Components
Service manual
75
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Is the measured voltage on the PCB
correct?
Action
Yes
Return to
of the PCB and continue with the next
procedure.
No
Continue with the next step.
3
Check the power supply to the unit, see
127].
Does the unit receive power?
Action
Yes
Replace the main PCB, see
No
Adjust the power supply to the unit, see
To check the HAP LED of the main PCB
Prerequisite:
First check the power supply to the main PCB, see
1
Locate the HAP LED on the main PCB.
a
a
HAP LED
INFORMATION
Make sure the correct software is available on the PCB. If NOT, update using the
updater tool.
Does the HAP LED blink in regular
intervals (1 second ON/1 second OFF)?
Action
Yes
Return to
of the main PCB and continue with the
next procedure.
No
Replace the main PCB, see
To check if the correct spare part is installed
Prerequisite:
First perform all earlier main PCB checks, see
1
Visit your local spare parts webbank.