness for R410A piping must be in accordance with the table 
below.

Only use annealed material for flare connections.

8.2.

Refrigerant pipe size

Refer to 

figure 3

 for twin system, to 

figure 4

 for triple system and to 

figure 5

 for double twin system.

Main pipe (pipe between outdoor and first branch).
The pipes should have the same size as the outdoor 
connections.

Pipe between first branch and second branch (L2+L3) (only for 
double twin).

Pipe between branch and indoor units (L2~L3 for twin, L2~L4 for 
triple and L4~L7 for double twin).
These pipe sizes must have the same size as the connected 
indoor units pipe sizes. Branch: see marking '

' on figures 

3

4

 

and 

5

.

L

A

L

H

L

1/2H

250

1/2H<L

H

300

H<L

Installation impossible

DANGER

Piping and other pressure containing parts shall 
comply with the applicable legislation and shall be 
suitable for refrigerant. Use phosphoric acid 
deoxidised seamless copper for refrigerant.

Installation shall be done by an installer, the choice of 
materials and installation shall comply with applicable 
legislation. In Europe the EN378 is the application 
standard that shall be used.

NOTICE

To persons in charge of piping work:

Be sure to open the stop valve after piping installing and 
vacuuming is complete. (Running the system with the 
valve closed may break the compressor.)

INFORMATION

It is forbidden to discharge refrigerant into the atmosphere. 
Collect the refrigerant in accordance with the freon 
collection and destruction law.

NOTICE

Do not use flux when brazing the refrigerant piping.

For brazing, use phosphor copper brazing filler metal 
(BCuP) which does not require a flux.

(If a chlorine flux is used, the piping will corrode, and if the 
flux contains fluoride, it will cause the coolant oil to 
deteriorate, adversely affecting the coolant piping system.

•

•

•

A

L

H

•

•

•

•

•

•

Pipe Ø

Temper grade 

of piping material

Minimal thickness 

t (mm)

6.4 / 9.5 / 12.7

Annealed

0.80

15.9

Annealed

1.00

19.1

Half hard

Refrigerant pipe size

(a)

(a) In case of twin, triple and double twin applications, the listed refrigerant pipe sizes 

relate to the main pipes only. (L1 = the pipes between the outdoor unit and the 
branch in figures 

3

~

5

).

Gas pipe

Model

Size-down

Standard size

Size-up

RZQG71

Ø12.7

Ø15.9

RZQG100~140

Ø15.9

Ø19.1

RZQSG100~140

Ø15.9

Ø19.1

Liquid pipe

Model

Size-down

Standard size

Size-up

RZQG71~140

Ø6.4

Ø9.5

Ø12.7

RZQSG100~140

Ø6.4

Ø9.5

Ø12.7

Liquid

Ø9.5

Gas

Ø15.9

NOTICE

For new installations, use the standard pipe sizes.

When using existing pipes, size-up is allowed as 
mentioned in the table above.
Additional restrictions towards allowable pipe lengths, 
as mentioned in the table 

"Allowable pipe length and 

height difference" on page 8

must be taken into 

account.
Not using the standard pipe size may result in 
capacity decrease. The installer must acknowledge 
this and judge this very carefully in function of the 
complete installation.

Summary of Contents for SkyAir RZQG100L7V1B

Page 1: ...RZQG71L7V1B RZQG100L7V1B RZQG125L7V1B RZQG140L7V1B RZQG71L7Y1B9 RZQG100L7Y1B RZQG125L7Y1B RZQG140L7Y1B RZQSG100L7V1B RZQSG125L7V1B RZQSG140L7V1B RZQSG100L7Y1B9 RZQSG125L7Y1B9 RZQSG140L7Y1B Split syst...

Page 2: ...A B 1 2 4 5 H1 L3 L2 L3 L4 L2 L3 L3 L4 L5 L6 A C E B D H 1 2 3 1 50 Hz 220 240 V 3N 50 Hz 380 415 V V1 type Y1 type 1 2 4 5 A 1 A 2 100 100 100 100 1 1 2 H1 H1 H1 H2 H2 H2 L1 L1 L1 L1 L2 7 R410A R410...

Page 3: ...com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet C 12 Merk som det fremkommer i...

Page 4: ...run 18 15 4 Precautions regarding test runs 19 15 5 Failure diagnosis at the moment of first installation 19 16 Wiring diagram 20 Thank you for purchasing this product The original instructions are w...

Page 5: ...at can withstand its weight Insufficient strength may result in the fall of equipment and causing injury Carry out the specified installation work in consideration of strong winds typhoons or earthqua...

Page 6: ...it is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting the unit...

Page 7: ...bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibility of flammable gas or product...

Page 8: ...e outdoor unit In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind...

Page 9: ...outlet space position the units with consideration to the space required for the onsite refrigerant piping work as well Consult your dealer if the work conditions do not match those in the drawings 7...

Page 10: ...llation shall comply with applicable legislation In Europe the EN378 is the application standard that shall be used NOTICE To persons in charge of piping work Be sure to open the stop valve after pipi...

Page 11: ...ze Model 71 100 125 140 Maximum total one way piping length a a Parenthesized figure represents the equivalent length Pair L1 size down 10 m 10 m standard 50 m 70 m 75 m 90 m size up 25 m 35 m 35 m 45...

Page 12: ...ecause using existing piping with deteriorated oil will cause compressor breakdown Put some residual oil of the pipes you want to reuse on a piece of white paper or on the white surface of an oil chec...

Page 13: ...ine it will deteriorate the refrigerant oil 9 3 Stop valve operation Cautions on handling the stop valve Make sure to keep both stop valves open during operation The figure below shows the name of eac...

Page 14: ...to the edge and the surrounding end surfaces to prevent rusting When passing electrical wiring through the knock out holes remove any burrs from the knock out holes and wrap the wiring with protective...

Page 15: ...leaks Use a 2 stage vacuum pump with a non return valve which can evacuate to a gauge pressure of 100 7 kPa 5 Torr absolute 755 mm Hg Connect the vacuum pump to both the service port of the gas stop...

Page 16: ...the leak test and vacuum drying see 11 Leak test and vacuum drying on page 12 This unit requires additional charging of refrigerant according to the length of refrigerant piping connected at the site...

Page 17: ...kg b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0kg b G1 G2 30 5 54 30 29 6 4 R2 0 9 kg 3 Refrige...

Page 18: ...nding on mode type RZQG71 RZQSG100 125 RZQG100 140 RZQSG140 Model Liquid piping Refrigerant piping length 5 10 m a b a For RZQG units only 3 10 m b For RZQG units only When piping length is less than...

Page 19: ...t wiring Secure the earth wire to the stop valve attachment plate so that it does not slide Secure the earth wire to the stop valve attachment plate one more time along with the electric wiring and th...

Page 20: ...esponsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circ...

Page 21: ...the wiring as mentioned on the wiring diagram Make sure no wiring has been forgotten and that there are no missing phases or reverse phases Is the unit properly grounded Is the wiring between units co...

Page 22: ...tector of this product only works during the initialisation stage after a power reset The reversed phase protection detector is designed to stop the product in case of an abnormality when the product...

Page 23: ...or heat exchanger middle R6T Thermistor liquid R10T Thermistor fin RC V1B Signal receiver circuit S1PH High pressure switch TC V1B Signal transmission circuit V1R IGBT power module V1T V1B Insulated g...

Page 24: ...4P327537 1 2012 08 Copyright 2012 Daikin...

Reviews: