background image

3 Installation

Installation manual

6

AZQS100~14 AZQS100~140B7Y1B

Split system air conditioners

4P385528­1 – 2014.08

3.2.2

To determine if oil traps are required

If oil flows back into the outdoor unit's compressor, this might cause
liquid compression or deterioration of oil return. Oil traps in the rising
gas piping can prevent this.

If

Then

The indoor unit is installed
higher than the outdoor
unit

Install an oil trap every 10 m (height
difference).

a

b

10 m

a

 Rising gas piping with oil trap

b

 Liquid piping

The outdoor unit is
installed higher than the
indoor unit

Oil traps are NOT required.

3.3

Checking the refrigerant piping

3.3.1

Checking refrigerant piping: Setup

a

c

f

b

d

e

R410A

a

Pressure gauge

b

Nitrogen

c

Refrigerant

d

Weighing machine

e

Vacuum pump

f

Stop valve

3.3.2

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare.

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

3.3.3

To perform vacuum drying

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4­5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Evacuate  for  at  least  2  hours  to  a  pressure  on  the  manifold  of
−0.1 MPa (−1 bar).

4

After  turning  OFF  the  pump,  check  the  pressure  for  at  least
1 hour.

5

If you do NOT reach the target vacuum or cannot maintain the
vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

3.4

Charging refrigerant

3.4.1

To determine the additional refrigerant
amount

To determine if adding additional refrigerant is necessary

If

Then

L1≤30 m (chargeless length)

You do not have to add
additional refrigerant.

L1>30 m

You must add additional
refrigerant.

For future servicing, encircle the
selected amount in the tables
below.

INFORMATION

Piping length is the one way length of liquid piping.

To determine the additional refrigerant amount (R in kg)

L1 (m)

30~40 m

40~50 m

R:

0.5 kg

1.0 kg

3.4.2

To determine the complete recharge
amount

Model

L1 (m)

5~10

10~20

20~30

30~40

40~50

125

1.9

2.4

2.9

3.4

3.9

AZQS140

3.0

3.5

4.0

4.5

5.0

Summary of Contents for Siesta

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners AZQS100B8V1B AZQS125B8V1B AZQS140B8V1B AZQS100B7Y1B AZQS125B7Y1B AZQS140B7Y1B...

Page 2: ...iivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja liet...

Page 3: ...tdoor unit installation 9 3 6 1 To finish the outdoor unit installation 9 3 6 2 To check the insulation resistance of the compressor 9 4 Commissioning 9 4 1 Checklist before test run 9 4 2 To perform...

Page 4: ...ake sure that condensation water can be evacuated properly INFORMATION If necessary you can use a drain plug kit field supply to prevent drain water from dripping NOTICE If drain holes of the outdoor...

Page 5: ...piping a and the gas piping b Wind heat insulation around the curves and then cover it with vinyl tape c Make sure the field piping does not touch any compressor components d Seal the insulation ends...

Page 6: ...surize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solution to all connections 3 Discharge all nitrogen gas 3 3 3 To perform vacuum drying 1 Vacuum...

Page 7: ...F ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables CAUTION For use of units in applications with temperature alarm settings it is recommended to foresee a delay of 10 minutes f...

Page 8: ...unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover Fix the earth wire to the stop valve attachment plate so that it does not slide Make sure the...

Page 9: ...edure is finished 1 M Insulation resistance is not OK Go to the next step 2 Turn ON the power and leave it on for 6 hours Result The compressor will heat up and evaporate any refrigerant in the compre...

Page 10: ...d switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA The outdoor and indoor unit are incompatible NOTICE The reversed phase protection detector of this pr...

Page 11: ...tor lower fan PS Switching power supply Q1DI Earth leakage circuit breaker field supply R1 R6 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger...

Page 12: ...4P385528 1 2014 08 Copyright 2014 Daikin 4P385528 1 0000000T...

Reviews: