ENGLISH
WIRING
IMPORTANT :
*
The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.
**
The appropriate voltage range should be checked with label data on the unit.
Indoor Unit
Interconnection
Outdoor Unit
Terminal Block
cable
Terminal Block
L
N
Power Supply Cable
Power
Supply
There must be an all
pole disconnection in
the supply mains with
a contact separation of
at least 3mm.
N / L2
Fuse / Main L / L1
Circuit Switch
Breaker
• All wires must be firmly connected.
• Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
• The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.
• The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
• Make sure no external pressure is applied to the terminal connectors and wires.
• Make sure all the covers are properly fixed to avoid any gap.
• Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching to
the indication on terminal block. (Refer to the wiring diagram attached on the unit).
Attach insulation sleeve
Electric wire
Round crimp-style terminal
• Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
• Over tightening can damage the terminal screws.
• Do not connect wire of different gauge to same terminal.
• Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
Connect wires of the
same gauge to both sides.
Do not connect wires of the
same gauge to one side.
Do not connect wires
of different gauges.
8
1
2
3
1
2
3
Model
Indoor (ATXC)
20/25/35D 50/60/71D
Outdoor (ARXC)
20/25/35D 50/60/71D
Voltage range
**
220-240V/~/50Hz +
Power supply cable size
*
mm
2
Number of conductors
1.5
3
2.5
3
Interconnection cable size
*
mm
2
Number of conductors
1.5
4
1.5
4
Recommended fuse /
circuit breaker rating
**
A
16
16