3
|
Specific installer safety instructions
Installer reference guide
21
RZAG71~Y1
Sky Air Alpha-series
4P695307-1 – 2022.05
CAUTION
▪
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
▪
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
▪
The length of the conductors between the power supply stress relief and the
terminal block itself MUST be as such that the current-carrying wires are
tautened before the earth wire is in case the power supply is pulled loose from
the stress relief.
)
WARNING
Commissioning method MUST be in accordance with the instructions from this
manual. See
65].
CAUTION
Do NOT perform the test operation while working on the indoor units.
When performing the test operation, NOT ONLY the outdoor unit, but the connected
indoor unit will operate as well. Working on an indoor unit while performing a test
operation is dangerous.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT
remove the fan guard. When the fan is rotating at high speed, it will cause injury.
Troubleshooting (
)
WARNING
▪
When carrying out an inspection on the switch box of the unit, ALWAYS make
sure that the unit is disconnected from the mains. Turn off the respective circuit
breaker.
▪
When a safety device was activated, stop the unit and find out why the safety
device was activated before resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default setting. If you are unable to
find the cause of the problem, call your dealer.
WARNING
Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this
appliance MUST NOT be supplied through an external switching device, such as a
timer, or connected to a circuit that is regularly turned ON and OFF by the utility.