3 Installation

Installation manual

5

AZQS100~14 AZQS100~140B7Y1B
Split system air conditioners
4P385528­1 – 2014.08

3.1.4

To prevent the outdoor unit from falling
over

Connect cables (field supply) as shown:

3.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING

3.2.1

To connect the refrigerant piping to the
outdoor unit

1

Do the following:

▪ Remove the service cover (a) with screw (b).
▪ Remove the piping intake plate (c) with screw (d).

c

a

b

d

2

Choose a piping route (a, b, c or d).

a

b

c

d

3

If you have chosen the downwards piping route:

▪ Drill (a, 4×) and remove the knockout hole (b).
▪ Cut out the slits (c) with a metal saw.

c

c

b

a

4× Ø6 mm

4

Do the following:

▪ Connect the liquid pipe (a) to the liquid stop valve.
▪ Connect the gas pipe (b) to the gas stop valve.

a

b

5

Do the following:

▪ Insulate the liquid piping (a) and the gas piping (b).
▪ Wind  heat  insulation  around  the  curves,  and  then  cover  it

with vinyl tape (c).

▪ Make  sure  the  field  piping  does  not  touch  any  compressor

components (d).

▪ Seal the insulation ends (sealant etc.) (e).

d

e

f

b

a

c

6

If  the  outdoor  unit  is  installed  above  the  indoor  unit,  cover  the
stop  valves  (f,  see  above)  with  sealing  material  to  prevent
condensed water on the stop valves from moving to the indoor
unit.

NOTICE

Any exposed piping might cause condensation.

7

Reattach the service cover and the piping intake plate.

8

Seal  all  gaps  (example:  a)  to  prevent  snow  and  small  animals
from entering the system.

a

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

Summary of Contents for Siesta

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners AZQS100B8V1B AZQS125B8V1B AZQS140B8V1B AZQS100B7Y1B AZQS125B7Y1B AZQS140B7Y1B...

Page 2: ...iivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja liet...

Page 3: ...tdoor unit installation 9 3 6 1 To finish the outdoor unit installation 9 3 6 2 To check the insulation resistance of the compressor 9 4 Commissioning 9 4 1 Checklist before test run 9 4 2 To perform...

Page 4: ...ake sure that condensation water can be evacuated properly INFORMATION If necessary you can use a drain plug kit field supply to prevent drain water from dripping NOTICE If drain holes of the outdoor...

Page 5: ...piping a and the gas piping b Wind heat insulation around the curves and then cover it with vinyl tape c Make sure the field piping does not touch any compressor components d Seal the insulation ends...

Page 6: ...surize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solution to all connections 3 Discharge all nitrogen gas 3 3 3 To perform vacuum drying 1 Vacuum...

Page 7: ...F ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables CAUTION For use of units in applications with temperature alarm settings it is recommended to foresee a delay of 10 minutes f...

Page 8: ...unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover Fix the earth wire to the stop valve attachment plate so that it does not slide Make sure the...

Page 9: ...edure is finished 1 M Insulation resistance is not OK Go to the next step 2 Turn ON the power and leave it on for 6 hours Result The compressor will heat up and evaporate any refrigerant in the compre...

Page 10: ...d switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA The outdoor and indoor unit are incompatible NOTICE The reversed phase protection detector of this pr...

Page 11: ...tor lower fan PS Switching power supply Q1DI Earth leakage circuit breaker field supply R1 R6 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger...

Page 12: ...4P385528 1 2014 08 Copyright 2014 Daikin 4P385528 1 0000000T...

Reviews: