background image

Disposal requirement

NOTICE

Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste.

Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualified

installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery.

By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or

local authority for more information. Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.

ENGLISH

WARNING

    • All electrical wiring must not touch the water piping or any moving parts of the fan motors.
    • Confirm that the unit has been switched OFF before installing or servicing the unit.

• Disconnect from the main power supply before servicing the air conditioner unit.

•  DO NOT pull out the power cord when the power is ON.

This may cause serious electrical shocks which may result in fire hazards.

•  Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static.

Depending on the type and source of the electrical waves, static may be heard even when more than 1m away.

    • Do not use means to accelerate the defrosting process (if applicable) or to clean, other than those recommended by the manufacturer.
    • The appliance must be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater).
    • Do not pierce or burn.
    • Be aware that refrigerants may not contain an odour.

•  The appliance must be installed, operated and stored in a room with a floor area larger than Xm

2

(refer to Section “Special Precautions When Dealing With R32 Unit”).

In case it does not satisfy minimum floor area, it requires to install at good ventilation room.

•  NOTE: The manufacturer may provide other suitable examples or may provide additional information about the refrigerant odour.

CAUTION

•  Do not install the air conditioner at any place where there is danger of flammable gas leakage.

In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out.

•  While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate piping to prevent condensation.

Improper drain piping may result in indoor water leakage and property damage.

•  Tighten the flare nut according to specified method such as with a torque wrench.

If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage.

•  Do not overcharge the unit.

This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.

•  Ensure that the unit’s panel is closed after service or installation.

Unsecured panels will cause the unit to operate noisily.

•  Sharp edges and coil surfaces are potential locations which may cause injury hazards.

Avoid from being in contact with these places.

•  Before turning off the power supply set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit.

If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user.

•  Make sure to provide for adequate measure in order prevent that the outdoor unit be used as a shelter by small animals. Small animal making contact with electrical parts can cause malfunctions, smoke or fire.

Please instruct the customer to keep the area around the unit clean.

    • The temperature of refrigerant circuit will be high, please keep the inter-unit wiring away from copper pipes that are not thermally insulated.

• Only qualified personnel can handle, fill, purge and dispose of the refrigerant.

IMPORTANT

Important information regarding the refrigerant used

This product contains fuorinated greenhouse gases.
Do not vent gases into the atmosphere.
Refrigerant type: R32
GWP

(1)

value: 675

(1)

GWP = Global Warming Potential

1 Please fill in with indelible ink,

„

1

the factory refrigerant charge of the product,

„

2

the additional refrigerant amount charged in the field and

„

1

+

2

the total refrigerant charge

on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging
port (e.g. onto the inside of the service cover).

a Factory refrigerant charge: see unit name plate
b Additional refrigerant amount charged
c Total refrigerant charge

NOTICE

Contains fluorinated greenhouse gases

R32

1

=

GWP: 675

2

=

kg

kg

2

1

1

+

2

=

kg

GWP× kg =

1000

tCO eq

2

d Quantity of fluorinated greenhouse gases of the total refrigerant

charge expressed as tonnes CO

2

equivalent.

e GWP  =  Global warming potential

Applicable legislation on

fluorinated greenhouse gases

requires that the refrigerant charge of the unit is indicated both in weight and CO

2

equivalent.

 

 

 

Formula to calculate the quantity in CO

2

equivalent tonnes:

GWP value of the refrigerant × total refrigerant charge [in kg] / 1000

2 Fix the label on the inside of the outdoor unit. There is a dedicated place for it on the wiring diagram label.

2

Summary of Contents for Siesta ATXC20DV1B

Page 1: ...NDITIONER INSTALLATION MANUAL MODELS Installation Manual R32 Split Series ATXC20DV1B ARXC20DV1B ATXC25DV1B ARXC25DV1B ATXC35DV1B ARXC35DV1B ATXC50DV1B ARXC50DV1B ATXC60DV1B ARXC60DV1B ATXC71DV1B ARXC7...

Page 2: ...dz x z d z xz e d x e d x v d y d d d d C I H 3 9D 50A4 F w x d d P RaU SP_W bRa R NV TT d d d d v w x d g k d d d d d k j d d d d d d d U SR ZTSR TM RZRZTO u d d d d k x x d d v w x d dd d d J 8B GI...

Page 3: ...d d fv vd u vd vd f v v d v d vd d d d d d h i hk f d d d zdz x z d z xz e d x e d x v d y d d d d C I H 3 9D 50A4 F w x d d P RaU SP_W bRa R NV TT d d d d v w x d g k d d d d d k j d d d d d d d U SR...

Page 4: ...e wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or...

Page 5: ...ainage and insulate piping to prevent condensation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to specified method such as with a torqu...

Page 6: ...if any and find the site where remote controller signals are properly received by the indoor unit within 7 metres Outdoor Unit The outdoor unit should be sited in a place where The restrictions on ins...

Page 7: ...of work space below the ceiling surface Stop valve cover How to remove the stop valve cover Remove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve co...

Page 8: ...INDOOR UNIT ATXC60 71 y Recommended mounting plate retention spots 7 spots in all Place a leveler on these tabs Use a tape measure as shown Position the end of the tape measure at Z 117 126 5 65 65 49...

Page 9: ...guide How to replace the drain plug and drain hose Removal method Drain hose attachment position 1 Rotate to detach wire clip from hook on the right and remove The drain hose is on the back of the un...

Page 10: ...the marked area Front grille Bottom frame Mark rear side maintenance All dimensions are in mm at the lower part of the front grille to release the claws DRAIN PIPING Connect the drain hose as describ...

Page 11: ...pressure is applied to the terminal connectors and wires Make sure all the covers are properly fixed to avoid any gap Use round crimp style terminal for connecting wires to the power supply terminal b...

Page 12: ...s so that the evacuated condensate CANNOT freeze FLARING THE PIPE END 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe...

Page 13: ...bend radius Piping thickness Thermal insulation size Thermal insulation thickness Gas pipe Inter unit wire 6 4 1 4 30mm or more 9 5 3 8 30mm or more 12 7 1 2 40mm or more 15 9 5 8 50mm or more 19 1 3...

Page 14: ...rating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the refrigerant piping If...

Page 15: ...that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block Firmly fix the wires with the terminal screws Inter unit wire 4 core 60245 IEC 57 H07RN F 1 1 2...

Page 16: ...checks shall include that capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking there shall be no live electrical components and wiring are exposed while char...

Page 17: ...f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accordance with manufacturer s instructions h Do not overfill cylinders No...

Page 18: ...ation between the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interfac...

Page 19: ...peration Unit error Blinking OPERATING RANGE Heat Pump Model Model ATXC20 25 35 ARXC20 25 35 COOLING 50 46 43 40 30 HEATING 20 18 10 20 0 10 0 14 15 19 20 23 25 INDOOR TEMP CWB 10 15 20 10 15 20 25 27...

Page 20: ...ance devices of the unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING NOTICE Risk of electrostatic discharge Before performing any maintenance or service work touch a metal part of the unit in...

Reviews: