background image

English

(Flux has an extremely negative effect on refrigerant piping 
systems. For instance, if chlorine based fl ux is used, it will 
cause pipe corrosion. Flux containing fl uorine will damage 
refrigerant oil.)

 NOTE

Maximum piping length between the outdoor and indoor unit 

• 

is 230ft.
Installation tools:

• 

Make sure to use installation tools (gauge manifold charge 
hose, etc.) that are exclusively used for R410A installations 
to withstand the pressure and to prevent foreign materials 
(e.g. mineral oils such as SUNISO and moisture) from 
mixing into the system.
(The screw specifi cations differ for R410A and R407C.)
Vacuum pump (use a 2-stage vacuum pump with a non-
return valve):

Make sure the pump oil does not fl ow oppositely into the 

1. 

system while the pump is not working.
Use a vacuum pump which can evacuate to –14.6 psi.

2. 

Selection of piping material

6-1 

Foreign materials inside pipes (including oils for fabrication) 

1. 

must be 9mg/10ft. or less.
Use the following material specifi cation for refrigerant 

2. 

pipping:

construction material: Phosphoric acid deoxidized seam-

• 

less copper for refrigerant.
size: Determine the proper size referring to chapter 

• 

“Example of connection”.

Protection of piping

6-2 

Protect the pipings to prevent moisture and dusts from 

• 

coming into the pipings.
Especially, pay attention when passing the pipings through a 

• 

hole or connecting the end of piping to the outdoor.

Location

Working period

Protection method

Outdoor

1 month or more

Pinch pipes

Less than 1 month

Pinch or tape pipes

Indoor

Regardless of period

Piping connection

6-3 

For handling of stop valves, refer to “Stop valve opera-

 

tion method” in “6-7 Additional refrigerant charge”.
Only use the fl are nuts attached to the stop valves.

 

Using different fl are nuts may cause the refrigerant to 
leak.
Be sure to perform a nitrogen blow when brazing.

 

(Brazing without performing nitrogen replacement or releasing 
nitrogen into the piping will create large quantities of oxidized 
fi lm inside the pipes, adversely affecting valves and compressor 
in the refrigerating system and preventing normal operation.)

 DANGER

Use of oxygen could cause an explosion resulting in severe 

• 

injury or death.  Only use nitrogen gas.
Refrigerant gas may produce toxic gas if it comes in contact 

• 

with fi re such as from a fan heater, stove or cooking device. 
Exposure to this gas could cause severe injury or death.

 NOTE

When brazing with blowing nitrogen, set the nitrogen pres-

• 

sure to 2.9 psi or less by using a pressure reducing valve.

Location to 
be brazed

Taping

Refrigerant 
piping

Nitrogen

Regulator

Manual valve

Nitrogen

 CAUTION

Do not use anti-oxidants when brazing.

• 

Residue can clog pipes and break the unit.

  Do not let any refrigerant other than the specifi ed refrigerant 

enter  the refrigerant system.

  Do not let any gas such as air enter the refrigerant system.

Precautions when connecting the pipings

See the following table for fl are dimensions.

• 

When connecting the fl are nuts, apply refrigerant oil to the 

• 

inside and outside of the fl ares and turn them three or four 
times at fi rst. (Use ester oil or ether oil.)
See the following table for tightening torque. (Applying too 

• 

much torque may cause the fl ares to crack.)
After connecting all the pipings perform a gas leak check by 

• 

using nitrogen.

Pipe size

Tightening 

torque (ft·lbf)

Flare dimension 

A (in.)

Flare shape (in.)

φ

3/8”

24.1 - 29.4

0.504 - 0.520

A

45°± 2°

9

0°± 2°

R0.016

~0.031

φ

5/8”

45.6 - 55.6

0.760 - 0.776

Ester oil or ether oil

If you are obliged to install the unit without a torque wrench, 

• 

you may follow the installation method mentioned below.
After the work is fi nished, make sure to check that there is 
no gas leak.
When you keep on tightening the fl are nut with a spanner, 

• 

there is a point where the tightening torque suddenly in-
creases.
From that position, further tighten the fl are nut the angle 
shown below.

Pipe size

Tightening angle 

(Guideline)

Recommended arm 

length of tool (in.)

φ

3/8”

60°~90°

Approx. 7 7/8

φ

5/8”

30°~60°

Approx. 11 13/16

Disposal requirements

Dismantling of the unit,  treatment of the refrigerant, oil and 
eventual other parts should be comply the relevant local and 
national regulations.

01_EN_3PA60114-14U.indd   9

01_EN_3PA60114-14U.indd   9

2/24/2009   5:23:07 PM

2/24/2009   5:23:07 PM

Summary of Contents for SkyAir RZQ18PVJU

Page 1: ... This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener alguna duda Este manual debe permanecer con el ...

Page 2: ...act with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or death After completing the installation work check that the refrigerant gas does not leak Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or death Safely dispose of t...

Page 3: ... the refrigerant pipes Do not turn off the power immediately after stopping operation Always wait at least five minutes before turning off the power Otherwise water leakage and trouble may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keep ing the system clean dry and tight A Clean and dry ...

Page 4: ...D a 0 5 59 115 41 50 50 43 70 95 81 50 23 77 60 67 82 57 A Outdoor temperature FDB B Indoor temperature FWB C Outdoor temperature FWB D Indoor temperature FDB Range for continuous operation Range for pull down operation Range for warming up operation Range for operation Technical specifications 2 2 a and b in the table indicate the operating condition shown in the figure bottom left Model RZQ18PVJ...

Page 5: ...e the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following effect may be caused The capacity is deteriorated The adhered frost increases during heating operation The operation is stopped by pressure rise If excessive strong wind continuously blows from the air outlet side of the outdoor unit the fan may rotate in the reverse direction at high ...

Page 6: ...or unit is installed individually 1 When an obstruction is present only on the air inlet side 4 or more When an obstruction is present on the both sides 4 or more 4 or more 4 or more When two or more outdoor units are installed side 2 by side When an obstruction is present on the both sides 40 or more 12 or more 8 or more When an obstruction is present also in the upward area When one outdoor unit...

Page 7: ...ts are installed side 2 by side 12 or more H L 40 or more L H When an obstruction is present also in the upward area When one outdoor unit is installed individually 1 L A 20 or less 40 or more 10 or more H The dimensional relationship between H L and A is as shown in the table below L A L H 0 L 1 2H 30 1 2H L H 40 H L Install the frame to achieve L H NOTE Close the area under the frame so that the...

Page 8: ... L A L H 0 L 1 2H 4 1 2H L H 8 H L Install the frame to achieve L H NOTE Close the area under the frame so that the outlet air does not bypass there When only two outdoor units are installed side by 2 side 60 or more 20 or less H L A 40 or more The dimensional relationship between H L and A is as shown in the table below L A L H 0 L 1 2H 10 1 2H L H 12 H L Install the frame to achieve L H NOTE Clo...

Page 9: ...oundation bolts should be protruded by 15 16 in Refer to figure 13 16 Resin washer Drain treatment In a location where drain from the outdoor unit may cause troubles for example where drainage may splash on gen eral passersby perform the drain piping work using the drain plug optional For drain treatment space of at least 4 in is required under the bottom frame of the outdoor unit In the drain pip...

Page 10: ...film inside the pipes adversely affecting valves and compressor in the refrigerating system and preventing normal operation DANGER Use of oxygen could cause an explosion resulting in severe injury or death Only use nitrogen gas Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could cause severe injury or d...

Page 11: ...g 6 6 The unit has been checked for leaks by the manufacturer Confirm that the valves are firmly closed before airtight test or vacuumdrying To prevent entry of any impurities and insure sufficient pres sure resistance always use the special tools dedicated for R410A Perform the following inspections securely after the piping work Airtight test Make sure to use nitrogen gas For the service port po...

Page 12: ...ls you exclusively use on R410A installations to withstand the pressure and to prevent foreign materials from mixing into the system Procedures for charging additional refrigerant Nitrogen Dotted lines represent field piping Cylinder Stop valve service port Vacuum pump Weighing scale Charge hose R410A Pressure reducing valve Outdoor unit Indoor units Liquid line Gas line Siphon system Valve A See ...

Page 13: ...ec tion procedure CAUTION To electrician Do not operate the air conditioner until the refrigerant piping work is completed Operating the air conditioner before the refrigerant piping work is completed may damage the compressor Install an earth leakage circuit interrupter The inverter is provided in the air conditioner In order to prevent malfunction of the earth leakage circuit interrupter itself ...

Page 14: ...re it as described in 7 3 Power supply wiring connection procedure Fix the wiring between the units in accordance with 7 4 Transmission wiring connection procedure Secure the wirings with the clamps accessory so that do not touch the piping Make sure the wirings will not be pinched by the front panel and close the panel firmly Route the conduit along the unit by using a elbow socket and so on to p...

Page 15: ...e table below for tightening torque for the terminal screws Tightening torque ft lbf M5 Power supply and ground terminal block 1 76 2 15 M4 Shielded ground 0 87 1 06 M3 5 Transmission wiring terminal block 0 58 0 72 Transmission wiring connection procedure 7 4 If an excessive force is applied while connecting a cable to the terminal block on the PC board the PC board may be damaged IN D OUT D F1F2...

Page 16: ...he power to the crankcase heater 2 Open the outer panel of the outdoor unit Check the LED on the PC board A1P and A2P in the outdoor unit to see if the data transmission is performed normally One outdoor unit installed H1P H5P H4P H6P H7P H2P H3P HAP Blinking ON OFF LED display LED display Default status before delivery A1P A2P SERVICE MONITOR MODE IND SLAVE MASTER TEST HWL C H SELE CTOR L N O P D...

Page 17: ...ration button since it was first installed a malfunc tion code U3 is displayed In this case perform the check operation by referring to 9 1 Power on and check operation When a malfunction code is displayed in the remote controller Check a malfunction code in the remote controller connected to the indoor unit Malfunction code Cause Solution E3 The stop valves in the outdoor unit remain closed Open ...

Page 18: ...in to which it could leak The unit of measurement of the concentration is lb ft the weight in lb of the refrigerant gas in 1ft volume of the occu pied space Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required Direction of the refrigerant flow Room where refrigerant leak has occurred outflow of all the refrigerant from the system Pa...

Page 19: ...3PA60114 14U EM08A096 0902 HT ...

Reviews: