background image

English 

2

When wiring the power supply and connecting the 

 

remote controller wiring and transmission wiring, posi-
tion the wires so that the terminal cover (panel) can be 
securely fastened.

Improper positioning of the electric parts box lid may result 
in electric shocks, fi re or the terminals overheating.

Before touching electrical parts, turn off the power.

 

Securely install the outside unit terminal cover (panel).

 

If the terminal cover (panel) is not installed properly, dust or 
water may enter the outside unit and fi re or electric shock 
may result.

When installing or relocating the system, be sure to 

 

keep the refrigerant circuit free from substances other 
than the specifi ed refrigerant (R410A) such as air.

Any presence of air or other foreign materials in the refriger-
ant circuit causes an abnormal pressure rise or rupture, 
resulting in injury.

Do not reconstruct or change the settings of the protec-

 

tion devices.

If the pressure switch, thermal switch, or other protection 
device is shorted and operated forcibly, or parts other than 
those specifi ed by Daikin are used, fi re or explosion may 
result.

Do not touch the switch with wet fi ngers.

 

Touching a switch with wet fi ngers can cause electric shock.

Be sure to install a ground fault circuit interrupter.

 

Failure to install a ground fault circuit interrupter may result 
in electric shocks, or fi re.

Heat exchanger fi ns are sharp enough to cut.

 

To avoid injury wear glove or cover the fi ns when working 
around them.

Do not allow children to play on or around the unit as 

 

they could be injured.
Refrigerant pipes may be very hot or very cold during or 

 

immediately after operation.

Touching them could result in burns or frostbite. To avoid 
injury give the pipes time to return to normal temperature or, 
if you must touch them, be sure to wear proper gloves.

 CAUTION

While following the instructions in this installation 

 

manual, install drain piping in order to ensure proper 
drainage and insulate piping in order to prevent con-
densation.

Improper drain piping may result in water leakage and 
property damage.

Be very careful about product transportation.

 

Do not touch the refrigerant pipes during and immedi-

 

ately after operation.

During and immediately after operation, the refrigerant pipes 
may be hot and may be cold, depending on the condition of 
the refrigerant fl owing through the refrigerant piping, com-
pressor, and other refrigerant cycle parts. Your hands may 
suffer burns or frostbite if you touch the refrigerant pipes.

Do not turn off the power immediately after stopping 

 

operation.

Always wait at least fi ve minutes before turning off the 
power. Otherwise, water leakage and trouble may occur.

Do not use a charging cylinder.

 

Using a charging cylinder may cause the refrigerant to 
deteriorate.

The refrigerant R410A requires strict cautions for keep-

 

ing the system clean, dry and tight.

A.  Clean and dry

Foreign materials (including mineral oils such as SUNISO 
oil or moisture) should be prevented from getting mixed 
into the system.

B.  Tight

R410A does not contain any chlorine, does not destroy 
the ozone layer, and does not reduce the earth’s protec-
tion against harmful ultraviolet radiation.
R410A can contribute slightly to the greenhouse effect if it 
is released. Therefore we should take special attention to 
check the tightness of the installation.
Read the chapter “Refrigerant piping work” carefully and 
follow these procedures correctly.

Since R410A is a mixed refrigerant, the required addi-

 

tional refrigerant must be charged in its liquid state. (If 
the refrigerant is charged in a state of gas, its composi-
tion changes and the system will not work properly.)

The indoor unit is for R410A. See the catalog for indoor unit 
models which can be connected.
(Normal operation is not possible when connected to other 
units.)

Do not install the air conditioner in the following loca-

 

tions:

(a) where a mineral oil mist or an oil spray or vapor is pro-

duced, for example in a kitchen
Plastic parts may deteriorate and fall off or result in water 
leakage.

(b) where corrosive gas, such as sulfurous acid gas, is 

produced
Corroding copper pipes or soldered parts may result in 
refrigerant leakage.

(c)  near machinery emitting electromagnetic waves

Electromagnetic waves may disturb the operation of the 
control system and result in a malfunction of the unit.

(d) where fl ammable gas may leak, where there are carbon 

fi ber or ignitable dust suspensions in the air, or where 
volatile fl ammables such as thinner or gasoline are 
handled.
Operating the unit in such conditions may result in fi re.

For installation of the indoor units, refer to the installa-

 

tion manual supplied together with each indoor unit.
Never operate the air conditioner with the discharge 

 

pipe thermister (R3T), suction pipe thermister (R2T) and 
pressure sensors (S1NPH, S1NPL) removed.

Such operation may burn out the compressor.

Make sure to provide for adequate measures in order to 

 

prevent that the outdoor unit be used as a shelter by 
small animals.

Small animals making contact with electrical parts can 
cause malfunctions, smoke or fi re. Please instruct the cus-
tomer to keep the area around the unit clean.

01_EN_3PA60114-14U.indd   2

01_EN_3PA60114-14U.indd   2

2/24/2009   5:23:04 PM

2/24/2009   5:23:04 PM

Summary of Contents for SkyAir RZQ18PVJU

Page 1: ... This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener alguna duda Este manual debe permanecer con el ...

Page 2: ...act with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or death After completing the installation work check that the refrigerant gas does not leak Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or death Safely dispose of t...

Page 3: ... the refrigerant pipes Do not turn off the power immediately after stopping operation Always wait at least five minutes before turning off the power Otherwise water leakage and trouble may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keep ing the system clean dry and tight A Clean and dry ...

