background image

English 

12

Valve cap

Service port

Field piping 
connection part

Valve stem

Silicon sealant

(Take care not to generate cavity.)

<Liquid line>

<Gas line>

Opening direction

Opening direction

Cautions on handling the valve cap

The valve is sealed in the arrow area.  Take care not to 

• 

damage the arrow area.

Valve cap

Stop valve 
(valve cap attachment area)

After handling the valve, make sure to tighten the valve cap 

• 

securely.

Liquid line

Gas line

10.0~12.2 ft·lbf

16.6~20.3 ft·lbf

Cautions on handling the service port

Use charge hose equipped with push in the work.

• 

After the work, make sure to tighten the valve cap securely.

• 

Tightening torque.....8.5~10.3 ft·lbf

Do not apply any force to the valve cap.

Using a spanner on the valve cap and the valve body could 
cause a refrigerant leak.

Stop valve of two
hangs stucture

Stop valve of one
hangs stucture

Torque 
wrench

Torque

wrench

Spanner

Spanner prohibition 
to valve cap and 
body part

ELECTRIC WIRING WORK

7. 

 DANGER

Do not ground units to water pipes, telephone wires or 

• 

lightning rods because incomplete grounding could cause a 
severe shock hazard resulting in severe injury or death, and 
to gas pipes because a gas leak could result in an explosion 
which could lead to severe injury or death.

 WARNING

Disconnect all power to unit to avoid possible electric shock 

• 

during installation.
Use only specifi ed wire and connect wires to terminals 

• 

tightly.  Be careful that wires do not place external stress on 
terminals.  Keep wires in neat order so as to not to obstruct 
other equipment.  Incomplete connections could result in 
overheating, and in worse cases, electric shock or fi re.
For the details, refer to  “

7-3 Power supply wiring connec-

tion procedure

”.

 CAUTION

<To electrician>

Do not operate the air conditioner until the refrigerant piping 

• 

work is completed.
(Operating the air conditioner before the refrigerant piping 
work is completed may damage the compressor.)
Install an earth leakage circuit interrupter.

• 

(The inverter is provided in the air conditioner. In order to 
prevent malfunction of the earth leakage circuit interrupter 
itself, use a breaker resistant to higher harmonics.)

Electricians having suffi cient knowledge should perform the 

• 

electrical wiring work.
All wiring must comply with local electrical codes and Na-
tional Electrical Code (NEC).

Perform the electric wiring work in accordance with the 

• 

“electric wiring diagram label”.
Make sure to turn OFF the branch switch and overcurrent 
breaker before starting the work.
Perform grounding to the indoor units and outdoor units.

• 

Use only copper wires.

• 

Make sure to turn the power off before starting the electric 

• 

wiring work.
Do not turn ON any switch until the work is completed.
The outdoor unit has an inverter which generates noise and 

• 

charges the outer casing with the leakage current. The 
outdoor unit should be grounded so that the effect of the 
generated noise on other equipment can be reduced, and 
that the outer casing can be discharged.
As this unit is equipped with an inverter, installing a phase 

• 

advancing capacitor will not only reduce the power factor 
improvement factor, but may also cause the capacitor to 
overheat due to high-frequency waves.  Therefore, never 
install a phase advancing capacitor.
Never push excessive electric wires into the units.

• 

Protect electric wires with conduit tubes or vinyl tubes so 

• 

that they will not be damaged by edges of knock holes.
Fix electric wires with clamps as accessories so that they will 

• 

not come to contact with pipes and stop valves.
(Refer to  “

7-3 Power supply wiring connection procedure

”.)

01_EN_3PA60114-14U.indd   12

01_EN_3PA60114-14U.indd   12

2/24/2009   5:23:08 PM

2/24/2009   5:23:08 PM

Summary of Contents for SkyAir RZQ18PVJU

Page 1: ... This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener alguna duda Este manual debe permanecer con el ...

Page 2: ...act with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or death After completing the installation work check that the refrigerant gas does not leak Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or death Safely dispose of t...

Page 3: ... the refrigerant pipes Do not turn off the power immediately after stopping operation Always wait at least five minutes before turning off the power Otherwise water leakage and trouble may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keep ing the system clean dry and tight A Clean and dry ...

Page 4: ...D a 0 5 59 115 41 50 50 43 70 95 81 50 23 77 60 67 82 57 A Outdoor temperature FDB B Indoor temperature FWB C Outdoor temperature FWB D Indoor temperature FDB Range for continuous operation Range for pull down operation Range for warming up operation Range for operation Technical specifications 2 2 a and b in the table indicate the operating condition shown in the figure bottom left Model RZQ18PVJ...

Page 5: ...e the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following effect may be caused The capacity is deteriorated The adhered frost increases during heating operation The operation is stopped by pressure rise If excessive strong wind continuously blows from the air outlet side of the outdoor unit the fan may rotate in the reverse direction at high ...

Page 6: ...or unit is installed individually 1 When an obstruction is present only on the air inlet side 4 or more When an obstruction is present on the both sides 4 or more 4 or more 4 or more When two or more outdoor units are installed side 2 by side When an obstruction is present on the both sides 40 or more 12 or more 8 or more When an obstruction is present also in the upward area When one outdoor unit...

Page 7: ...ts are installed side 2 by side 12 or more H L 40 or more L H When an obstruction is present also in the upward area When one outdoor unit is installed individually 1 L A 20 or less 40 or more 10 or more H The dimensional relationship between H L and A is as shown in the table below L A L H 0 L 1 2H 30 1 2H L H 40 H L Install the frame to achieve L H NOTE Close the area under the frame so that the...

Page 8: ... L A L H 0 L 1 2H 4 1 2H L H 8 H L Install the frame to achieve L H NOTE Close the area under the frame so that the outlet air does not bypass there When only two outdoor units are installed side by 2 side 60 or more 20 or less H L A 40 or more The dimensional relationship between H L and A is as shown in the table below L A L H 0 L 1 2H 10 1 2H L H 12 H L Install the frame to achieve L H NOTE Clo...

Page 9: ...oundation bolts should be protruded by 15 16 in Refer to figure 13 16 Resin washer Drain treatment In a location where drain from the outdoor unit may cause troubles for example where drainage may splash on gen eral passersby perform the drain piping work using the drain plug optional For drain treatment space of at least 4 in is required under the bottom frame of the outdoor unit In the drain pip...

Page 10: ...film inside the pipes adversely affecting valves and compressor in the refrigerating system and preventing normal operation DANGER Use of oxygen could cause an explosion resulting in severe injury or death Only use nitrogen gas Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or d...

Page 11: ...g 6 6 The unit has been checked for leaks by the manufacturer Confirm that the valves are firmly closed before airtight test or vacuumdrying To prevent entry of any impurities and insure sufficient pres sure resistance always use the special tools dedicated for R410A Perform the following inspections securely after the piping work Airtight test Make sure to use nitrogen gas For the service port po...

Page 12: ...ls you exclusively use on R410A installations to withstand the pressure and to prevent foreign materials from mixing into the system Procedures for charging additional refrigerant Nitrogen Dotted lines represent field piping Cylinder Stop valve service port Vacuum pump Weighing scale Charge hose R410A Pressure reducing valve Outdoor unit Indoor units Liquid line Gas line Siphon system Valve A See ...

Page 13: ...ec tion procedure CAUTION To electrician Do not operate the air conditioner until the refrigerant piping work is completed Operating the air conditioner before the refrigerant piping work is completed may damage the compressor Install an earth leakage circuit interrupter The inverter is provided in the air conditioner In order to prevent malfunction of the earth leakage circuit interrupter itself ...

Page 14: ...re it as described in 7 3 Power supply wiring connection procedure Fix the wiring between the units in accordance with 7 4 Transmission wiring connection procedure Secure the wirings with the clamps accessory so that do not touch the piping Make sure the wirings will not be pinched by the front panel and close the panel firmly Route the conduit along the unit by using a elbow socket and so on to p...

Page 15: ...e table below for tightening torque for the terminal screws Tightening torque ft lbf M5 Power supply and ground terminal block 1 76 2 15 M4 Shielded ground 0 87 1 06 M3 5 Transmission wiring terminal block 0 58 0 72 Transmission wiring connection procedure 7 4 If an excessive force is applied while connecting a cable to the terminal block on the PC board the PC board may be damaged IN D OUT D F1F2...

Page 16: ...he power to the crankcase heater 2 Open the outer panel of the outdoor unit Check the LED on the PC board A1P and A2P in the outdoor unit to see if the data transmission is performed normally One outdoor unit installed H1P H5P H4P H6P H7P H2P H3P HAP Blinking ON OFF LED display LED display Default status before delivery A1P A2P SERVICE MONITOR MODE IND SLAVE MASTER TEST HWL C H SELE CTOR L N O P D...

Page 17: ...ration button since it was first installed a malfunc tion code U3 is displayed In this case perform the check operation by referring to 9 1 Power on and check operation When a malfunction code is displayed in the remote controller Check a malfunction code in the remote controller connected to the indoor unit Malfunction code Cause Solution E3 The stop valves in the outdoor unit remain closed Open ...

Page 18: ...in to which it could leak The unit of measurement of the concentration is lb ft the weight in lb of the refrigerant gas in 1ft volume of the occu pied space Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required Direction of the refrigerant flow Room where refrigerant leak has occurred outflow of all the refrigerant from the system Pa...

Page 19: ...3PA60114 14U EM08A096 0902 HT ...

Reviews: