![Daikin Sky Air Alpha Series Installer'S Reference Manual Download Page 57](http://html1.mh-extra.com/html/daikin/sky-air-alpha-series/sky-air-alpha-series_installers-reference-manual_4705613057.webp)
7
|
Installation
Installer reference guide
57
RZAG71~Y1
Sky Air Alpha-series
4P695307-1 – 2022.05
Prerequisite:
Before completely recharging refrigerant, make sure the system is
pumped down, the outdoor unit's
external
refrigerant piping is checked (leak test,
vacuum drying) and vacuum drying on the outdoor unit's
internal
refrigerant
piping is performed.
1
If not already done (for vacuum drying of the unit), activate the vacuum mode
(see
"To activate/deactivate the vacuum mode field setting"
2
Connect the refrigerant cylinder to the service port of the liquid stop valve.
3
Open the liquid stop valve.
4
Charge the complete refrigerant amount.
5
Deactivate the vacuum mode (see
"To activate/deactivate the vacuum mode
55]).
6
Open the gas stop valve.
7.6.7 To fix the fluorinated greenhouse gases label
1
Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a
If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of
a
.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e Quantity of fluorinated greenhouse gases
of the total refrigerant charge
expressed as tonnes CO
2
equivalent.
f
GWP = Global warming potential
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label.
2
Fix the label on the inside of the outdoor unit. There is a dedicated place for it
on the wiring diagram label.
Summary of Contents for Sky Air Alpha Series
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ...4P695307 1 2022 05 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...