Page 4: ...D a 0 5 59 115 41 50 50 43 70 95 81 50 23 77 60 67 82 57 A Outdoor temperature FDB B Indoor temperature FWB C Outdoor temperature FWB D Indoor temperature FDB Range for continuous operation Range for pull down operation Range for warming up operation Range for operation Technical specifications 2 2 a and b in the table indicate the operating condition shown in the figure bottom left Model RZQ18PVJ...

Page 5: ...e the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following effect may be caused The capacity is deteriorated The adhered frost increases during heating operation The operation is stopped by pressure rise If excessive strong wind continuously blows from the air outlet side of the outdoor unit the fan may rotate in the reverse direction at high ...

Page 6: ...or unit is installed individually 1 When an obstruction is present only on the air inlet side 4 or more When an obstruction is present on the both sides 4 or more 4 or more 4 or more When two or more outdoor units are installed side 2 by side When an obstruction is present on the both sides 40 or more 12 or more 8 or more When an obstruction is present also in the upward area When one outdoor unit...

Page 7: ...ts are installed side 2 by side 12 or more H L 40 or more L H When an obstruction is present also in the upward area When one outdoor unit is installed individually 1 L A 20 or less 40 or more 10 or more H The dimensional relationship between H L and A is as shown in the table below L A L H 0 L 1 2H 30 1 2H L H 40 H L Install the frame to achieve L H NOTE Close the area under the frame so that the...

Page 8: ... L A L H 0 L 1 2H 4 1 2H L H 8 H L Install the frame to achieve L H NOTE Close the area under the frame so that the outlet air does not bypass there When only two outdoor units are installed side by 2 side 60 or more 20 or less H L A 40 or more The dimensional relationship between H L and A is as shown in the table below L A L H 0 L 1 2H 10 1 2H L H 12 H L Install the frame to achieve L H NOTE Clo...

Page 9: ...oundation bolts should be protruded by 15 16 in Refer to figure 13 16 Resin washer Drain treatment In a location where drain from the outdoor unit may cause troubles for example where drainage may splash on gen eral passersby perform the drain piping work using the drain plug optional For drain treatment space of at least 4 in is required under the bottom frame of the outdoor unit In the drain pip...

Page 10: ...film inside the pipes adversely affecting valves and compressor in the refrigerating system and preventing normal operation DANGER Use of oxygen could cause an explosion resulting in severe injury or death Only use nitrogen gas Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or d...

Page 11: ...g 6 6 The unit has been checked for leaks by the manufacturer Confirm that the valves are firmly closed before airtight test or vacuumdrying To prevent entry of any impurities and insure sufficient pres sure resistance always use the special tools dedicated for R410A Perform the following inspections securely after the piping work Airtight test Make sure to use nitrogen gas For the service port po...

Page 12: ...ls you exclusively use on R410A installations to withstand the pressure and to prevent foreign materials from mixing into the system Procedures for charging additional refrigerant Nitrogen Dotted lines represent field piping Cylinder Stop valve service port Vacuum pump Weighing scale Charge hose R410A Pressure reducing valve Outdoor unit Indoor units Liquid line Gas line Siphon system Valve A See ...

Page 13: ...ec tion procedure CAUTION To electrician Do not operate the air conditioner until the refrigerant piping work is completed Operating the air conditioner before the refrigerant piping work is completed may damage the compressor Install an earth leakage circuit interrupter The inverter is provided in the air conditioner In order to prevent malfunction of the earth leakage circuit interrupter itself ...

Page 14: ...re it as described in 7 3 Power supply wiring connection procedure Fix the wiring between the units in accordance with 7 4 Transmission wiring connection procedure Secure the wirings with the clamps accessory so that do not touch the piping Make sure the wirings will not be pinched by the front panel and close the panel firmly Route the conduit along the unit by using a elbow socket and so on to p...

Page 15: ...e table below for tightening torque for the terminal screws Tightening torque ft lbf M5 Power supply and ground terminal block 1 76 2 15 M4 Shielded ground 0 87 1 06 M3 5 Transmission wiring terminal block 0 58 0 72 Transmission wiring connection procedure 7 4 If an excessive force is applied while connecting a cable to the terminal block on the PC board the PC board may be damaged IN D OUT D F1F2...

Page 16: ...he power to the crankcase heater 2 Open the outer panel of the outdoor unit Check the LED on the PC board A1P and A2P in the outdoor unit to see if the data transmission is performed normally One outdoor unit installed H1P H5P H4P H6P H7P H2P H3P HAP Blinking ON OFF LED display LED display Default status before delivery A1P A2P SERVICE MONITOR MODE IND SLAVE MASTER TEST HWL C H SELE CTOR L N O P D...

Page 17: ...ration button since it was first installed a malfunc tion code U3 is displayed In this case perform the check operation by referring to 9 1 Power on and check operation When a malfunction code is displayed in the remote controller Check a malfunction code in the remote controller connected to the indoor unit Malfunction code Cause Solution E3 The stop valves in the outdoor unit remain closed Open ...

Page 18: ...in to which it could leak The unit of measurement of the concentration is lb ft the weight in lb of the refrigerant gas in 1ft volume of the occu pied space Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required Direction of the refrigerant flow Room where refrigerant leak has occurred outflow of all the refrigerant from the system Pa...

Page 19: ...3PA60114 14U EM08A096 0902 HT ...

Reviews: