background image

ENGLISH

*

1. Pipe length vs. vacuum pump run time

*

2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.

Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

PUMP DOWN OPERATION

In order to protect the environment, be sure to pump down when relocating or disposing

of the unit.

1) Remove the valve lids from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop forced cooling

Forced cooling operation

„

Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)

• Forced cooling operation will stop automatically after around 15 minutes.

To stop the operation, press the indoor unit ON/OFF switch.

CAUTION

Hexagonal

wrench

Close

Liquid stop valve

Gas stop valve

t

Service por

Valve lid

After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced cooling operation.

To pump down

DANGER: RISK OF EXPLOSION

Pump down - Refrigerant leakage

. If you want to pump down the system, and there is a leakage in the refrigerant circuit:

•  Do NOT use the unit’s automatic pump down function, with which you can collect all refrigerant from the system into

the outdoor unit. Possible consequence: Self-combustion and explosion of the compressor because of air going into the

operating compressor.

• Use a separate recovery system so that the unit’s compressor does NOT have to operate.

NOTICE

During pump down operation, stop the compressor before removing the refrigerant piping. If the compressor is still running

and the stop valve is open during pump down, air will be sucked into the system. Compressor breakdown or damage to the

system can result due to abnormal pressure in the refrigerant cycle.

11

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve.

Close it after 5 seconds, and check for gas leakage. Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and

valve rods. After the check is complete, wipe all soapy water off.

5) Remove covers from liquid stop valve and gas stop valve.

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump. (Keep this state for a few minutes to make sure that the compound

pressure gauge pointer does not swing back.)

*

2

.

3) Do vacuum pumping and make sure that the compound pressure gauge reads - 0.1MPa (- 760mmHg)

*

1

.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).

(High-pressure valve subsequently requires no operation.)

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

Pipe length

Up to 15 metres

More than 15 metres

Run time

Not less than 10 min.

Not less than 15 min.

Summary of Contents for Siesta ATXC20DV1B

Page 1: ...NDITIONER INSTALLATION MANUAL MODELS Installation Manual R32 Split Series ATXC20DV1B ARXC20DV1B ATXC25DV1B ARXC25DV1B ATXC35DV1B ARXC35DV1B ATXC50DV1B ARXC50DV1B ATXC60DV1B ARXC60DV1B ATXC71DV1B ARXC7...

Page 2: ...dz x z d z xz e d x e d x v d y d d d d C I H 3 9D 50A4 F w x d d P RaU SP_W bRa R NV TT d d d d v w x d g k d d d d d k j d d d d d d d U SR ZTSR TM RZRZTO u d d d d k x x d d v w x d dd d d J 8B GI...

Page 3: ...d d fv vd u vd vd f v v d v d vd d d d d d h i hk f d d d zdz x z d z xz e d x e d x v d y d d d d C I H 3 9D 50A4 F w x d d P RaU SP_W bRa R NV TT d d d d v w x d g k d d d d d k j d d d d d d d U SR...

Page 4: ...e wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or...

Page 5: ...ainage and insulate piping to prevent condensation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to specified method such as with a torqu...

Page 6: ...if any and find the site where remote controller signals are properly received by the indoor unit within 7 metres Outdoor Unit The outdoor unit should be sited in a place where The restrictions on ins...

Page 7: ...of work space below the ceiling surface Stop valve cover How to remove the stop valve cover Remove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve co...

Page 8: ...INDOOR UNIT ATXC60 71 y Recommended mounting plate retention spots 7 spots in all Place a leveler on these tabs Use a tape measure as shown Position the end of the tape measure at Z 117 126 5 65 65 49...

Page 9: ...guide How to replace the drain plug and drain hose Removal method Drain hose attachment position 1 Rotate to detach wire clip from hook on the right and remove The drain hose is on the back of the un...

Page 10: ...the marked area Front grille Bottom frame Mark rear side maintenance All dimensions are in mm at the lower part of the front grille to release the claws DRAIN PIPING Connect the drain hose as describ...

Page 11: ...pressure is applied to the terminal connectors and wires Make sure all the covers are properly fixed to avoid any gap Use round crimp style terminal for connecting wires to the power supply terminal b...

Page 12: ...s so that the evacuated condensate CANNOT freeze FLARING THE PIPE END 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe...

Page 13: ...bend radius Piping thickness Thermal insulation size Thermal insulation thickness Gas pipe Inter unit wire 6 4 1 4 30mm or more 9 5 3 8 30mm or more 12 7 1 2 40mm or more 15 9 5 8 50mm or more 19 1 3...

Page 14: ...rating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the refrigerant piping If...

Page 15: ...that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block Firmly fix the wires with the terminal screws Inter unit wire 4 core 60245 IEC 57 H07RN F 1 1 2...

Page 16: ...checks shall include that capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking there shall be no live electrical components and wiring are exposed while char...

Page 17: ...f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accordance with manufacturer s instructions h Do not overfill cylinders No...

Page 18: ...ation between the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interfac...

Page 19: ...peration Unit error Blinking OPERATING RANGE Heat Pump Model Model ATXC20 25 35 ARXC20 25 35 COOLING 50 46 43 40 30 HEATING 20 18 10 20 0 10 0 14 15 19 20 23 25 INDOOR TEMP CWB 10 15 20 10 15 20 25 27...

Page 20: ...ance devices of the unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING NOTICE Risk of electrostatic discharge Before performing any maintenance or service work touch a metal part of the unit in...

Reviews: