background image

ENGLISH

This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented
down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are
to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.

• Labelling

This unit shall be labelled ‘de-commissioned and emptied of refrigerant’. This label shall be dated and signed. Ensure that there are
labels on the equipment stating the equipment contains flammable refrigerant.

• Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed.

– Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as

short as possible to minimise the amount of refrigerant contained in them.

–  Cylinders shall be kept upright.
–  Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
–  Label the system when charging is complete (if not already).
–  Extreme care shall be taken not to overfill the refrigeration system.

Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior
to commissioning. A follow up leak test shall be carried out prior to leaving the site.

Decommissioning

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is
recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample
shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before
the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:

•  mechanical handling equipment is available, if required, for handling refrigerant cylinders;
•  all personal protective equipment is available and being used correctly;
•  the recovery process is supervised at all times by a competent person;
•  recovery equipment and cylinders conform to the appropriate standards.

d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are

removed from site promptly and all isolation valves on the equipment are closed off.

k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

Recovery

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants
are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated
for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be
complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and,
if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall
be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good
working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine,
check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed
to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer
Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that
flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor
to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a
system, it shall be carried out safely.

14

Summary of Contents for Siesta ATXC20DV1B

Page 1: ...NDITIONER INSTALLATION MANUAL MODELS Installation Manual R32 Split Series ATXC20DV1B ARXC20DV1B ATXC25DV1B ARXC25DV1B ATXC35DV1B ARXC35DV1B ATXC50DV1B ARXC50DV1B ATXC60DV1B ARXC60DV1B ATXC71DV1B ARXC7...

Page 2: ...dz x z d z xz e d x e d x v d y d d d d C I H 3 9D 50A4 F w x d d P RaU SP_W bRa R NV TT d d d d v w x d g k d d d d d k j d d d d d d d U SR ZTSR TM RZRZTO u d d d d k x x d d v w x d dd d d J 8B GI...

Page 3: ...d d fv vd u vd vd f v v d v d vd d d d d d h i hk f d d d zdz x z d z xz e d x e d x v d y d d d d C I H 3 9D 50A4 F w x d d P RaU SP_W bRa R NV TT d d d d v w x d g k d d d d d k j d d d d d d d U SR...

Page 4: ...e wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or...

Page 5: ...ainage and insulate piping to prevent condensation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to specified method such as with a torqu...

Page 6: ...if any and find the site where remote controller signals are properly received by the indoor unit within 7 metres Outdoor Unit The outdoor unit should be sited in a place where The restrictions on ins...

Page 7: ...of work space below the ceiling surface Stop valve cover How to remove the stop valve cover Remove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve co...

Page 8: ...INDOOR UNIT ATXC60 71 y Recommended mounting plate retention spots 7 spots in all Place a leveler on these tabs Use a tape measure as shown Position the end of the tape measure at Z 117 126 5 65 65 49...

Page 9: ...guide How to replace the drain plug and drain hose Removal method Drain hose attachment position 1 Rotate to detach wire clip from hook on the right and remove The drain hose is on the back of the un...

Page 10: ...the marked area Front grille Bottom frame Mark rear side maintenance All dimensions are in mm at the lower part of the front grille to release the claws DRAIN PIPING Connect the drain hose as describ...

Page 11: ...pressure is applied to the terminal connectors and wires Make sure all the covers are properly fixed to avoid any gap Use round crimp style terminal for connecting wires to the power supply terminal b...

Page 12: ...s so that the evacuated condensate CANNOT freeze FLARING THE PIPE END 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe...

Page 13: ...bend radius Piping thickness Thermal insulation size Thermal insulation thickness Gas pipe Inter unit wire 6 4 1 4 30mm or more 9 5 3 8 30mm or more 12 7 1 2 40mm or more 15 9 5 8 50mm or more 19 1 3...

Page 14: ...rating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the refrigerant piping If...

Page 15: ...that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block Firmly fix the wires with the terminal screws Inter unit wire 4 core 60245 IEC 57 H07RN F 1 1 2...

Page 16: ...checks shall include that capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking there shall be no live electrical components and wiring are exposed while char...

Page 17: ...f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accordance with manufacturer s instructions h Do not overfill cylinders No...

Page 18: ...ation between the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interfac...

Page 19: ...peration Unit error Blinking OPERATING RANGE Heat Pump Model Model ATXC20 25 35 ARXC20 25 35 COOLING 50 46 43 40 30 HEATING 20 18 10 20 0 10 0 14 15 19 20 23 25 INDOOR TEMP CWB 10 15 20 10 15 20 25 27...

Page 20: ...ance devices of the unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING NOTICE Risk of electrostatic discharge Before performing any maintenance or service work touch a metal part of the unit in...

Reviews: